Backflow Preventers

BA300

Backflow Preventer

with flanged connections

APPLICATION

Backflow preventers of this type are suitable for the 
protection of drinking water systems against back pressure, 
back flow and back syphonage.

Fluids up to and including liquid category 4 to EN 1717 are 
protected.

They can be used for residential buildings, industrial and 
commercial purposes within the scope of their specification.

The powder-coated ductile iron housing provides increased 
corrosion protection.

APPROVALS

DVGW

BELGAQUA

NF

KIWA

WRAS

SVGW

VdS (BA300-80ZVDS)

VA-ETA

SPECIAL FEATURES

Optimal protection of the drinking water supply system

Easy access to all internal components

Powder-coated inside and outside - Powder used is 
physiologically and toxicologically safe

Easy Maintenance due to optimized construction

Triple security - two check valves and a discharge valve 
separate the backflow preventer into three pressure 
zones

Few individual parts

Light weight

Standardised discharge connection

All materials are ACS approved

All materials are KTW approved

Approved by OTH (Hungary)

TECHNICAL DATA

Media

Medium: 

Drinking water

Connections/Sizes

Connection size: 

DN65 - DN200 

Discharge pipe connection: 

DN150 

Pressure values

Min. inlet pressure: 

1.5 bar 

Max. operating pressure: 

10.0 bar 

Operating temperatures

Max. operating temperature 
medium: 

65 °C (WRAS 60 °C)

Specifications

Installation position: 

Horizontal with discharge 
valve downwards 

Summary of Contents for BA300 Series

Page 1: ...L FEATURES Optimal protection of the drinking water supply system Easy access to all internal components Powder coated inside and outside Powder used is physiologically and toxicologically safe Easy Maintenance due to optimized construction Triple security two check valves and a discharge valve separate the backflow preventer into three pressure zones Few individual parts Light weight Standardised...

Page 2: ...ore and after backflow preventer Install backflow preventer downstream of the filter or strainer This protects the appliance against dirt Install in horizontal pipework with the discharge valve downwards Ensure good access Simplifies maintenance and inspection In order to avoid flooding it is recommended to arrange a permanent professionally dimensioned wastewater connection The installation envir...

Page 3: ... rate and the used connection size Connection sizes DN 65 80 100 150 200 inch 21 2 3 4 6 8 Min clearance above backflow preventer 650 mm 650 mm 650 mm 650 mm 650 mm Clearance from wall 160 mm 160 mm 160 mm 200 mm 200 mm 0 0 1 0 20 40 60 80 100 120 140 160 180 200 220 240 260 280 300 320 340 360 DN65 Flow V m3 h Pressure drop in valve Δp bar 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 1 1 1 2 1 3 1 4 1 5 1 6...

Page 4: ...er for connection size Accessories Overview F Parameter Values Connection size DN 65 80 100 150 200 Weight kg 23 9 32 7 44 6 70 9 114 1 Dimensions L 356 440 530 630 763 H 152 167 185 219 254 h 246 275 296 314 346 T 77 77 77 77 77 F 185 200 220 285 340 Nominal flow rate at Δp 1 0 bar m3 h 35 8 54 3 108 190 9 339 3 Discharge flow rates in the event of failure m3 h 35 35 35 35 35 BA300 A BA300 80ZVDS...

Page 5: ...ntrol line DN65 0904063 DN80 0904064 DN80 0904073 DN100 0904065 DN150 0904066 DN200 0904067 5 Sealing set DN65 0904068 DN80 0904069 DN100 0904070 DN150 0904071 DN200 0904072 Environmental Energy Solutions Honeywell GmbH Hardhofweg 74821 MOSBACH GERMANY Phone 49 6261 810 Fax 49 6261 81309 http ecc emea honeywell com Manufactured for and on behalf of the Environmental and Combustion Controls Divisio...

Reviews: