background image

3

62-3047

Fig. 4—Typical installations.

M9734

18 INCH

MINIMUM

Settings and Calibration

The T104F Control includes an adjustable range limit-

ing pin (order additional pins separately). The pin is fac-
tory-set to limit the low range of the control to the frost
protection (*) setting (see Fig. 5). The pin can be moved to
a different low or high limit setting and lock point, or it can
be removed. Use a second pin if both low and high limit
settings are desired.

Setting the Limit

To set a limit different from the factory setting, proceed

as follows:

1. Determine the desired temperature range limit or lock-

ing temperature. Select the appropriate number on the ad-
justment knob to match the desired temperature setting. See
Fig. 5.

Fig. 5—Temperature settings.

M9729

SCALE MARKING

ADJUSTMENT RANGE SETTING

OFF

OFF

PIN
POS.

TEMP.

RANGE

°F

TEMP.

RANGE

°C

6

0

1

1

PIN REQUIRED.

FACTORY SETTING.

*

*

2

3

4

5

6

43

8

46

12

54

16

61

20

68

23

73

26

79

6 - 26

16 - 26

OFF - 26

20

22

0 - 20

6 - 20

0 - 23

6 - 23

43 - 79

61 - 79

OFF - 79

68

72

0 - 68

43 - 68

0 - 73

43 - 73

3

NONE

4a

4b

4b

4b + *

5 + *

5

°C

°F

2

2

1

1

Summary of Contents for Braukmann T104F

Page 1: ...icatesthe68 F 20 C setpointlimit Highersettingsmay be made by holding in the button while turning The thermo staticsensorisprotectedbyasafetyspringagainsttempera tures to 125 F 52 C M9730 2 3 Specifications MATERIALS OF CONSTRUCTION Body Industrial grade plastics with low thermal conductivity Fastening Ring Plated brass Internal Parts Brass thermostat capsule other metals TEMPERATURE RANGE 43 to 7...

Page 2: ... VALVE BODIES V110E V110F Fig 3 T104A B C V Thermostatic Controls T104B T104C T104A T104V M9736 1 2 3 4 5 1 2 3 4 5 2 3 Installation IMPORTANT TheT104Fcanbemountedinsideanenclo sureifthesensorislocatedaminimumof3in 76mm beneath the heating coils in the cold air return Coil excess capillary tubing beneath and away from the heating coils Take care not to break kink or sharply bend the capillary tubi...

Page 3: ...gh limit settings are desired Setting the Limit To set a limit different from the factory setting proceed as follows 1 Determine the desired temperature range limit or lock ing temperature Select the appropriate number on the ad justment knob to match the desired temperature setting See Fig 5 Fig 5 Temperature settings M9729 SCALE MARKING ADJUSTMENT RANGE SETTING OFF OFF PIN POS TEMP RANGE F TEMP ...

Page 4: ...romthewhitemark unscrewthe head completely from the base and rethread the head to the base so that it is aligned with the white mark Turn the act uatorheadclockwiseuntiltheheadstops Completeremoval of the head from the base is required only if the actuator was previously dismantled NOTE Thedistancebetweentheactuatorheadandthestatic portion of the control should be approximately 3 8 in 9 mm 4 Turn ...

Page 5: ...y tube is broken kinked or bent sharply 3 Replace the control 4 Dirt or scale is under the seat preventing tight shutoff 4 Remove the control from the valve body allowing the valve to open fully and flush away scale and debris Reinstall the control and turn fully clock wise If the valve does not fully close remove con trol and cartridge using a cartridge changer tool or service socket isolate valv...

Page 6: ...nn Honeywell Braukmann Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in Germany www honeywell ca braukmann ...

Reviews: