C7189U REMOTE INDOOR SENSOR

3

69-1710EFS-1

WIRING

The sensor can be used to provide one remote sensor (see Fig. 6) or as a temperature averaging network with multiple 
sensors connected (see Fig. 7). The thermostat is not part of the average network.

CAUTION

ELECTRICAL HAZARD.

Can cause electrical shock or equipment damage. Disconnect power before wiring.

1.

Run the wire cable from the thermostat to the 
remote sensor location.

2.

Loosen screw terminals, insert wires into terminal 
block (polarity does not matter), then retighten 
screws.

3.

Push excess wire back into the wall opening.

4.

Plug the wall opening with non-flammable insulation 
to prevent drafts from affecting the sensor operation 
and replace the cover on the remote sensor.

5.

Connect the two wires to the thermostat's remote
sensor terminals (polarity does not matter) and
replace the thermostat back onto the wallplate. See 
Fig. 6.

Fig. 5. Terminal block wiring.

Fig. 6. Wiring a single C7189U Sensor.

Fig. 7. Wiring Multiple C7189U Sensors.

OPERATION

Once a remote indoor temperature sensor is connected to 
the thermostat, the thermostat's sensor is no longer used.  
The thermostat's installer setup should be modified to tell 
the thermostat that remote indoor temperature sensor(s) 
have been used. The Inside temperature reading on the 
thermostat's display will be the remote sensor(s) 
temperature location(s). See Fig. 8.

.

Fig. 8. Inside Temperature Reading on TH8000 Series 

Thermostat.

M24116

C7189 

RC 

Y2 

W2 

S2 

S1 

M19972A

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND 

OVERLOAD PROTECTION AS REQUIRED. 

IF MORE THAN ONE C7189 REMOTE SENSOR IS REQUIRED, 

REFER TO FIGURE 7.

WIRES MUST HAVE A CABLE SEPARATE FROM THE 

THERMOSTAT CABLE.

M19973

SENSORS MUST BE ARRANGED IN THIS
CONFIGURATION TO OPERATE CORRECTLY.

WIRES MUST HAVE A CABLE SEPARATE FROM THE 
THERMOSTAT CABLE.

1

2

Y2

W2

S2

1

1

2

C7189

C7189

C7189

C7189

Y2

W2

2

1

1

2

C7189

C7189

C7189

C7189

C7189

C7189

C7189

C7189

C7189

Heat On

SCHED

HOLD

CLOCK SCREEN

MORE

TUE

AM

FAN 

AUTO 

SYSTEM

HEAT

CHANGE FILTER UV LAMP HUMIDIFIER PAD 

Following

Schedule

Inside

Set To

M19974

Summary of Contents for C7189U

Page 1: ...perature location s Fig 1 C7189U Remote Indoor Sensor SPECIFICATIONS Operating Ambient Temperature Range 45 to 88 F 7 2 to 32 C Display Range 0 to 99 F 18 to 37 C Sensor Accuracy 1 5 F at 70 F 84 at 21 C Operating Relative Humidity 5 to 95 non condensing Finish White Resistance Characteristics Negative temperature coefficient NTC Resistance decreases as the temperature increases Dimensions in inch...

Page 2: ... Disconnect power before beginning installation Fig 2 Typical location for C7189U Sensor Remote Sensor Wallplate Installation Remove the cover from the remote sensor as shown in Fig 3 1 Pull wires through wire hole 2 Position wallplate on wall level and mark screw hole positions with pencil 3 Drill holes at marked positions then tap in supplied wall anchors 4 Place wallplate over anchors insert an...

Page 3: ...9U Sensor Fig 7 Wiring Multiple C7189U Sensors OPERATION Once a remote indoor temperature sensor is connected to the thermostat the thermostat s sensor is no longer used The thermostat s installer setup should be modified to tell the thermostat that remote indoor temperature sensor s have been used The Inside temperature reading on the thermostat s display will be the remote sensor s temperature l...

Page 4: ...on 2 Remove one wire from one of the sensor s wiring terminals Use an ohmmeter to measure the resis tance across the sensor Verify the sensor accu racy with the temperature resistance in Table 1 CALIBRATION The sensor is calibrated at the factory and cannot be recalibrated in the field Table 1 Sensor Resistance at Room Temperature Room Temperature Ohms of Resistance F C 40 4 4 22537 42 5 6 21516 4...

Page 5: ...nte à distance C7189U CARACTÉRISTIQUES TECHNIQUES Gamme de température ambiante de service 7 2 à 32 C 45 à 88 F Gamme d affichage 18 à 37 C 0 à 99 F Précision du capteur 0 84 à 21 C 1 5 F à 70 F Humidité relative de service 5 à 95 sans condensation Fini Blanc Caractéristiques de la résistance Coefficient de température négatif CTN La résistance diminue à mesure que la température augmente Encombre...

Page 6: ...rdement Fig 2 Emplacement type d un capteur C7189U Installation de la plaque murale du capteur à distance 1 Retirer le couvercle du capteur à distance comme l illustre la Fig 3 2 Faire passer les fils par l ouverture réservée aux fils 3 Placer la plaque murale sur le mur mettre de niveau et marquer au crayon l emplacement des trous de vis 4 À l aide d une perceuse percer les trous aux endroits mar...

Page 7: ...stat sur la plaque murale Voir la Fig 6 Fig 5 Raccordement au bornier Fig 6 Raccordement d un seul capteur C7189U Fig 7 Raccordement de plusieurs capteurs C7189U FONCTIONNEMENT Lorsqu un capteur à distance est raccordé au thermostat le capteur intégré au thermostat n est plus en service La configuration du thermostat devrait être modifiée pour indiquer au thermostat qu un ou plusieurs capteurs de ...

Page 8: ...l emplacement du capteur 2 Retirer un fil des fils des bornes de raccordement du capteur Mesurer la résistance du capteur à l aide d un ohmmètre Vérifier ensuite la précision du capteur en comparant avec la résistance température du tableau 1 ÉTALONNAGE Le capteur est étalonné en usine et ne peut être ré étalonné en clientèle Tableau 1 Résistance du capteur à la température ambiante Température am...

Page 9: ...teriores C7189U ESPECIFICACIONES Rango de temperatura ambiente de funcionamiento De 45 ºF a 88 ºF de 7 2 ºC a 32 ºC Rango de visualización De 0 ºF a 88 ºF de 18 ºC a 32 ºC Precisión del sensor 1 5 F a 70 F 0 84 C a 21 C Humedad relativa de funcionamiento Del 5 al 95 sin condensación Acabado Blanco Características de la resistencia Coeficiente de temperatura negativo NTC La resisten cia disminuye a...

Page 10: ...eléctrica Fig 2 Ubicación típica para el sensor C7189U Instalación de la placa para pared del sensor remoto Quite la cubierta del sensor remoto como se muestra en la Fig 3 1 Pase los cables a través el agujero para cables 2 Coloque a nivel la placa para pared en la pared y marque con un lápiz las posiciones para los tornillos 3 Haga los agujeros en las posiciones marcadas y después introduzca con ...

Page 11: ...para un sensor C7189U independiente Fig 7 Cableado para sensores C7189U múltiples FUNCIONAMIENTO Una vez que se conecta el sensor de temperatura para interiores al termostato el sensor del termostato no se utiliza más Es necesario modificar la configuración de instalación del termostato para indicarle a éste que se ha utilizado un sensor remoto de temperatura para interiores La lectura de la tempe...

Page 12: ...do el sensor 2 Extraiga un cable de uno de los teminales del cableado del sensor Use un ohmímetro para medir la resistencia del sensor Verifique la pre cisión del sensor con los valores de temperatura resistencia de la Tabla 1 CALIBRACION El sensor viene calibrado desde la fábrica y no se puede volver a calibrar en el lugar de la instalación Tabla 1 Resistencia del sensor a temperatura ambiente Te...

Reviews: