4. Test the detector immediately after completing the
installation (as described in the TESTING section of
this manual) and refer to the control system's
instructions for additional information concerning the
use of wireless smoke detectors.
DO
NOT PA
IN
T
TAMPER SWITCH
ACTIVATOR
TAMPER SWITCH
ACTIVATOR
Figure 6. Detector Mounting Bracket
Figure 7. Mount Detector Across Ceiling Panel Support
CAUTION
DO NOT attach the detector to removable ceiling panels.
Attach the detector across panel support as shown in
Figure 7.
Tamper Protection
This detector has a built-in tamper switch that will cause a
CHECK signal to be displayed at the console of the
system if it is removed from its installation bracket. The
mounting bracket can also be made tamperproof by
breaking off the smaller tab at the scribed line (see Figure
6), thus preventing removal of the detector without a tool.
To remove the detector, use a small screwdriver to
depress the tamperproof tab and turn the detector
counterclockwise.
Testing
NOTE:
Before testing, notify the proper authorities that
the smoke detector system is undergoing
maintenance and will temporarily be out of
service. Disable the zone or system undergoing
maintenance to prevent unwanted alarms.
Detectors must be tested after installation and following
periodic maintenance. The 5808EU may be tested as
follows:
A. Test Switch
A recessed test switch is located on the detector housing.
Push and hold the recessed test switch with a 2.5mm
maximum diameter tool (an allen wrench or small
screwdriver). The LED on the detector should blink once
per second.
B. Test Module
(Model No. MOD400R)
The MOD400R test module can be used with a digital
multimeter or analog voltmeter to check the detector
sensitivity as described in the test module’s manual.
C. Smoke Entry Test
Hold a smoldering punk stick or cotton wick at the side of
the detector and gently blow smoke through the detector
until the unit alarms.
D. Direct Heat Method
(Hair dryer of 1000-1500 watts)
Direct the heat toward either side thermistor. Be sure to
hold the heat source about 30cm from the detector to
avoid damage to the plastic. The detector will reset only
after it has time to cool.
Smoke detection testing is recommended for verifying
system protection capability.
A detector that fails to activate with any of these tests
should first be cleaned as outlined in this manual's
MAINTENANCE section. If the detector still fails to
activate, return for repair.
Notify the proper authorities that the system is back on
line.
Testing Transmitter Signal
NOTE:
Remove battery tab before installation.
This test should be performed before installation to
determine a strong communication path with the control
panel and after installation is complete. Also, the
owner/user should test the unit at least weekly.
1. Activate the wireless system's TEST mode from the
console.
2. Depress and hold the smoke detector's TEST switch
and the detector should immediately transmit an alarm
signal to the control panel. The LED will start to blink
about 2.5 seconds after depressing the switch.
3. The wireless system's console should emit at least 3
audible sounds when the alarm transmission is
received and will display the trans-mitting detector's ID
number.
4. When the console has received the test signal, release
the TEST switch. The LED will immediately turn off,
and a few seconds later, the detector's ID number will
clear from the console display.
5. If the console does not respond as noted, check the
polarity of the batteries and be sure they are fresh. If
this is an initial installation, try moving the detector to
another location that provides proper reception. Also
be sure that the detector's ID has been enrolled by the
control panel (see PROGRAMMING). Then, repeat the
test.
6. Turn off the system's TEST mode from the console
(security code +
OFF).
Maintenance
NOTE:
Before removing the detector, notify the proper
authorities that the smoke detector is
undergoing maintenance and will be out of
service. If the detector will be out of service for
an extended period of time, disable the zone to
prevent unwanted alarms.
To clean or replace the filter, refer to Figure 8:
1. Remove the detector from its mounting plate (rotate
counter-clock-wise and pull straight out).
2. Carefully remove the two batteries.
3. Remove the detector cover (A) by using a thin-bladed
screwdriver to push back each of the four plastic
retention pads on the cover while applying constant
upward pressure on the battery-retaining plastic clip.
4. Remove the filter (B) by lifting straight out. Vacuum the
filter thoroughly.
5.
Clean the black-veined chamber section (C) by
vacuuming or blowing out dust and particles.
6. To reinstall the filter, position over the black-veined
chamber section (aligning two of the four legs of the
screen near the two thermistors), and snap into place.
Replacement filters are available (order part number
K4419).
7. Replace the cover by positioning the two V-notches in
the metal base with the V-shaped plastic guides on
both inner sides of the cover and snapping the metal
base into place.
8. Replace the batteries. Remount the detector to the
mounting plate.
9. Notify the proper authorities that the detector is back
on line.
A
COVER
B
FILTER
(REPLACEMENT
P/N K4419)
THERMISTOR
LED
PC BOARD
THERMISTOR
BATTERIES
TEST SWITCH
C
Figure 8. Removal of Cover and Filter for Cleaning
WARNING!
Limitations of Smoke Detectors / Transmitters
This smoke detector is designed to
activate and initiate
emergency action, but will do so only when used in
conjunction with an authorized fire alarm system.
Smoke detectors will not work without power. Battery-
powered smoke detectors will not work if batteries are
weak, missing, or improperly installed.
Alarm signals sent by the wireless transmitter in this
detector may be blocked or reflected by metal before
reaching the alarm receiver. Even if the signal path has
been recently checked, blockage can occur if a metal
object is moved into the path.
Smoke detectors will not sense fires that start where
smoke does not reach the detectors.
Smouldering
fires typically do not generate a lot of heat, which is
needed to drive smoke up to the ceiling where the smoke
detector is usually located. For this reason, there may be
large delays in detecting a smouldering fire with a
photoelectric-type detector. It may alarm only after
flaming has initiated, which will generate the heat needed
to drive the smoke to the ceiling.
Smoke from fires in chimneys, in walls, on roofs, or on
the other side of a closed door may not reach the smoke
detector and alarm it. A detector cannot quickly detect a
fire developing on another level of a building. Alarm
warning devices, such as bells or horns, may not alert
people or wake up sleepers if they are located on the
other side of closed or partly open doors, or on another
level. Persons may not hear a warning device over the
noise levels of a radio, air conditioner, other appliances,
or traffic. For this reason,
detectors and alarm horns
shall be located on every level and in every bedroom
within a building.
Alarm warning devices, however loud,
may not warn hearing-impaired people or waken deep
sleepers.
Smoke detectors shall be located in any room where
an alarm control is located, or in any room where
alarm control connections to an
AC source or phone
lines are made.
If detectors are not so located, a fire
within any of these rooms could prevent the control from
reporting a fire.
Smoke detectors have sensing limitations, too.
Photoelectronic detectors are required to pass fire tests
of the flaming and smouldering types. This is to ensure
that they can detect a wide range of fires.
Photoelectronic detectors sense smoldering fires better
than flaming fires, which have little, if any, visible smoke.
Because fires develop in different ways, and are often
unpredictable in their growth, this type of detector is not
always best, and a given detector may not always provide
early warning of a specific type of fire. In general,
detectors cannot be expected to provide warnings for
fires resulting from inadequate fire protection practices,
violent explosions, escaping gases that ignite, improper
storage of flammable liquids like cleaning solvents that
ignite, other similar safety hazards, arson, smoking in
bed, children playing with matches or lighters, etc. Smoke
detectors used in high air velocity conditions may cause
smoke detector alarm delay due to dilution of smoke
densities created by frequent and rapid air exchanges.
Additionally, high air velocity environments may create
increased dust contamination, demanding more frequent
detector maintenance.
To keep your equipment in excellent working order,
ongoing maintenance is required per the manufacturer’s
recommendations. A preventative maintenance
agreement should be arranged through the local
manufacturer’s representative. Though smoke detectors
are designed for long life, they may fail at any time. Any
smoke detector, fire alarm equipment, or any component
of that system which fails shall be repaired or replaced as
soon as possible.
LIMITED WARRANTY
Honeywell International Inc., acting through its Security &
Custom Electronics business ("Seller") 165 Eileen Way,
Syosset, New York 11791, warrants its product(s) to be in
conformance with its own plans and specifications and to be
free from defects in materials and workmanship under normal
use and service for 24 months from the date stamp control on
the product(s) or, for product(s) not having a manufacturer’s
date stamp, for 12 months from date of original purchase
unless the installation instructions or catalog sets forth a
shorter period, in which case the shorter period shall apply.
Seller's obligation shall be limited to repairing or replacing, at
its option, free of charge for materials or labor, any product(s)
which is proved not in compliance with Seller's specifications
or proves defective in materials or workmanship under normal
use and service. Seller shall have no obligation under this
Limited Warranty or otherwise if the product(s) is altered or
improperly repaired or serviced by anyone other than
Honeywell factory service. Connection of any device(s) to a
communicating bus of a Honeywell security system (e.g.,
keypad bus, polling loop) other than those manufactured or
approved by Honeywell shall void this warranty. For warranty
service, return product(s) transportation prepaid, to Honeywell
Factory Service, 165 Eileen Way, Syosset, New York 11791.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED,
OF MERCHANTABILITY, OR FITNESS FOR A
PARTICULAR PURPOSE OR OTHERWISE, WHICH
EXTEND BEYOND THE DESCRIPTION ON THE FACE
HEREOF. IN NO CASE SHALL SELLER BE LIABLE TO
ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL
DAMAGES FOR BREACH OF THIS OR ANY OTHER
WARRANTY, EXPRESS OR IMPLIED, OR UPON ANY
OTHER BASIS OF LIABILITY WHATSOEVER, EVEN IF THE
LOSS OR DAMAGE IS CAUSED BY THE SELLER'S OWN
NEGLIGENCE OR FAULT.
Seller does not represent that the product(s) it sells may not
be compromised or circumvented; that the product(s) will
prevent any personal injury or property loss by burglary,
robbery, fire or otherwise; or that the product(s) will in all
cases provide adequate warning or protection. Customer
understands that a properly installed and maintained alarm
system may only reduce the risk of a burglary, robbery, fire
,
or other events occurring without providing an alarm, but it is
not insurance or a guarantee that such will not occur or that
there will be no personal injury or property loss as a result.
CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY
FOR ANY PERSONAL INJURY, PROPERTY DAMAGE OR
OTHER LOSS BASED ON A CLAIM THAT THE
PRODUCT(S) FAILED TO GIVE WARNING. HOWEVER,
IF
SELLER
IS
HELD
LIABLE,
WHETHER
DIRECTLY
OR
INDIRECTLY,
FOR
ANY
LOSS
OR
DAMAGE
ARISING
UNDER
THIS
LIMITED
WARRANTY
OR
OTHERWISE,
REGARDLESS
OF
CAUSE
OR
ORIGIN,
SELLER'S
MAXIMUM
LIABILITY
SHALL
NOT
IN
ANY
CASE
EXCEED
THE
PURCHASE
PRICE
OF
THE
PRODUCT(S),
WHICH
SHALL
BE
THE
COMPLETE
AND
EXCLUSIVE
REMEDY
AGAINST
SELLER.
This warranty replaces any previous warranties and is the
only warranty made by Seller on this product(s). No increase
or alteration, written or verbal, of the obligations of this
Limited Warranty is authorized.
0560 DECLARATION OF CONFORMITY
The 5808EU is in conformity with the essential
requirements as described in Directive 1999/5/EC and
satisfies all the technical regulations applicable to the
product within this directive.
EN 300 220-1:2000
ETS 300 683:1997 EN 50130-4:1998
EN
60950:1992
Intended for use in Europe except Ireland and the UK.
Replace battery only with the same or equivalent type.
Dispose of used batteries according to the battery
manufacturer’s instructions.
165 Eilleen Way, Syosset, New York 11791
Copyright © 2006 Honeywell International Inc.
www.honeywell.com/security
ÊK4021ENV3ÅŠ
K4021ENV3 Rev. B
(Part of K4021V3 Rev. B 7/01)