- 2 -
1. Push the two case release snaps at the bottom of the
keypad with the blade of a medium screwdriver (this
will push in the release snap), then pull that side of the
case back away. Insert the screwdriver in the side of
the keypad (between the front and back case) and
gently twist to release the side locking tab. Repeat for
the other side. Refer to Figure 1 for location of the case
back release snaps and locking tabs.
ARMED
READY
CPU
MOUNTING
RELEASE
SNAPS
NOTE:
THE 6164US IS NOT
EQUIPPED WITH A
CPU LED
TO REMOVE REAR COVER
PUSH IN THE TWO MOUNTING
SNAPS LOCATED ALONG THE
BOTTOM OF THE KEYPAD
AND LIFT COVER UP.
6164-003-V6
LOCKING
TAB
Figure 1. Removing the Case Back
2.
Mount the case back
to a wall or to an electrical box
using the 25mm-long self-tapping screws supplied
(anchors for drywall are not supplied).
If you wish to tamper-protect the keypad for
removal from the wall, use an additional
mounting screw in the tamper hole in the case
back (see Figure 2 for location).
3.
Pass the four power/data wires, wires for up to four
zones, and two or three relay contact wires through
the opening in the case back. If surface wiring is being
used, wiring may be routed through the top or the
bottom left-side breakout in the case back. See Figure
2. The breakouts must be punched out using a
screwdriver before mounting the case back. If desired,
wires may be strain-relieved to the wire tie point on
the inside of the case back with a tie wrap (not
supplied).
WIRE
TIE
POINT
USE AN
ADDITIONAL
MOUNTING
SCREW
HERE IF
BACK CASE
TAMPER IS
TO BE USED
BREAKOUT
FOR
SURFACE
WIRING
BREAKOUT FOR
SURFACE WIRING
6164-02-V0
MOUNTING
HOLES
Figure 2. Wiring Entry (Case Back)
4.
Connect the power/data wires to the four screw
terminals on the keypad’s PC board marked as shown
in Figure 3 and as follows:
Wiring Table
Keypad Control
Panel
Color
▲
G
Data Out
Data In
Green
−
GND
−
Aux Pwr
Black
+
+12VDC
+ Aux Pwr
Red
▼
Y
Data In
Data Out
Yellow
5. Connect the wires for the four 2K EOLR zones to the
six screw terminals on keypad PC board as shown in
Figure 3 and as follows:
Keypad
Wired
Zone
Z1
+ Zone 1
- Zone 1 and Zone 2 return
Z2
+ Zone 2
Z3
+ Zone 3
- Zone 3 and Zone 4 return
Z4
+ Zone 4
Note:
There is a common ground for zones 1 and 2, and
one for zones 3 and 4.
6. Connect the zone contact’s wires (door strike, etc.) to
the three relay terminals marked NC, NO, and C as
shown in Figure 3 and as follows:
Keypad Relay
NO N.O.
contact
C
Pole contact (common)
NC N.C.
contact
-
[-] GROUND (-12V)
G
Z1
Z2
(Z1
&
Z2)
(Z3
&
Z4)
Z4
Z3
2K
2K
2K
2K
TAMPER
CONTACTS
TAMPER
CONTACTS
N.O.
N.C.
DOUBLE BALANCED
CONVENTIONAL
EOLR
6164-005-V2
[Y] DATA IN
[+] +12VDC IN
[G] DATA OUT
OPTIONAL
Y +
N.O.
C.
N.C.
Figure 3. Wiring Details
7.
Reattach the keypad
to the mounted case back.
Attach the top of the keypad first, and then press the
bottom section down until it snaps into place
securely.
8.
Peel off the protective film on the LED and keypad
labels.
SETTING THE KEYPAD OPTIONS
The 6164/6164US allows eight items to be programmed
via local keypad programming mode:
WWW.DIYALARMFORUM.COM
WWW.DIYALARMFORUM.COM