APPLICATION

The C7772A series of Wallplate Temperature Sensors are 

designed to be used with the Excel 5000 family and other 

Honeywell controllers. The C7772F Series is designed to be 

used with the TB7600, TB7300, and TB7200 Series 

communicating thermostats and other controllers that require 

a 10K ohm NTC Type II sensor. The C7772G is designed to 

be used with WEBs-AX I/O modules and other controllers that 

require a 10K ohm NTC Type III sensor. The C7772 sensors 

provide a resistive output signal proportional to sensed room 

or space temperature. The C7772 is well suited for low-profile 

wall-mounted applications where durability and tamper-proof 

construction is desired, such as schools, prisons and 

institutions.

FEATURES

• Low profile when mounted on industry standard utility 

conduit box.

• Rugged, brushed stainless steel wallplate.
• Integral foam pad isolates wallplate sensor from conduit 

box.

• Insulated screw terminals ensure reliable field wiring 

connection.

• Models available with a variety of resistive temperature 

sensor elements.

Summary of Contents for C7772A

Page 1: ... and other controllers that require a 10K ohm NTC Type III sensor The C7772 sensors provide a resistive output signal proportional to sensed room or space temperature The C7772 is well suited for low profile wall mounted applications where durability and tamper proof construction is desired such as schools prisons and institutions FEATURES Low profile when mounted on industry standard utility cond...

Page 2: ...no appreciable drift thereafter No calibration of the device is possible Long term drift calibration maintenance through controller software is typically not necessary Humidity Ratings 5 to 95 rh non condensing Approvals National Electrical Code NEC Class II Fig 1 C7772 Dimensions in in mm INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could da...

Page 3: ...sized from 16 to 20 AWG depending on the application The maximum length of wire from a device to the wallplate sensor is 300 ft 91m NOTE Erratic temperature readings from a sensor can be caused by the wiring practices described below These must be avoided to assure proper operation 1 Do not route temperature sensor wiring with building power wiring next to control contactors near light dimming cir...

Page 4: ...ons are made Use an accurate thermometer of 1 F 0 5 C to measure the temperature at the sensor location To verify sensor accuracy use an ohmmeter to measure the resistance across the sensor wires and use Table 2 to check the accuracy of the specific model Table 2 Typical Resistance of Sensor Models Typical Resistance in ohms C7772A C7772F C7772G At 41 F 5 C 54 200 25 392 23 467 At 50 F 10 C 41 758...