Honeywell Ademco Vista-48LA Installation And Setup Manual Download Page 1

 

 

ADEMCO VISTA-48LA 

Security System 

 

 

 

 

Installation and Set-Up Guide  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

K0749-6EN    5/05  Rev. A 

Summary of Contents for Ademco Vista-48LA

Page 1: ...ADEMCO VISTA 48LA Security System Installation and Set Up Guide K0749 6EN 5 05 Rev A ...

Page 2: ...ii ...

Page 3: ... Module 2 9 Installing the Transmitters 2 9 Installing a Keyswitch 2 10 Connecting Relay Modules 2 11 Powerline Carrier Devices 2 12 On Board Triggers 2 13 Phone Line Connections 2 14 Alternative Communications Media ACM Connections 2 14 Programming Overview 3 1 About Programming 3 1 Zones and Partitions 3 1 Keypads 3 2 Wireless Receiver Transmitters and Wireless Keys keyfobs 3 2 Pager Programming...

Page 4: ...4 About Descriptor Programming 82 Menu Mode 5 15 Configurable Zone Type Programming 83 Menu Mode 5 16 Programming Installer and User Schedules 5 18 System Communication and Operation 6 1 Panel Communication with Central Station 6 1 Report Code Formats 6 1 Robofon 8 Format 6 3 ADEMCO Contact ID 6 4 Security Codes 6 5 Keypad Functions 6 6 Panic Keys 6 6 Follow Me Feature 6 7 Setting Adjusting the Re...

Page 5: ...to arm disarm or allow disarm the system Up to 4 Keypad macros which can be activated by wired wireless keypads Paging feature allows certain system conditions to be reported to up to two pager phone numbers can use a dedicated key on keypads to send a signal to a pager User programmable telephone number for audio beeps reporting of alarms to the user follow me feature Built in Telephone Line Moni...

Page 6: ...ication Media Primary telephone number messages can be reported via ECP connection to Ethernet TCP IP Internet AC Power Supply Wired in or Plug in 110 e g 1321 220VAC transformer Important Installation Highlights Installer Please Read This system uses addressable keypads and Zone Expander Modules see table of addresses in Programming Overview section Keypads must be set for addresses 16 23 first k...

Page 7: ... be closed and secured without a lock by using 2 screws in the cover s edge CABINET DOOR BOTTOM LOCKED UNLOCKED cab_lock_snap 001 V0 ADEMCO ADEMCO PUSH SNAP TAB SNAP TAB PUSH ON LOCK UNTIL IT IS SEATED SECURELY STEP 2 STEP 1 CHECK POSITION Figure 1 Installing the Cabinet Lock Mounting the PC Board Alone no RF Receiver 1 Hang two short mounting clips provided on the raised cabinet tabs see Detail B...

Page 8: ...inet into the blocks right hand terminals and tighten the screws Notes Do not mount the cabinet on or near metal objects This will decrease RF range and or block RF transmissions from wireless transmitters Do not locate the cabinet in an area of high RF interference revealed by frequent or prolonged lighting of the LED in the receiver after it is operational random flicker is OK ANTENNA MOUNT 2 PL...

Page 9: ...ces exceeds 600mA Suggested power supply AD12612 Keypad Addresses Keypad Address Keypad Address no 1 16 no 5 20 no 2 17 no 6 21 no 3 18 no 7 22 no 4 19 no 8 23 The first keypad is address 16 which is always enabled and set for partition 1 with all sounds on IMPORTANT Keypads powered from supplies that do not have a backup battery will not function if AC mains power is lost Make sure to power at le...

Page 10: ...ceed 2 amps going beyond 2 amps will overload the power supply or may cause the electronic circuit protecting the sounder output to activate You must install a battery since the battery supplies this current Do NOT perform steps 2 and 3 if using a self activated siren Wiring the AC Transformer Transformer Connect the Transformer to terminals 1 and 2 on the control board See wiring table at right f...

Page 11: ...lly expected levels of lightning and electrical discharge and does not normally require an earth ground If an earth ground is desired for additional protection in areas of severe electrical activity terminal 25 on the control board or the cabinet may be used as the ground connection point The examples of good earth grounds listed at the left are available at some installations AUXILIARY DEVICE CUR...

Page 12: ...se zone doubling for fire zones If enabled Zone Programming mode Hardwire Type prompt option 3 basic wired zones are automatically paired as follows ZonePaired with zone 2 10 3 11 4 12 5 13 6 14 7 15 8 16 NOTE A short across the EOL i e at terminal on either zone of a zone doubled pair or on a double balanced zone causes a tamper condition displayed at keypad as CHECK Smoke Detectors 2 Wire Smoke ...

Page 13: ...sses For Zones Set Module to Device Address 09 16 07 not available if zone doubling enabled 17 24 08 25 32 09 33 40 10 41 48 11 3 Connect sensors to the module s loops 4 If using relays with the 4229 connect the desired field wiring to the unit s relay contact terminals Notes Supports up to 40 expansion zones NO or NC using 4219 4229 Zone Expander Modules as follows Use 1000 ohm end of line resist...

Page 14: ...tructions for other mounting wiring and programming information Notes Each 6164 keypad supports up to 4 wired expansion EOLR or double balanced zones and one relay output Use 2000 ohm end of line resistors at the end of loops connected to the 6164 keypads Enter 6164 keypad program mode by pressing and holding down both the 1 and 3 keys within 60 seconds of power up Enable the keypad addresses usin...

Page 15: ...TO RELEASE CIRCUIT BOARD REMOVE SCREWS AND BEND BACK TABS NOTE CIRCUIT BOARD IS MOUNTED IN CONTROL S CABINET GROUNDING LUGS 2 PROVIDED MUST BE INSERTED IN LEFT HAND TERMINALS OF ANTENNA BLOCKS AND SECURED TO CABINET SEE RECEIVER S AND CONTROL S INSTRUCTIONS SOCKET PLUG MODEL NO IS INDICATED ON CIRCUIT BOARD 5881 003 V0 INSERT IN RIGHT HAND TERMINALS Figure 9 5881EN RF Receiver cover removed Instal...

Page 16: ...e output 17 output 18 trigger connector pins 3 Connect a 2000 ohm EOL resistor across the momentary switch 4 You can wire an optional closed circuit tamper switch model 112 in series with the zone If the switchplate is then removed from the wall the tamper will open disabling keyswitch operation until the system is next disarmed from the keypad If the tamper is opened when the system is armed an a...

Page 17: ... where xx is the module s address If communication tamper failure occurs on a device with zones wired to it all zones on the device will be displayed in their respective partitions Relay Module Addresses 4204 6164 Address 4229 6164 Address no 1 12 no 1 zn 09 16 07 no 2 13 no 2 zn 17 24 08 no 3 14 no 3 zn 25 32 09 no 4 15 no 4 zn 33 40 10 no 5 zn 41 48 11 Use these addresses if using only relays wi...

Page 18: ...ulator It supplies signals from the control panel through the premises AC mains wiring to the Powerline Carrier devices which are plugged into AC outlets You can then make devices that are plugged into Powerline Carrier devices perform various functions in response to commands you enter at the security system keypads 1 2 3 4 SA4120XM 1 CABLE PART OF 4120TR XM10E POWERLINE INTERFACE MODULATOR YEL R...

Page 19: ...ure 13 On Board Trigger Connector with 4 Wire Cable for Trigger Use Only Notes There are two on board triggers that can be used to activate output devices These outputs are normally high and go low upon programmed condition The outputs can be programmed for inverted operation normally low go high using 79 Menu mode Program these triggers using 80 81 Menu modes as you would for any other relay outp...

Page 20: ...agram below Connections use one of the on board triggers Suggested AAV Module ADEMCO UVS shown or Eagle 1250 Notes Set field 91 for AAV and program the appropriate output output 17 or 18 using 80 Menu mode select zone type 60 For voice session monitoring connect an EOLR zone to UVCM module terminals 6 7 and program the zone as zone type 81 56 Menu mode E g Using output 18 for the trigger program a...

Page 21: ...line carrier zones chime zones night stay exit route zones final exit door zone and pager zones 82 Alpha Programming Create alpha descriptors for easy zone identification Scheduling Mode code 64 Create schedules to automate various system functions or to determine user access Zones and Partitions Each protection zone needs to be programmed with various attributes using 56 Zone Programming mode or ...

Page 22: ...on 24 RF House ID Code if using DIP switch equipped wireless keypads for each partition 25 Arming Prevention Override 67 Transmitter Low Battery Report Code 75 Transmitter Low Battery Restore Report Code 173 RF Reporting Options 178 RF Supervision RF Jam Options Use 56 Menu mode to program wireless zones 9 48 and wireless button zones 49 64 Transmitters Use 56 or 58 Zone Programming Menu modes to ...

Page 23: ... Zone types are defined below Zone Type Description Type 00 Zone Not Used Program a zone with this zone type if the zone is not used Type 01 Entry Exit Burglary 1 Assign to zones that are used for primary entry and exit Provides entry delay when zone type is faulted if control is armed in the Away Stay or Night Stay modes No entry delay provided when the panel is armed in the Instant Maximum mode ...

Page 24: ...t Stay mode Type 12 Monitor Zone Works as a dynamic monitor of a zone fault trouble not alarm In the case of a short open the message ALARM 24 Hr Non Burg XXX where XXX is the zone number will be sent to the Central Station The system keypad will display a CHECK message indicating the appropriate zone but keypad beeping does not occur Upon restoral of the zone the message RESTORE 24 Hr Non Burg XX...

Page 25: ...are sent Type 82 Blockschloss Used with special blockschloss lock and key System arms 5 seconds after the key is fully turned arms MAXIMUM key can then be removed When armed the blockschloss zone is shorted An open circuit on this zone causes trouble condition If zones are not ready the key will not turn fully and the system will not arm Contact ID report code is 409 Once the system is armed using...

Page 26: ... Mode No for example 56 while in Program Mode The Alpha display keypad will display the first of a series of prompts requesting entries After making the appropriate entry press the key to accept the entry and continue to the next prompt Loading Factory Defaults Initializing for Download To Load Default Entries Data Field System and Zone Defaults The control has two unique sets of default entries D...

Page 27: ...ule 3 6164 relay only module 4 6164 relay only 12 13 14 15 112 113 114 115 79 output device programming device address prompt entered at device address prompt entered at device address prompt entered at device address prompt entered at device address prompt Keypads keypad 1 keypad 2 keypad 3 keypad 4 keypad 5 keypad 6 keypad 7 keypad 8 16 17 18 19 20 21 22 23 116 117 118 119 120 121 122 123 data f...

Page 28: ...Installation Instructions 3 8 ...

Page 29: ...r 3 23 Quick Forced Bypass 0 no quick bypass 1 allow quick bypass code 6 All zones bypassed by this function will be displayed after the bypass is initiated 24 RF House ID Code 00 disable all wireless keypad usage 01 31 House ID for partition 1 2 3 The House ID identifies receivers and wireless keypads If a 5827 or 5827BD wireless keypad or 5804BD 5804BDV transmitter is being used a House ID code ...

Page 30: ...a Partition 0 no must be 0 if system uses zone type 82 Blockschloss 1 yes make partition 3 a common area partition If selected partition 3 functions as a common area partition rather than as an independent partition Zone Sounds Timing FIELD TITLE and DATA ENTRIES EXPLANATION 31 Single Alarm Sounding Per Zone per armed period 0 no limit on alarm sounding per zone 1 limit alarm sounding to once per ...

Page 31: ...State 0 always power up in a disarmed state 1 assume the system status prior to power down When the system powers up armed an alarm will occur 1 minute after arming if a zone is faulted at that time Note that if the previous state was armed AWAY or STAY the system will not respond to sensor changes for 1 minute which allows time for sensors such as PIRs to stabilize Dialer Programming 40 50 FIELD ...

Page 32: ...l Reporting 0 disable standard backup report only 1 5 see table to right To Primary No To Secondary No 1 alarms restore cancel others 2 all except open close test open close test 3 alarms restore cancel all 4 all except open close test all 5 all all 50 Burglary Dialer Delay 0 no dial delay UL must be 0 1 15 seconds 2 30 seconds 3 45 seconds Provides delay of BURGLARY ALARM report to the central st...

Page 33: ...lable digits If the number of zones exceeds the number of available digits begin with digit 1 again This is an enabling code only and is not the actual code sent to the Central Station office Entries in the second entry pair are ignored An entry of 0 in the first box disables the report FIELD TITLE and DATA ENTRIES EXPLANATION 59 Exit Error Report Code 0 no report 1 F report code see description a...

Page 34: ... 59 Sent when an alarm zone is restored to its non faulted condition or at the times selected in field 69 71 Trouble Restore Report Code 0 disable 1 F see description above 59 Sent when a trouble in a zone is restored 72 Bypass Restore Report Code 0 disable 1 F see description above 59 Sent when a zone that has been bypassed is unbypassed either manually or when the partition system is disarmed 73...

Page 35: ...ral station This can serve as a safety feature for elderly infirm or disabled persons 86 Cancel Verify Keypad Display 0 no 1 yes When enabled 1 yes this feature causes a ALARM CANCELED display on the LCD keypad under the following conditions After the kissoff of the cancel message to the Central Station indicating a successful transmission When an alarm is successfully canceled before the Central ...

Page 36: ... Reports are sent to a secondary number unless the monitoring zone option is used which pauses calls Otherwise the call to the secondary number by the communicator after the alarm report will prevent the AAV from taking control of the telephone line and the AAV Listen in session cannot take place 92 Telecom Monitor Enable Entry 1 Timeout 0 disabled 1 15 1 minute to 15 minutes respectively 2 2 min ...

Page 37: ...one number in field 160 must have been entered If fewer than 16 characters exit by pressing and next field number To clear entries from this field press 161 For example use these optional 16 characters for the following PIN number to identify a specific pager to the paging company Subscriber account number enter 11 to send enter 12 to send Pause enter 13 to allow a 2 second pause Any special chara...

Page 38: ...mally detects tamper faults from devices equipped with tamper switches for cover removal and or wall removal while the system is armed or disarmed Tamper faults are ignored when a zone is bypassed or when the system is in Test mode unless entry 1 options 1 2 or 3 are selected Tamper display is as follows Disarmed TAMPER 1xx or zz where 1xx ECP device address zz zone number of faulted device Armed ...

Page 39: ...e enabled field 70 in order for RF Supervision RF Jam alarm restores to be reported Trouble reports and trouble restore reports must be enabled fields 60 71 in order for RF supervision RF jam trouble conditions and restores to be reported 180 Zone Bypass Limit 0 unlimited zone bypasses in each partition 1 7 number of zone bypasses allowed in each partition Select the maximum number of zones that c...

Page 40: ... 1 0 disable 1 enable Enable this option if you want an external device connected to trigger 1 to mimic keypad sounding NOTE If using this option trigger 1 must be dedicated to only this function do not assign any other functions to trigger 1 188 Keypad Sabotage Options Entry 1 Keypad Lockout 0 disable 1 enable 15 minute lockout Entry 2 Keypad Supervision and Tamper Fault Detection 0 no 1 yes Entr...

Page 41: ...n 192 Keypad 4 Device Address 19 Keypad 4 See field 190 for entries and explanation 193 Keypad 5 Device Address 20 Keypad 5 See field 190 for entries and explanation 194 Keypad 6 Device Address 21 Keypad 6 See field 190 for entries and explanation 195 Keypad 7 Device Address 22 Keypad 7 See field 190 for entries and explanation 196 Keypad 8 Device Address 23 Keypad 8 See field 190 for entries and ...

Page 42: ...Installation Instructions 4 14 ...

Page 43: ...t to Confirm 0 no 1 yes If 1 Yes is entered the XMIT TO CONFIRM prompt appears later in this procedure after entering RF transmitter serial and loop numbers and lets you confirm the programming of each RF transmitter We recommend that you confirm every transmitter If 0 No is entered the XMIT TO CONFIRM prompt is automatically skipped This option is ignored if programming wired zones only Enter Zn ...

Page 44: ...rs only for basic wired zones 01 08 zone 02 is used as an example in display NOTE If zone doubling is being used the response time set for zones 01 08 automatically applies to each zone s associated doubled zone 10 INPUT TYPE RF TRANS 3 Input Device type In 2 AW Aux wired zone 3 RF supervised RF transmitter 4 UR unsupervised RF transmitter 5 BR unsupervised button type RF transmitter 7 RM supervis...

Page 45: ...tered in error simply re enter the loop number or press and the serial number will return to the display XMIT TO CONFIRM PRESS TO SKIP Confirmation Option Activate the loop input or button to continue This prompt will only appear if you answered Yes at the first prompt in this section The system will enter a confirmation mode so that the operation of the actual programmed input can be confirmed Ac...

Page 46: ... 10 Summary Screen 01 64 zone number 00 quit to continue OR D to go to prompts for wireless key programming templates A summary screen will appear showing zone 1 s currently programmed or default values Enter the zone number being programmed then press which displays a summary screen for that zone See next prompt in this example zone 10 is being entered If programming a wireless key press the D ke...

Page 47: ...only appear if the first prompt after entering 58 was answered Yes To confirm activate the loop input or button that corresponds to this zone The system checks for a duplicate If a duplicate exists a long error beep will sound Press to back up and re enter the serial and or loop number Entd A022 4063 Rcvd A022 4064 If Serial or Loop Numbers do not match after activating the transmitter to continue...

Page 48: ...8 The system will search for the highest available consecutive 4 zone group the four zones in the case of the 5804 and 5804BD and display the lowest zone number of the group If you want to start at a different zone enter the zone desired and press If that zone number is displayed the system has the required number of consecutive zones available beginning with the zone you entered If not the system...

Page 49: ...ramming Form then enter the other information zone number zone type loop number etc relevant to that device Wireless Key Predefined Default Templates YOU MUST PROGRAM THIS BUTTON LOOP 4 LOOP 3 ENROLL AS BR LOOP 1 LOOP 2 ON OFF 5804 001 V1 5804 Wireless Key Transmitter LOOP 3 LOOP 1 LOOP 2 LOOP 4 YOU MUST PROGRAM THIS BUTTON RED YELLOW LED GREEN YELLOW LED ENROLL AS BR 5804BD 007 V0 5804BD 2 Way Wi...

Page 50: ... an entry Press to go forward again Output Device programming involves 1 Use 79 Menu Mode to assign module and output numbers and map them to device addresses NOTE You must map output devices using 79 Menu Mode before you can use 80 Menu Mode 2 Use 80 Menu Mode to create output definitions which control the output devices 79 Menu Mode Output Device Mapping Use this menu to assign Relay Module devi...

Page 51: ... keypad 2 Powerline Carrier device to continue Select whether this is a relay or a Powerline Carrier X 10 device If relay is selected skip to B prompt If X 10 is selected go to A prompt A XX UNIT No yy Unit Number 01 16 predefined address to continue If X 10 is selected a prompt for the unit number appears Enter the unit code set at the device and press The system returns to the Output Number prom...

Page 52: ...event Note that each defined function is associated with only one output number This means that if more than one output device needs to perform this particular function you need to define another output function number with the same attributes but assign the appropriate output number i e output devices can be assigned more than one function number but each function number can only be assigned a si...

Page 53: ...ne type was selected this screen appears Otherwise skip to the next row Enter the desired zone type associated with this output number See below for a list of available zone types CHOICES FOR ZONE TYPES 00 Not Used 05 Trouble Day Alarm Night 14 Gas 01 Ent Exit 1 06 24 Hr Silent 16 Fire w verification 02 Ent Exit 2 07 24 Hr Audible 23 No Alarm Response 03 Perimeter 08 24 Hr Aux 24 Silent Burglary 0...

Page 54: ...ice action as listed below Press the key to continue 0 off 4 Change Device State 1 Close for 2 seconds 5 Duration 1 see data field 177 2 Close and Stay Closed 6 Duration 2 see data field 177 3 Pulse 1 sec ON 1 sec OFF Duration 1 see data field 177 entry 1 from 15 secs to 15 minutes Duration 2 see data field 177 entry 2 from 1 to 7 days Enter Output No R02 02 Output Number 01 16 output no 17 18 on ...

Page 55: ...ng example 01 02 03 After all zones are entered press 00 to continue IMPORTANT Do not include fire zones in zone lists that are used to STOP device actions 01 Del Zn List 0 No 1 Yes 0 Deleting Zone Lists 0 don t delete list 1 delete this zone list to continue To delete the zone list enter 1 All zones in the zone list will be deleted automatically and the system returns to the Zone List No prompt T...

Page 56: ... key is active Key A Func Zone 95 00 Define Key Function 00 12 see list to right to continue Returns to key number prompt with the next function key letter displayed System defaults to these function key settings For Options 09 12 note that there are only four macros per system Therefore be careful when assigning these macros to the various partitions Enter the desired function for this key 00 to ...

Page 57: ...er words for Scheduling mode event 10 NOTE Do not assign reminder words if using fixed word keypads Pressing 0 goes to the next prompt to let you enter zone descriptors Pressing 1 lets you program a partition descriptor or reminder words If selected the following prompt appears PART REMIND Enter the 2 digit custom word number 08 13 to be programmed then press Enter the descriptor as described in s...

Page 58: ...be 0 2 For zone doubled zones both zones of the doubled pair must be assigned the same response to a short 90 Resp to open Armed 0 DArmd 0 Response to Opens 0 none 2 trouble 1 Alarm 3 fault to continue Select the type of response when zones assigned to this zone type are opened when the system is armed 90 Vent Zone 0 No 1 Yes Vent Zone 0 no 1 yes to continue If selected the system can be armed eve...

Page 59: ...arm ID 000 Trouble ID 000 Contact ID Report Codes 000 999 report code to continue returns to Enter configurable zone type number prompt Enter the desired 3 digit Contact ID report codes for faults and troubles occurring on zones assigned to this zone type IMPORTANT Make sure the code does not conflict with existing predefined Contact ID report codes See the System Communication section for a list ...

Page 60: ...d time Events 10 11 are reserved for the installer only Child Not Home report option 03 is sent to all pagers in the user s partition message sent is 777 7777 User must be enabled for paging see User Attributes in System Operation section Disarm Time Window 08 System can be disarmed only during this time period Exception If a burglary alarm occurs the system can be disarmed outside the scheduled t...

Page 61: ...ing the key to move forward then press 1 to select the day s This entry applies only to the following events 1 relay on off 2 user access 3 child not home report use 00 23 if 24 hour time is enabled REPEAT OPTION 0 4 X Repeat Option 0 do not repeat 1 repeat schedule weekly 2 repeat schedule biweekly every other week 3 repeat schedule every third week 4 repeat schedule every fourth week to continue...

Page 62: ...Installation Instructions 5 20 ...

Page 63: ...ILURE on alpha keypads or FC on fixed word keypads Report Code Formats The following chart indicates the types of handshake kissoff frequencies that the panel supports and the different formats that can be sent with each FORMAT HANDSHAKE TRANSMITS DATA KISSOFF TRANSMIT TIME Low Speed 1400 Hz 1900Hz 10PPS 1400 Hz Under 15 secs 3 1 4 1 4 2 Standard report Sescoa Rad 2300 Hz 1800Hz 20PPS 2300 Hz Unde...

Page 64: ...le Res SSS S RT SSS S RT SSSS SS RTt RTRTRT RT t Bypass Res SSS S RB SSS S RB SSSS SS RBb RBRBRB RB b Characters in parenthesis are included in Robofon 8 format Where SSS or SSSS Subscriber ID C Close Code 1st Digit A Alarm Code 1st digit U User Number in hex Z Typically Zone Number 2nd digit Gg Test Code 1st 2nd digits Tt Trouble Code 1st 2nd digits R Restore Code Alarm Bb Bypass Code 1st 2nd dig...

Page 65: ...ode as in 4 2 format Signal flow Receiving equipment Dialing equipment Send start char w 77h Send message described above Acknowledge ACK 06h Delay greater than 500ms Send new start char w 77h Send next message if available Acknowledge ACK 06h etc Dialer should start sending the message no more than 200ms after start char If no response is detected the receiver retries sending start char three tim...

Page 66: ...ceiver Jam Detect 351 Telecom Line Fault 353 Alternative Comm Media Trouble 354 Failure to Communicate log only 373 Fire Loop Trouble 374 Exit Error Alarm 380 Trouble Zone Type 5 381 RF Sensor Supervision 382 Supervision Auxiliary Wired Zone sent after code 333 is sent 383 RF Sensor Tamper and Double Balanced Zone Tamper Code Definition 384 RF Sensor Low battery 393 Clean Me ESL smoke detectors on...

Page 67: ...stem only if it was used to arm the system 3 Duress see user performs security functions but also silently sends a duress message to the central station reports as duress code user number 4 Partition see user See Partition Master paragraph above used to assign Master other user numbers as partition masters Refer to the user guide for detailed procedures on adding deleting security codes and changi...

Page 68: ...te key on the keypads see Single Button Arming above Arming Instant Enter code INSTANT 7 Arming Maximum Enter code MAXIMUM 4 or simply press appropriate lettered key on the keypads see Single Button Arming above Disarming Enter code OFF 1 If entry delay or an alarm is active you do not need to press OFF entering the security code alone disarms the system Bypassing Zones Enter code BYPASS 6 zone nu...

Page 69: ...with the partition in which it is entered To include a 2 second dialing pause in the number press at the point in the entry the pause is desired it displays as Pauses entered at the end of the number will allow dialing but will delay the tones by the amount of pause programmed If no number is desired leave the entry blank and go to the next step Press to save the new number The following prompt ap...

Page 70: ...ith a zone number and a once per minute beeping at the keypad indicates that a low battery condition exists in the wireless sensor displayed zone 00 indicates a wireless keypad If the battery is not replaced within 30 days a CHECK display may occur Note Some wireless sensors contain a non replaceable long life battery which requires replacement of the entire unit at the end of battery life e g 580...

Page 71: ...ll be transmitted with a TEST report The keypad will beep once per minute as a reminder that the system is in the Test mode NOTE Wireless motion detectors Passive Infrared units will send signals out only if they have been inactive for 3 minutes from their prior transmission conserves battery life 3 Test all sensors using the procedure described in the User s Guide Testing the System section 4 Aft...

Page 72: ...ou should reorient or move the transmitter to another location Usually a few centimeters in either direction is all that is required 4 If each transmitter produces the proper keypad response when it is faulted you can then permanently mount each of the transmitters according to the instructions provided with them 5 Exit the Go No Go Test mode by entering Installer code OFF Dialer Communication Tes...

Page 73: ...MF multi frequency Data Tones 1400 2300Hz ACK 1400Hz KISSOFF Robofon Contact ID same as ADEMCO except 2300Hz ACK LINE SEIZE Double Pole DOC Load No 3 4 Maximum Zone Resistance Zones 1 8 300 ohms excluding EOLR in standard EOLR zones COMPATIBLE DEVICES Keypads 6128RF 6148 6150 6150RF 6160RF 6160V 6164 Wireless Receivers 5881ENL 5882L accepts up to 8 transmitters 5881ENM 5882M accepts up to 16 trans...

Page 74: ...he transmitters illustrated below have one or more unique factory assigned input loop ID codes Each of the input loops requires its own programming zone e g a 5804 s four inputs require four programming zones 5802MN2 5802H ENROLL AS UR OR RF LOOP 1 VISTA48D 001 V0 5817 ENROLL AS RF 5890 5888H ENROLL AS RF OR RM LOOP 1 5808LST 5808H ENROLL AS RF LOOP 1 5809 ENROLL AS RF 5852 5852H ENROLL AS RF Gree...

Page 75: ...ansmitter RF Reed switch magnetic contact sensor easily hidden in the frame and edge of a door or window Has a single unique input loop code 5819 Shock Processor Transmitter RF Connects to externally mounted inertia type shock detector not supplied Has built in tampered cover switch Has 3 unique input loop codes Loop 1 Terminals for a wired N C sensor loop Loop 2 For a closed circuit contact loop ...

Page 76: ...Installation Instructions 8 6 NOTES ...

Page 77: ...ion or intrusion that takes place behind walls ceilings floors closed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of any material on the mirrors windows or any part of the optical system can reduce their detection ability Passive Infrared Detectors sense changes in temperature however as the ambient temperature of the protected area approaches th...

Page 78: ...ouse ID 2 9 4 1 4 2 8 5 IBM Personal Computer 3 1 Input Device Type 5 4 8 5 Installer Code 3 6 4 1 7 1 7 2 Interior Follower 3 3 5 2 5 11 Interior w Delay 3 4 5 2 5 11 keypad addresses 2 3 3 2 Keypad Programming Fields 4 13 Keyswitch 2 10 3 5 5 2 6 4 Kissoff 5 11 6 1 Lock 2 1 Long Range Radio 1 2 2 14 4 4 4 5 6 4 Low Battery Message 7 2 Macros 1 1 Master Security Code 4 1 Modem 3 1 6 8 Module Addr...

Page 79: ...TA TO TRANS GND 12 AUX 19 16 15 13 10 9 1 2 3 4 5 6 OUTPUT 18 TRIG 2 OUTPUT 17 TRIG 1 BATTERY FUSE FOR REPLACEMENT USE SAME VALUE e g ADEMCO No 90 12 3A 4 WIRE SMOKE DETECTOR CONNECTIONS SET RECEIVER S DIP SWITCH FOR DEVICE ADDRESS OF 0 SEE INSTRUCTIONS SET UNIT S DIP SWITCH FOR DEVICE ADDRESSES 7 15 SEE INSTRUCTIONS MAXIMUM NUMBER OF 2 WIRE SMOKE DETECTORS ON ZONE 1 IS 16 DETECTORS MUST HAVE COMP...

Page 80: ... HEREOF IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER S OWN NEGLIGENCE OR FAULT Seller does not represent that the product s it sells may not be compromised or circumvented that the product s will pr...

Reviews: