Minimum Air Setpoint

This parameter is available only when the thermostat is configured in A or AF 
mode (see page 19).

Maximum Air Setpoint

This parameter is available only when the thermostat is configured in A or AF 
mode (see page 19).

Minimum Floor Setpoint

This parameter is available only when the thermostat is configured in F mode 
(see page 19).

Maximum Floor Setpoint

This parameter is available only when the thermostat is configured in F mode 
(see page 19).

Default setting

41 °F (5 °C)

Range

41 °F (5 °C) to 100 °F (38 °C)

Default setting

100 °F (38 °C)

Range

41 °F (5 °C) to 100 °F (38 °C)

Default setting

41 °F (5 °C)

Range

41 °F (5 °C) to 100 °F (38 °C)

Default setting

100 °F (38 °C)

Range

41 °F (5 °C) to 100 °F (38 °C)

400-146-001-A_69-2245EF (AQ1000TP2) ENG.fm  Page 21  Wednesday, June 18, 2008  2:32 PM

Summary of Contents for AQ1000TP2 - Programmable Hydronic Communicating Thermostat

Page 1: ...OWNER S GUIDE Place Bar Code Here 7 day Programmable Hydronic Thermostat AQ1000TP2 400 146 001 A_69 2245EF AQ1000TP2 ENG fm Page 2 Wednesday June 18 2008 2 32 PM ...

Page 2: ...Care toll free at 1 800 468 1502 Read and save these instructions U S Registered Trademark Patents pending 6 08 Honeywell International Inc All rights reserved IMPORTANT This thermostat is to be used with an AQ2000 Series hydronic control panel 400 146 001 A_69 2245EF AQ1000TP2 ENG fm Page 1 Wednesday June 18 2008 2 32 PM ...

Page 3: ...he fan On Auto mode 6 Setting the clock and date 7 Default schedule 9 New schedule 10 Modifying the schedule 11 User s configuration menu 14 Alert messages 17 Installer s section Installation 18 Configuration switches 19 Installer s configuration menu 20 Appendix Technical specifications 23 2 year limited warranty 24 Table of contents 400 146 001 A_69 2245EF AQ1000TP2 ENG fm Page 0 Wednesday June ...

Page 4: ...uto or On mode see page 6 Programmable schedule The thermostat can be programmed to use up to 4 periods per day Each of the 28 periods for the week can have its own start time and temperature setpoints see page 9 Thermostat modes The thermostat can be placed in any of the following modes see page 4 In Hold mode the setpoint must be set manually In Run mode the setpoint is adjusted according to the...

Page 5: ...r button Fan button System button Hold Run button Fan On Auto mode System Heat Cool mode Thermostat Hold Run mode Temperature up and down buttons Keypad is locked Outdoor temperature Heating is on Cooling is on Day 400 146 001 A_69 2245EF AQ1000TP2 ENG fm Page 2 Wednesday June 18 2008 2 32 PM ...

Page 6: ...on is made to any of the thermostats configured for ALL ZONES scheduling all the other thermostats will adopt the schedule of that thermostat Setting the Temperature manually The thermostat displays the actual measured temperature of the zone To display the setpoint temperature press the or button once The setpoint will be displayed for the next 5 seconds SET HEAT or SET COOL appears at the same t...

Page 7: ...e or after 2 hours if the thermostat was in Vacancy mode Unoccupied Setback Mode The thermostat can be placed to Unoccupied mode from Hold mode only When the Unoccupied mode is activated by the hydronic control panel the temperature setpoint is lowered in heat mode or raised in cool mode by a setback margin The margin is set in the user s configuration menu see page 14 The thermostat cannot be pla...

Page 8: ...is in heat mode it becomes the heating setpoint and the cooling setpoint is equal to the heating setpoint plus 2 F 1 C If you set the temperature when the thermostat is in cool mode it becomes the cooling setpoint and the heating setpoint is equal to the cooling setpoint minus 2 F 1 C Off All cooling and heating are off Setting the system Heat Cool mode SYSTEM button System mode indicator A thermo...

Page 9: ...utton to place the fan in one of the two following modes of operation On mode The fan runs all the time Auto mode The fan runs only during a call for heat or cool Setting the fan On Auto mode FAN button Fan mode indicator 400 146 001 A_69 2245EF AQ1000TP2 ENG fm Page 6 Wednesday June 18 2008 2 32 PM ...

Page 10: ...lock and date n Press the Menu button o Press CLOCK p Press the or button to set the time A Press and hold the button to scroll faster Press NEXT B 400 146 001 A_69 2245EF AQ1000TP2 ENG fm Page 7 Wednesday June 18 2008 2 32 PM ...

Page 11: ...T B s Press the or button to set the day A Press the Menu button B to exit NOTE If you do not press any button for a period of 60 seconds the thermostat will automatically end the clock and date programming after saving all modifications 400 146 001 A_69 2245EF AQ1000TP2 ENG fm Page 8 Wednesday June 18 2008 2 32 PM ...

Page 12: ... thermostat s default schedule shown below Default schedule Monday to Friday Saturday Sunday Period Start Time Heat setpoint Cool setpoint Start Time Heat setpoint Cool setpoint WAKE 6 00 AM 70 F 21 0 C 78 F 25 5 C 6 00 AM 70 F 21 0 C 78 F 25 5 C LEAVE 8 00 AM 62 F 16 5 C 85 F 29 5 C RETURN 6 00 PM 70 F 21 0 C 78 F 25 5 C SLEEP 10 00 PM 62 F 16 5 C 82 F 28 0 C 10 00 PM 62 F 16 5 C 82 F 28 0 C The ...

Page 13: ...ng setpoint is always at least 2 F 1 C lower than the cooling setpoint For example if the heating setpoint is at 77 F 25 C and you lower the cooling setpoint to 78 F 25 5 C the heating setpoint will automatically be adjusted to 76 F 24 5 C New schedule MO TU WE TH FR SA SU WAKE Time Heat Cool LEAVE Time Heat Cool RETURN Time Heat Cool SLEEP Time Heat Cool 400 146 001 A_69 2245EF AQ1000TP2 ENG fm P...

Page 14: ...stat will be applied to other thermostats see page 19 As soon as you select ALL DAYS the displayed settings start time heating setpoint and cooling setpoint will be applied to the displayed period for all 7 days Afterwards if you wish to modify the settings for a specific day you can then select DAILY select the day and make the modifications for that day 400 146 001 A_69 2245EF AQ1000TP2 ENG fm P...

Page 15: ...lt settings r Press the or button to set the start time A Press and hold the button to scroll faster Press NEXT B To skip a period erase the settings for that period For example if you wish to use the Wake and Sleep periods only as programmed for the weekend in the default schedule erase the Leave and Return periods 400 146 001 A_69 2245EF AQ1000TP2 ENG fm Page 12 Wednesday June 18 2008 2 32 PM ...

Page 16: ...f necessary go back to step 3 to set another day or step 4 to set another period To exit press the Menu button NOTE If you do not press any button for a period of 60 seconds the thermostat will automatically exit the schedule programming after saving all modifications 400 146 001 A_69 2245EF AQ1000TP2 ENG fm Page 13 Wednesday June 18 2008 2 32 PM ...

Page 17: ...s will appear in the order shown in the following table Parameter descriptions can be found on page 15 User s configuration menu Parameter Default setting Options Temperature display mode Automatic Automatic F C Temperature setback 7 F 4 C 0 to 16 F 0 to 9 C Permanent backlight Off On Off Time display format 12 hours 12 hours 24 hours Automatic Daylight savings time Off On Off 400 146 001 A_69 224...

Page 18: ...thermostat displays the temperature in the selected format regardless of the format specified in the AQ2000 control panel Temperature Setback Amount When the Unoccupied mode is activated by the programmable AQ2000 control panel the temperature setpoint is set back lowered in heat mode or raised in cool mode Use this parameter to specify the amount of temperature setback 400 146 001 A_69 2245EF AQ1...

Page 19: ...ressed Time Display Format Use this parameter to select between the 12 hour format and the 24 hour format Automatic Daylight Savings Time When Automatic Daylight Savings Time is enabled On the thermostat automatically switches to daylight savings time on the second Sunday of March and reverts back to normal time on the first Sunday of November 400 146 001 A_69 2245EF AQ1000TP2 ENG fm Page 16 Wedne...

Page 20: ...defective The floor sensor may also be defective if the thermostat has been configured for F mode see page 19 Cooling or heating has stopped When the thermostat has been configured for AF mode see page 19 FLOOR will flash if the floor sensor is defective or not installed The thermostat will still control the ambient air temperature but will ignore the floor temperature limits Alert messages 400 14...

Page 21: ... will vary according to the wire size For example for 22 AWG use a maximum of 500 ft 150 m 4 If necessary set the configuration switches see page 19 5 Re install the faceplate to the wallplate and secure with the captive screw NOTE For optimal comfort control in the zone keep the thermostat s air vents clean and unobstructed at all times to ensure adequate air flow through the thermostat Installat...

Page 22: ...stats Installer s Configuration Menu switch 2 Use DIP switch 2 to place the thermostat in either Installer or User mode Set to Installer mode to access the installation parameters Otherwise leave it in User mode A F AF Regulation Mode switches 3 4 Use DIP switches 3 and 4 to select the regulation mode Configuration switches A mode controls and displays the Ambient air temperature AIR will appear o...

Page 23: ...first parameter is displayed NOTE See pages 21 and 22 for descriptions of the Installer s configuration parameters 4 To modify a parameter press the or button 5 To save any modification and view the next or previous parameter press NEXT or PREVIOUS 6 To exit the menu return DIP switch 2 to the down position User mode NOTE If you exit the menu without first pressing PREVIOUS or NEXT any modificatio...

Page 24: ...is available only when the thermostat is configured in F mode see page 19 Maximum Floor Setpoint This parameter is available only when the thermostat is configured in F mode see page 19 Default setting 41 F 5 C Range 41 F 5 C to 100 F 38 C Default setting 100 F 38 C Range 41 F 5 C to 100 F 38 C Default setting 41 F 5 C Range 41 F 5 C to 100 F 38 C Default setting 100 F 38 C Range 41 F 5 C to 100 F...

Page 25: ...e floor temperature is equal to this setting or below Maximum Floor Limit This parameter is available only if the thermostat is configured in AF mode see page 19 Heating is disabled regardless of setpoint if the floor temperature is equal to this setting or above Default setting 41 F 5 C Range between the minimum and maximum setpoints Default setting 81 F 27 C Range between the minimum and maximum...

Page 26: ...rature display range 58 F to 212 F 50 C to 100 C Display resolution 1 0 F 0 5 C Operating temperature 4 F to 130 F 20 C to 55 C Storage temperature 20 F to 130 F 30 C to 55 C Humidity rating 5 to 90 RH non condensing at 95 F 35 C Controller type Proportional Integral PI Memory type All settings are stored in non volatile memory and are not erased during a power outage Technical Specifications 400 ...

Page 27: ...ase to the place from which you purchased it or ii call Honeywell Customer Care at 1 800 468 1502 Customer Care will make the determination whether the product should be returned to the following address Honeywell Return Goods Dock 4 MN10 3860 1885 Douglas Dr N Golden Valley MN 55422 or whether a replacement product can be sent to you This warranty does not cover removal or reinstallation costs Th...

Page 28: ...THE DURATION OF ANY IMPLIED WARRANTIES INCLUDING THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE IS HEREBY LIMITED TO THE TWO YEAR DURATION OF THIS WARRANTY Some states do not allow limitations on how long an implied warranty lasts so the above limitation may not apply to you This warranty gives you specific legal rights and you may have other rights which vary from state to...

Page 29: ...Place Bar Code Here GUIDE DU PROPRIÉTAIRE Thermostat hydronique programmable 7 jours AQ1000TP2 400 146 001 A_69 2245EF AQ1000TP2 FRE fm Page 2 Wednesday June 18 2008 2 34 PM ...

Page 30: ...uillez consulter le http yourhome honeywell com ou joindre le service à la clientèle en composant sans frais le 1 800 468 1502 Veuillez lire le guide et le conserver en lieu sûr Marque de commerce enregistrée aux États Unis Brevets en instance 6 08 Honeywell International inc Tous droits réservés 400 146 001 A_69 2245EF AQ1000TP2 FRE fm Page 1 Wednesday June 18 2008 2 34 PM ...

Page 31: ...e du ventilateur ON AUTO 6 Réglage de l horloge et de la date 7 Horaire par défaut 9 Nouvelle horaire 10 Modification de l horaire 11 Menu de configuration de l utilisateur 14 Messages d alerte 17 Section de l installateur Installation 18 Sélecteurs de configuration 19 Menu de configuration de l installateur 20 Annexe Fiche technique 23 Garantie limitée de 2 ans 24 Table des matières 400 146 001 A...

Page 32: ...6 Horaire programmable Le thermostat peut être programmé pour utiliser jusqu à 4 périodes par jour Chacune des 28 périodes pour toute la semaine peut avoir ses propres heures de début et températures de consigne voir la page 9 Sélection du mode du thermostat Le thermostat peut être mis dans n importe quel des modes suivants voir la page 4 En mode HOLD dérogation permanente la consigne doit être ré...

Page 33: ...AN bouton SYSTEM bouton HOLD RUN mode du ventilateur ON AUTO mode du système HEAT COOL mode du thermostat HOLD RUN Boutons de température haut et bas clavier verrouillé température extérieure le chauffage est activé la climatisation est activée jour 400 146 001 A_69 2245EF AQ1000TP2 FRE fm Page 2 Wednesday June 18 2008 2 34 PM ...

Page 34: ...e modification sera apportée à n importe quel thermostat configuré pour la programmation globale tous les autres thermostats adopteront la programmation de ce thermostat Réglage manuel de la température Le thermostat affiche la température mesurée de la zone Pour afficher la température de consigne appuyer une fois sur le bouton ou La consigne s affichera pendant les 5 prochaines secondes SET HEAT...

Page 35: ... le thermostat était en mode Vacance Mode SETBACK inoccupé On ne peut mettre le thermostat en mode Inoccupé qu à partir du mode HOLD Lorsque le mode Inoccupé est activé par le panneau de commande hydronique la température de consigne est abaissée en mode chauffage ou augmentée en mode climatisation par une marge de recul La marge est réglée à partir du menu de configuration de l utilisateur voir l...

Page 36: ...e ci devient la consigne de chauffage et la consigne de climatisation est égale à la consigne de chauffage plus 1 C 2 F Si vous réglez la température lorsque le thermostat est en mode climatisation celle ci devient la consigne de climatisation et la consigne de chauffage est égale à la consigne de climatisation moins 1 C 2 F OFF arrêt Le chauffage et la climatisation sont désactivés Sélection du m...

Page 37: ...un des deux modes de fonctionnement suivants Mode ON continu Le ventilateur fonctionne sans arrêt Mode AUTO automatique Le ventilateur fonctionne seulement lors d une demande de chauffage ou de climatisation Sélection du mode du ventilateur bouton FAN indicateur de mode du ventilateur 400 146 001 A_69 2245EF AQ1000TP2 FRE fm Page 6 Wednesday June 18 2008 2 34 PM ...

Page 38: ...sur le bouton Menu o Appuyer sur CLOCK horloge p Appuyer sur le bouton ou pour régler l heure A Maintenir le bouton enfoncé pour défiler l heure plus rapidement Appuyer sur NEXT B 400 146 001 A_69 2245EF AQ1000TP2 FRE fm Page 7 Wednesday June 18 2008 2 34 PM ...

Page 39: ...T B s Appuyer sur le bouton ou pour régler le jour A Appuyer sur le bouton Menu pour sortir de la programmation B NOTA Si vous n appuyez sur aucun bouton pendant 60 secondes le thermostat automatiquement enregistrera toute modification et sortira de la programmation 400 146 001 A_69 2245EF AQ1000TP2 FRE fm Page 8 Wednesday June 18 2008 2 34 PM ...

Page 40: ...2 ci dessous Horaire par défaut lundi à vendredi samedi dimanche Période Heure du début Consigne de chauffage Consigne de climatisation Heure du début Consigne de chauffage Consigne de climatisation WAKE RÉVEIL 6 00 AM 70 F 21 0 C 78 F 25 5 C 6 00 AM 70 F 21 0 C 78 F 25 5 C LEAVE DÉPART 8 00 AM 62 F 16 5 C 85 F 29 5 C RETURN RETOUR 6 00 PM 70 F 21 0 C 78 F 25 5 C SLEEP COUCHER 10 00 PM 62 F 16 5 C...

Page 41: ...e est toujours au moins 2 F 1 C inférieure à la consigne de climatisation Par exemple si le chauffage de consigne est de 77 F 25 C et vous descendez la consigne de climatisation à 78 F 25 5 C la consigne de chauffage sera automatiquement ajusté à 76 F 24 5 C Nouvel horaire MO LU TU MA WE ME TH JE FR VE SA SA SU DI RÉVEIL Début Chauffage Climatisation DÉPART Début Chauffage Climatisation RETOUR Déb...

Page 42: ...mostat sera appliquée aux autres thermostats voir la page 19 Aussitôt que vous sélectionnez ALL DAYS les réglages affichés heure du début consignes de chauffage et de climatisation seront appliqués à la période affichée pour tous les 7 jours Si vous voulez par la suite modifier les réglages pour un jour spécifique vous pourrez sélectionner DAILY quotidien et sélectionner le jour pour ensuite y app...

Page 43: ...défaut r Appuyer sur le bouton ou pour régler l heure du début A Maintenir le bouton enfoncé pour défiler l heure plus rapidement Appuyer sur NEXT B Pour sauter une période effacer ses réglages Par exemple si vous désirez utiliser les périodes WAKE et SLEEP seulement tel que programmé pour la fin de semaine dans l horaire par défaut effacer les périodes LEAVE et RETURN 400 146 001 A_69 2245EF AQ10...

Page 44: ...retourner à l étape 3 pour modifier les réglages d un autre jour ou à l étape 4 pour régler une autre période Pour sortir de la programmation appuyer sur le bouton Menu NOTA Si vous n appuyez sur aucun bouton pendant 60 secondes le thermostat enregistrera automatiquement toute modification et sortira de la programmation 400 146 001 A_69 2245EF AQ1000TP2 FRE fm Page 13 Wednesday June 18 2008 2 34 P...

Page 45: ...aissent dans le tableau suivant Les descriptions des paramètres sont à la page 15 Menu de configuration de l utilisateur Paramètre Réglage par défaut Options Mode d affichage de la température automatique automatique F C Recul de la température 7 F 4 C 0 à 16 F 0 à 9 C Rétroéclairage permanent OFF désactivé ON OFF activé désactivé Format d affichage de l heure 12 heures 12 heures 24 heures Passage...

Page 46: ...rmostat affiche la température dans le format sélectionné sans tenir compte du format spécifié dans le panneau de commande AQ2000 Recul de la température Lorsque le mode Inoccupé est activé à partir du panneau de commande programmable AQ2000 la température de consigne subit un recul une baisse en mode chauffage ou une augmentation en mode climatisation Ce paramètre permet de spécifier le montant d...

Page 47: ...ton Format d affichage de l heure Ce paramètre permet de sélectionner entre le format 12 heures et le format 24 heures Passage automatique à l heure avancée Lorsque le passage automatique à l heure avancée est activée On le thermostat passe automatiquement à l heure avancée au deuxième dimanche de mars et retourne à l heure normale au premier dimanche de novembre 400 146 001 A_69 2245EF AQ1000TP2 ...

Page 48: ...du plancher pourrait aussi être defectueuse si le thermostat est configuré en mode F voir la page 19 Le chauffage ou la climatisation est arrêté Lorsque le thermostat est configuré en mode AF voir la page 19 FLOOR clignotera si la sonde du plancher est defectueuse ou non installée Le thermostat continuera à réguler la température de l air ambiante mais ignora les limites de température du plancher...

Page 49: ...xemple utiliser un maximum de 500 pieds 150 m pour du fil de calibre 22 AWG 4 Positionner les sélecteurs de configuration s il y a lieu voir la page 19 5 Retourner le thermostat sur la plaque murale et serrer la vis NOTA Pour un confort optimal à l intérieur de la zone garder les ouvertures d aération du thermostat propres et dégagées en tout temps afin d assurer une bonne circulation d air dans l...

Page 50: ...autres thermostats Menu de configuration de l installateur sélecteur 2 Sélecteur 2 permet de placer le thermostat en mode Inst Installateur ou en mode User Utilisateur Placer en mode Installateur pour accéder aux paramètres d installation Sinon laisser en mode Utilisateur Mode de régulation A F AF sélecteurs 3 4 Sélecteurs 3 et 4 permettent de choisir le mode de régulation Sélecteurs de configurat...

Page 51: ...i ché NOTE Voir les pages 21 et 22 pour les descriptions des paramètres de configuration de l installateur 4 Pour modifier un paramètre appuyer sur le bouton ou 5 Pour enregistrer toute modification et afficher le paramètre suivant ou précé dent appuyer sur NEXT ou PREVIOUS 6 Pour sortir du menu retourner le sélecteur 2 vers le bas mode Utilisateur NOTE Si vous sortez du menu sans d abord appuyer ...

Page 52: ...ramètre est offert seulement si le thermostat est configuré en mode F voir la page 19 Consigne maximale du plancher Ce paramètre est offert seulement si le thermostat est configuré en mode F voir la page 19 Réglage par défaut 5 C 41 F Plage 5 C 41 F à 38 C 100 F Réglage par défaut 38 C 100 F Plage 5 C 41 F à 38 C 100 F Réglage par défaut 5 C 41 F Plage 5 C 41 F à 38 C 100 F Réglage par défaut 38 C...

Page 53: ...le ou inférieure à la valeur réglée peu importe la température de consigne Limite maximale du plancher Ce paramètre est offert seulement si le thermostat est en mode AF voir la page 19 Le chauffage est désactivé si la température du plancher est égale ou supérieure à la valeur réglée peu importe la température de consigne Réglage par défaut 41 F 5 C Plage entre les consignes minimale et maximale R...

Page 54: ...ichage de la température extérieure 50 C à 100 C 58 F à 212 F Résolution d affichage 0 5 C 1 0 F Température de fonctionnement 20 C à 55 C 4 F à 130 F Température d entreposage 30 C à 55 C 20 F à 130 F Humidité 5 à 90 RH non condensé à 35 C 95 F Type de régulateur Proportionnel intégral PI Mémoire Les réglages sont stockés dans la mémoire non volatile et sont donc conservés lors d une panne de cou...

Page 55: ...ces à la clientèle détermineront alors si le produit doit être retourné à l adresse suivante Honeywell Return Goods Dock 4 MN10 3860 1885 Douglas Dr N Golden Valley MN 55422 ou si un produit de remplacement peut vous être expédié La présente garantie ne couvre pas les frais de retrait ou de réinstallation La présente garantie ne s appliquera pas s il est démontré que la défectuosité ou le mauvais ...

Page 56: ...PRÉSENTE GARANTIE Certaines provinces ne permettent pas de limiter la durée des garanties tacites et par conséquent la présente limitation peut ne pas s appliquer La présente garantie donne au consommateur des droits légaux spécifiques et peut être certains autres droits qui peuvent varier d une province à l autre Pour toute question concernant la présente garantie prière d écrire aux Services à l...

Reviews: