Installation and Setup Guide
1-2
Compatible Devices
•
Supports up to 8 Addressable Keypads: 6148/6150 Fixed-Word Display Keypads, 6164 Alpha
Keypad, 6128RF/6128RFH/6150RF/6160RF Keypad/Transceivers, 6160V Voice Keypad
•
Supports up to two (2)
Touch Screen (AUI) Devices (Symphony, 6270), which are in addition to the
standard eight (8) addressable keypads.
•
Supports up to five 4219, 4229 addressable basic wired zone expander modules
•
Supports 5881/5882EU/5882EUH/5883 series receiver and 5800/5800EU/5800H/5800AP series
transmitters
•
Outputs from up to 16 relays, two on-board triggers, and/or Powerline Carrier Devices (X-10 type)
-- Use any combination of 4204, 4229, 6164 relays and/or Powerline Carrier Devices.
-- Output functions (up to 48)
•
Alarm power output provides a 12VDC, 2 AMP output that can drive compatible sounders with a
steady output for burglary/panic, or temporal pulse (3 pulses – pause – 3 pulses – pause – 3 pulses.
. .) for fire. Uses current limiting circuitry for protection.
•
Auxiliary Power Output: 12VDC, 600 mA max.; all outputs are power limited.
•
Backup Battery: Rechargeable (sealed lead-acid type) 12VDC, 4AH minimum
•
Audio Alarm Verification (using AAV module, such as ADEMCO UVS); can be used in conjunction
with an output trigger to permit voice dialog between an operator at the central station and a
person at the premises.
•
Alternative Communication Media: Primary telephone number messages can be reported via ECP
connection to Ethernet TCP-IP Internet
•
AC Power Supply: Wired-in or Plug-in 110 (e.g 1321)/220VAC transformer
Important Installation Highlights (Installer Please Read)
•
This system uses addressable keypads and Zone Expander Modules (see table of addresses in
Programming Overview
section).
•
Keypads must be set for addresses 16-23 (first keypad is address 16, which is different from
previous controls) and programmed in data fields *190-*196.
•
Zone Expander Modules must be set for specific addresses (07-11), based on the zone numbers used
(see table of addresses in
4219/4229 Expansion Zones
section).
•
4204 Relay Modules must be set for specific addresses (12-15; see
Connecting Relay Modules
section).
•
6164 Keypads must be set for two addresses: a keypad address and a zone expander address (if
using the keypad’s expansion zones).
•
This control will not power-up unless AC mains is connected (will not power-up on battery alone).
However, once the system is powered up, it will operate on battery power in case of AC mains loss.
•
Relays have two programming menu modes: Use *79 Menu mode to map module addresses and
device (output) numbers. Use *80 Menu mode to define the output functions (see
Output Device
Programming
section).
•
This system supports programmable function keys. Use *57 Menu mode to define the function keys
(see
Function Key Programming
section).
•
This system provides various paging features. Refer to the
Programming Overview
section for a
summary on pager programming.