EAGLEHAWK NX CONTROLLER
BASIC OPERATION PROCEDURES
11
EN2Z-1053GE51 R0119
LEDs (4)
6 LEDs indicate operational statuses of the controller.
The following section gives an overview over the LEDs with the relevant operational
statuses of the controller.
Power LED (green)
Power LED Behavior Meaning
1 ON
Normal operation
2 OFF
Power supply not OK
Status / Alarm LED (red)
LED Behavior
Meaning
1 LED remains OFF after power-up
Normal operation
2 LED is lit continuously after power-up The controller has encountered a
hardware problem or
The application has a fault or
The controller has been powered up
without an application or
The operator has manually stopped the
application, e.g., using XW-Online. In
this case, the LED will light up 20
minutes after power-up without
application
3 LED flashes continuously with
following pattern:
4 x ON/OFF followed by pause
Sensor failure of analog input
5 LED flashes continuously with
following pattern:
7 x ON/OFF followed by pause
Communications failure on Panel Bus
Rx
,
Tx
RS485-1, Send (Tx) / Receive (Rx) LED (yellow)
RS485-1 LED Behavior
Meaning
1 Both LEDs are flickering
Normal operation, RS485-1
communication is functioning properly
2 Both LEDs are OFF
No Rs485-1 communication
3 Rx Led is flashing and Tx is OFF RS485-1 communication is switched off
but controller is receiving data from other
controllers
4 Tx Led is flashing and Rx is OFF Controller is trying to establish a
RS 485-1 connection but there is no
answer
,
Application LEDs (yellow)
LED Behavior
Meaning
1 LED is lit continuously
Platform is starting
LED is flashing
Platform is connected
2 LED is lit continuously
Station is starting
LED is flashing
Station is running
Operating Keys (5)
The operating keys provide the following functions: