INSTALLATION INSTRUCTIONS

62-3075EFS-06

®

C

US

AM-1 Series™

PROPORTIONAL THERMOSTATIC MIXING AND DIVERTING 
VALVE STANDARD AND “C” TEMPERATURE RANGE MODELS - 
NPT, UNION SWEAT, THREAD, CPVC, UNION PROPRESS AND 
PEX MODELS

APPLICATION

The AM-1 Series™ family of quality valves in a variety of 
temperature ranges and connections, for master mixing or 
diverting applications.

SPECIFICATIONS

Media Temperature Ranges:

Cold Inlet: 39°F-80°F (4°C-27°C)
Hot Inlet: 120°F-180°F (49°C-82°C)
Mixed Outlet: 
C Model: 70°F-120°F (21°C-49°C)
Standard Model: 70°F-145°F (21°C-63°C)

Connections:

Straight-through design (HOT and COLD at same level).

Construction:

Nickel plated brass construction. EPDM o-rings. Made in 

USA.

Lead Free Plumbing Code Compliance:  

The wettable 

surfaces of lead free models contain less than .25% of 
lead by weighted average

Operating Pressure: 

150 psi (1034 kPa) maximum.

Patent Information: 

U.S. Patent No. 6,079,625.

Temperature Gauge Adapter: 

Lead-free brass, EPDM o-

ring

INSTALLATION

IMPORTANT

Mounting must comply with all local codes.

NOTE TO INSTALLER: This product should be installed by 
a qualified individual, in accordance with local codes and 
ordinances. It is the responsibility of the installer to 
properly select, install and adjust these devices as 
specified in these instructions. For installations which 
require compliance with Building/Mechanical/Plumbing 
Codes, the appropriate AM-1 Series™ valve must be 
chosen and installed, and the discharge temperature set 
and locked according to these instructions. AM-1 “C” 
Series models with the temperature range, 70°F–120°F 
(21°C–49°C) and "Standard" models with temperature 
range 70°F–145°F (21°C–63°C) are ASSE

®

 1017 (point of 

source application) certified, and CSA

®a

 and IAPMO

®

 listed. 

These models shall be used to supply water to tubs, 
showers, bathing facilities and other outlets. These valves 
should be installed where they will be accessible for 
cleaning, servicing or adjustment.

ASSE 1017 Applications—Point of 
Source

These AM-1 Series models can be installed in any position 
consistent with the intended use. For domestic hot water 
supply, the valve must be installed as shown in Fig. 1. 
There shall be no shut-off valves installed between the 
cold water line and the cold water connection on the AM-1 
Series valve. Check valves shall be installed as indicated 
for NPT models; all AM-1 models with union fittings are 
supplied with integral check valves on both the hot and 
cold ports. A cold water service valve may be installed, as 
indicated, between the cold water supply line to the 
distribution system and the cold water line supplying both 
the water heater and the AM-1 Series valve.

NPT

Union

Press

Temperature 

Gauge

a

-UCPVC and -UPEX models are not CSA listed.

Summary of Contents for AM-1 Series

Page 1: ...d in these instructions For installations which require compliance with Building Mechanical Plumbing Codes the appropriate AM 1 Series valve must be chosen and installed and the discharge temperature set and locked according to these instructions AM 1 C Series models with the temperature range 70 F 120 F 21 C 49 C and Standard models with temperature range 70 F 145 F 21 C 63 C are ASSE 1017 point ...

Page 2: ...d 1 Install thermowell with O ring to the thermometer adapter body 2 Tighten to 75 LB IN 10 LB IN DO NOT OVER TIGHTEN 3 Install the thermometer into the thermowell until seated and tighten the set screw to secure in place Fig 2 Temperature gauge installation VALVE ADJUSTMENT To adjust temperature setting of the mixing valve attach thermostrip supplied with the valve to the piping connected to the ...

Page 3: ...ures This provides constant water temperature under different working conditions MAINTENANCE PROCEDURES Hard water conditions may result in scale deposits causing binding of internal parts in extreme cases Cleaning the internal parts will usually restore the valve to proper operating conditions In some cases it may be necessary to replace the lower assembly To clean and or replace the lower assemb...

Page 4: ...l Inc ASSE is a registered trademark of the American Society of Sanitary Engineering CSA is a registered trademark of the Canadian Standards Association IAPMO is a registered trademark of the International Association of Plumbing and Mechanical Officials ASTM is a registered trademark of the American Society for Testing and Materials Teflon is a registered trademark of E I du Pont de Nemours and C...

Page 5: ...conformément aux présentes directives Dans le cas d installations qui doivent être conformes aux codes du bâtiment de mécanique de plomberie la vanne AM 1 qui convient doit être choisie et installée et la température à la sortie doit être réglée et bloquée conformément aux présentes directives Les modèles de série AM 1 offrant les gammes de températures suivantes 21 C 49 C 70 F 120 F et 21 C 63 C ...

Page 6: ...Fixez le puits thermométrique avec joint torique au corps de l adaptateur du thermomètre 2 Serrez à 75 lb po 10 lb po NE SERREZ PAS EXCESSIVEMENT 3 Insérez le thermomètre dans le puits ther mométrique jusqu à ce qu il se tienne puis serrez la vis pour le fixer Fig 2 Installation de l indicateur de température AJUSTEMENT DE LA VANNE Pour régler la température de la vanne de mélange appliquez la ban...

Page 7: ... est ainsi acheminée à température constante peu importe les conditions d utilisation MAINTENANCE L eau calcaire peut entraîner des dépôts qui dans les cas extrêmes peuvent faire gripper les pièces internes Il suffit généralement de nettoyer les pièces internes pour que la vanne retrouve son fonctionnement d origine Dans certains cas il peut être nécessaire de remplacer les pièces inférieures Pour...

Page 8: ...ional Inc ASSE est une marque déposée de l American Society of Sanitary Engineering CSA est une marque déposée de l Association canadienne de normalisation IAPMO est une marque déposée de l International Association of Plumbing and Mechanical Officials ASTM est une marque déposée de l American Society for Testing and Materials Teflon est une marque déposée de E I du Pont de Nemours and Company Tab...

Page 9: ...a en estas instrucciones Para instalaciones en las que se requiere el cumplimiento de códigos de construcción mecánicos o de plomería se debe escoger e instalar la válvula AM 1 Series adecuada y se debe fijar y bloquear la temperatura de descarga según estas instrucciones Los modelos C de la serie AM 1 con rango de temperatura de 70 F 120 F 21 C 49 C y los modelos estándar con rango de temperatura...

Page 10: ...po del adaptador de termómetro 2 Ajústelo a 75 LB IN 10 LB IN No lo ajuste de más 3 Instale el termómetro en el termopozo de forma que se asiente de manera adecuada y ajuste el tornillo empotrado para asegurarlo Fig 2 Instalación del termómetro AJUSTE DE VÁLVULAS Para regular el ajuste de temperatura de la válvula mezcladora fije el termómetro suministrado con la válvula a la tubería conectada al ...

Page 11: ...o PROCEDIMIENTOS DE MANTENIMIENTO El uso de agua dura puede dar como resultado la formación de depósitos de sarro lo que provoca el agarrotamiento de las piezas internas en casos extremos La limpieza de las piezas internas restablece generalmente la válvula a las condiciones de operación normales En algunos casos puede ser necesario reemplazar el ensamblaje inferior Para limpiar y o reemplazar el ...

Page 12: ...registrada de American Society of Sanitary Engineering CSA es una marca registrada de Canadian Standards Association IAPMO es una marca registrada de International Association of Plumbing and Mechanical Officials ASTM es una marca registrada de American Society for Testing and Materials Teflon es una marca registrada de E I du Pont de Nemours and Company Tabla 1 Kits de reemplazo Serie AM 1 Pieza ...

Reviews: