AQS51/61-KAM  COMBINED CO

2

-/TEMPERATURE  DUCT SENSOR/CONTROLLER

EN0B-1023 GE02R0500

6

Pin

Jumper

Marked

Function

1
2
3

AN1

Current
Current/Voltage
Voltage

Pin 1 and 2 provides 0(4)...20mA for OUT1

Pin 2 and 3 provides 0(2)...10Vdc for OUT1

4
5
6

AN2

Current
Current/Voltage
Voltage

Pin 4 and 5 provides 0(4)...20mA for OUT2

Pin 5 and 6 provides 0(2)...10Vdc for OUT2

7-8
9-10

OUT

20 - 100%
0 - 100%

Pin 7 and 8 provides 2...10Vdc or 4...20mA
Pin 9 and 10 provides 0...10Vdc or 0...20mA

Table 1  Jumper selections

WIRING

Connection Terminal

Function

Electrical Data

Remarks

G+

Power+

24Vac/dc+

Internal rectifying diode

G0

Power ground (-)

24Vac/dc-

(see Note 1!)

OUT1

Analogue output 1 (+)

0...10Vdc, 0...20mA,

According to OUT, AN1

2...10Vdc, 4...20mA

jumper positions

OUT2

Analogue output 2 (+)

0...10Vdc, 0...20mA,

According to OUT, AN2

2...10Vdc, 4...20mA

jumper positions

M

Signal ground (-)

Protected by PTC resistor

NC

CM

Normally closed

Common relay terminal

NO

Normally open

Table 2  Electrical terminal connections

NOTE1: The ground terminal is used as negative power

supply DC input or AC phase ground G0 (halfwave

rectifier). The signal ground M, protected by a PTC

resistor, is the same as power ground G0

(permitting a “3-wire” configuration). A single

transformer may be used for the entire system.

Situations can occur where different transformers

must be used.

NOTE2: AQS51/61 can supply both a voltage or a current

output for OUT1/OUT2. To change between

voltage and current output mode the hardware

jumpers have to be set in accordance. There is

one jumper for AN1 and one for AN2, so that one

output can be a voltage output and the other a

current output. Both voltage output and current

output can be 0...100% (0...10 Vdc or 0...20 mA)

or 20...100% (2...10 Vdc or 4...20 mA) The same

percentage are used for both outputs, see Table 1.

Wiring should be done only according to the actual job wiring

diagrams or above wiring list. All wiring must conform to

applicable codes, ordinances and regulations.

Electric discharge may damage the sensor electronics.

Therefore handle the unit carefully and avoid electrostatic

discharge.

Do not connect the power supply unless all other connections

and settings are correctly done.

The AQS51/61 signal ground (M) is not galvanically

separated from the power supply. If the analog output signals

are connected to controllers or DDC system, the same

ground potential has to be used or install separate

transformers for sensor and controller/DDC system.

Potential free contact
relay
1mA/5V up to
1A/50Vac/24Vdc

Triggered by register
OUT3

Summary of Contents for AQS51-KAM

Page 1: ...s analog output configuration the software program STRATEGY is available which is part of the User Interface Program Software package AQS USP22 used for re calibration change of the measurement range or other service or set up purposes The switching setpoint and differential of the relay output for CO2 limit monitoring or plant system ON OFF control can be adjusted within the measurement range Thi...

Page 2: ...D indication Yellow Maintenance required Red Relay activated Power up time 1 min Ambient operating limits Temperature 0 50 C General Humidity 0 95 rh non condensing Operating principle Non dispersive infrared NDIR Gas sampling mode Diffusion and 3 mm gas inlet push on barb Response time 2 min diffusion or 10 sec 0 2 ltr min gas flow Measurement range 0 3000 ppm Converting range 0 2000 ppm 0 10 Vdc...

Page 3: ...using the PC software STRATEGY Version 3 Digital relay output Single pole double throw SPDT switching potential free contact Factory adjusted switching setpoint and differential 1A 50 Vac 50VA or 1 A 24 Vdc 30 W Relay activated 1000 ppm Relay deactivated 900 ppm Sensor housing 84 x 142 x 46 mm Dimensions Sampling probe 203 mm Zigzag traces accessible after removing the cover Shortage with a screwd...

Page 4: ...ions to provide different ventilation control strategies All sensor measurements can be addressed to these functions and mixed together by this software to form two independent and intelligent P I controllers The relay output contact CM NO is closed if the CO2 level exceeds the factory adjusted limit of 1000ppm and the contact CM NC is closed if the CO2 level is equal or below 900ppm These paramet...

Page 5: ...Pos 7 cable entry bushings To make a hole insert a screwdriver into the groove and hit firmly Mount for each cable a cable entry bushing into the aspiration box and seal properly 7 Mounting the aspiration box to the sampling probe is performed by a snap in bayonet fitting Pos 10 Insert first the temperature sensor placed on the end of a 150mm long soldered on lead Fig 3 Pos 2 into the air inlet to...

Page 6: ...G0 permitting a 3 wire configuration A single transformer may be used for the entire system Situations can occur where different transformers must be used NOTE2 AQS51 61 can supply both a voltage or a current output for OUT1 OUT2 To change between voltage and current output mode the hardware jumpers have to be set in accordance There is one jumper for AN1 and one for AN2 so that one output can be ...

Page 7: ...2 Error code 3 CO2 concentration in ppm 4 Temperature in C 5 OUT1 value full scale 6 OUT2 value full scale To access the maintenance level short at level 5 OUT1 value ENTER MENU ENTER in sequence The maintenance mode is restricted to competent trained service personnel only For detailed information see the Service Checkout Instruction EN2B 0461GE02 LED Signals The standard sensor has two different...

Page 8: ...sor probes are checked against failure by checking the valid dynamic measurement ranges Error Code and Actions Error Code Suggested Action 4 Indicate problems with the power supply Check power supply voltage 8 Indicates problem with OUT1 Could be too high an output load connected to the output Check OUT1 with a voltmeter and compare the output with the LCD reading for AQS61 KAM Disconnect the outp...

Reviews: