8. Maintenance

8.1 Inspection

8.1.1 Testing discharge valve

1. Procedure according to instruction of the test control 

unit TKA295 resp. TK295

8.1.2 Testing outlet check valve

1. Procedure according to instruction of the test control 

unit TKA295 resp. TK295

8.2 Maintenance

In accordance with DIN EN 1717 a regular mainte-
nance must be taken.

8.2.1 Cartridge insert

1. Close shut off valve on inlet
2. Release pressure on outlet side (e.g. through water 

tap)

1. Close shut off valve on outlet
2. Remove ball valve
3. Remove cover

4. Replace cartridge insert and lip seal 

5. Reassemble in reverse order

o push down the cartridge insert till it snaps in

6. Test function (see chapter inspection)

8.2.2 Check valve

1. Close shut off valve on inlet
2. Release pressure on outlet side (e.g. through water 

tap)

1. Close shut off valve on outlet
2. Remove ball valve
3. Remove cover
4. Exchange check valve

5. Test function (see chapter inspection)

9. Cleaning

If necessary, the cartridge insert can be cleaned.

1. Close shut off valve on inlet
2. Release pressure on outlet side (e.g. through water 

tap)

1. Close shut off valve on outlet
2. Remove ball valve
3. Remove cover
4. Clean or replace cartridge insert and lip seal

5. Reassemble in reverse order

o push down the cartridge insert till it snaps in

6. Test function (see chapter inspection)

We recommend a planned maintenance 
contract with an installation company

Maintenance of backflow preventer must be 
carried out by authorized personnel!

• Frequency: every 6 month (depending on 

local operating conditions)

• To be carried out by an installation company
• Inspection with a test control unit and mainte-

nance-set (see accessories)

Take note of the instructions of the test control 
unit TKA295 or TK295

Quick test for the discharge valve:
• Lower the inlet pressure

o if the discharge valve opens (it drops), the 

function is o.k.

Take note of the instructions of the test control 
unit TKA295 or TK295

We recommend a planned maintenance 
contract with an installation company

Frequency: every 1-3 years (depending on local 
operating conditions)
To be carried out by an installation company

• Don’t disassemble cartridge insert to indivi-

dual parts! 

Check valve will be destroyed after demounting

• To be carried out by an installation company
• To be carried out by the operator

Do not use any cleaning agents containing 
solvents or alcohol to clean the plastic parts!

Detergents must not be allowed to enter the 
environment or the sewerage system!

• Don’t disassemble cartridge insert to indivi-

dual parts! 

Summary of Contents for BA295I

Page 1: ...Instrukcja montażu Anleitung zum späteren Gebrauch aufbewahren Keep instructions for later use Conserver la notice pour usage ultérieur Zachowa instrukcj do pózniejszego wykorzystania Systemtrenner Backflow Preventer Disconnecteur Zespół odcinający T EBA BA295I Rev A ...

Page 2: ...e ca 0 6 mm Kartuscheneinsatz mit integriertem Rückflussver hinderer und Ablassventil Rückflussverhinderer ausgangsseitig 3 Kugelhähne zum Anschluss eines Differenzdruck manometers Ablaufanschluss 6 Varianten 7 Montage 7 1 Einbauhinweise Vor und nach dem Systemtrenner Absperrventile vorsehen Einbau in waagrechte Rohrleitung mit Ablassventil nach unten Auf gute Zugänglichkeit achten o Vereinfacht W...

Page 3: ... zapfen 3 Absperrarmatur ausgangsseitig schließen 4 Kugelhahn abschrauben 5 Abdeckung abschrauben 6 Kartuscheneinsatz und Nutring entnehmen und reinigen 7 Montage in umgekehrter Reihenfolge o Kartusche eindrücken bis sie einrastet 8 Funktion überprüfen siehe Kapitel Inspektion Wir empfehlen einen Wartungsvertrag mit einem Installationsunternehmen abzuschließen Instandhaltung von Systemtrennern dar...

Page 4: ...ebung Ablassventil öffnet ohne ersicht lichen Grund Druckschläge im Wassernetz Vor Systemtrenner einen Druckminderer einbauen Schwankender Vordruck Vor Systemtrenner einen Druckminderer einbauen Kartuscheneinsatz ist verschmutzt Kartuscheneinsatz ausbauen und reinigen Ablassventil schließt nicht Ablagerungen am Ventilsitz Kartuscheneinsatz ausbauen und reinigen oder ersetzen Beschädigter O Ring Ka...

Page 5: ...x 16 bar mit Klarsichtsiebtasse 25 bar mit Messingsiebtasse Hinterdruck 1 5 6 bar A Klarsichtsiebtasse bis 40 C 16 bar B Messingsiebtasse bis 70 C 25 bar TK295 Druck Prüfset Elektronisches Druckmessgerät mit Digital anzeige Batterie betrieben Mit Koffer und Zubehör ideal zur Inspektion und Wartung der Systemtrenner BA TKA295 Druck Prüfset Analoges Druckmessgerät mit Differenzdruckanzeige Mit Koffe...

Page 6: ...l check valve and discharge valve Outlet check valve Three ball valves for the connection of a differential pressure gauge Discharge connection 6 Options 7 Assembly 7 1 Installations Guidelines Install shutoff valves before and after backflow preventer Install in horizontal pipework with the discharge valve downwards Ensure good access o Simplifies maintenance and inspection Backflow preventers of...

Page 7: ...e cover 4 Clean or replace cartridge insert and lip seal 5 Reassemble in reverse order o push down the cartridge insert till it snaps in 6 Test function see chapter inspection We recommend a planned maintenance contract with an installation company Maintenance of backflow preventer must be carried out by authorized personnel Frequency every 6 month depending on local operating conditions To be car...

Page 8: ...reason Pressure strokes in water supply system Install a pressure reducing valve upstream the backflow preventer Fluctuating inlet pressure Install a pressure reducing valve upstream the backflow preventer Cartridge insert is contaminated Remove cartridge insert and exchange it Discharge valve don t close Deposits on valve seat Remove cartridge insert and clean or exchange it Damaged o ring Remove...

Page 9: ...brass filter bowl 25 bar outlet pressure range 1 5 6 0 bar A With clear filter bowl up to 40 C 16 bar B With brass filter bowl up to 70 C 25 bar TK295 Test kit Electronic pressure measuring device with digital indicator battery operated With case and accessories ideal for inspec tion and maintenance of backflow preventer type BA TKA295 Test kit Analogue pressure measuring device with differential ...

Page 10: ...c clapet anti retour et soupape de vidange intégrés Clapet anti retour côté sortie 3 robinets à boisseau sphérique pour le raccorde ment d un manomètre de pression différentielle Raccordement de sortie 6 Variantes 7 Montage 7 1 Dispositions à prendre Prévoir une valve d arrêt avant et après le sépara teur du système Montage dans les conduites horizontales avec une valve d écoulement vers le bas Ve...

Page 11: ...uriser le côté sortie ouverture du robinet de purge etc 3 Fermer le robinet de fermeture du côté sortie 4 Dévisser le robinet à boisseau sphérique 5 Dévisser le couvercle 6 Retirer la cartouche et la bague et nettoyer 7 Montage dans l ordre inverse o Appuyer sur la cartouche jusqu à ce qu elle s enclenche 8 Contrôler le fonctionnement voir chapitre Inspec tion Nous recommandons de souscrire à un c...

Page 12: ...utorisées 10 Défaut recherche de panne Panne Cause Remède Le clapet de décharge s ouvre sans raison manifeste Coups de bélier sur le réseau d eau Monter un régulateur de pression en amont du disconnecteur Variations de la pression d admission Monter un régulateur de pression en amont du disconnecteur Cartouche sale Retirer la cartouche et la nettoyer Le clapet de décharge ne ferme pas Dépôts sur l...

Page 13: ...6 bar B pot de décantation en laiton jusqu à 70 C 25 bar TK295 Kit de contrôle de pression Manomètre électronique avec affichage numérique à pile Avec mallette et acces soires idéal pour l inspection et l entretien des disconnecteurs BA TKA295Kit de contrôle de pression Manomètre analoque avec affichage de pres sion différentielle Avec mallette et acces soires idéal pour l inspection et l entretie...

Page 14: ...em przeciwzwrotnym i zaworem spustowym Zaworu przeciwzwrotnego na wyjściu 3 zawory kulowe do przyłączenia manometru rżnicowego przyłącza spustowego 6 Warianty 7 Montaż 7 1 Zamontowanie Przed i za oddzielaczem systemowym należy przewidzieć zawory odcinające Montaż w poziomym przewodzie rurowym z zaworem spustowym skierowanym w dół Zwrócić uwagę na dobry dostęp o Ułatwia konserwację i przeglądy W ze...

Page 15: ...3 Zamknąć armaturę odcinającą po stronie wylotowej 4 Odkręcić zawr kulowy 5 Odkręcić pokrywę 6 Wyjąć wkład kartuszowy z pierścieniem rowkowanym i oczyścić 7 Montaż w odwrotnej kolejności o Wciskać kartusz aż do zakleszczenia 8 Sprawdzić działanie zob rozdziaą Przegląd Zalecamy zawarcie umowy konserwacyjnej z odpowiednią firmą instalacyjną Utrzymywanie oddzielaczy systemowych w staniesprawnościmoże...

Page 16: ...ez wyraźnej przyczyny Uderzenie ciśnienia w sieci wodnej Zainstalować przed izolatorem reduktor ciśnienia Zmienne ciśnienie wstępne Zainstalować przed izolatorem reduktor ciśnienia Wkład kartuszowy jest zabrudzony Wymontować i oczyścić wkład kartuszowy Zawór spustowy nie zamyka Osad przy przy gnieździe zaworu Wymontować i oczyścić lub wymienić wkład kartuszowy Uszkodzony pierścień typu O ring Wymo...

Page 17: ...ar z mosiężną obudową filtra ciśnienie wylotowe 1 5 ń 6 barA przezroczysta obudowa filtra do 40 C 16 barB mosiężna obudowa filtra do 70 C 25 bar TK295 Zestaw testowy Elektroniczny przyrząd pomiarowy z cyfrowym wyświetlaczem zasilany z baterii Z futerałem i akcesoriami idealny do przeprowadzania przeglądów i konserwacji zespołów odcinających BA TKA295Zestaw testowy Analogowy przyrząd pomiarowy z cy...

Page 18: ...Honeywell GmbH 18 MU1H 1234GE23 R0812 PL ...

Page 19: ...MU1H 1234GE23 R0812 19 Honeywell GmbH PL ...

Page 20: ... 49 6261 81309 http ecc emea honeywell com Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl Z A La Pièce 16 1180 Rolle Switzerland by its Authorised Representa tive Honeywell GmbH EN0H 1234GE23 R0812 Subject to change 2012 Honeywell GmbH ...

Page 21: ...MU1H 1234GE23 R0812 Honeywell GmbH 7 2 2 8 1 1 8 1 2 8 2 1 8 3 4 6 5 8 2 2 5 4 6 ...

Page 22: ...leaning 7 10 Disposal 8 11 Troubleshooting 8 12 Spare Parts 9 1 Consignes de sécurité 10 2 Description fonctionnelle 10 3 Mise en oeuvre 10 4 Caractéristiques 10 5 Contenu de la livraison 10 6 Variantes 10 7 Montage 10 8 Maintenance 11 9 Matériel en fin de vie 12 10 Défaut recherche de panne 12 11 Pièces de rechange 13 12 Accessoires 13 1 WskazÛwki bezpieczeDstwa 14 2 Opis funkcji 14 3 Zastosowani...

Reviews: