background image

4. Test the detector immediately after completing the 

installation (as described in the TESTING section of 
this manual) and refer to the control system's 
instructions for additional information concerning the 
use of wireless smoke detectors. 

DO

NOT PA

IN

T

TAMPER SWITCH

ACTIVATOR

TAMPER SWITCH

ACTIVATOR

 

Figure 6. Detector Mounting Bracket 

 

 

Figure 7. Mount Detector Across Ceiling Panel Support 

 

CAUTION 

DO NOT attach the detector to removable ceiling panels. 
Attach the detector across panel support as shown in 
Figure 7. 

 

 

Tamper Protection

 

This detector has a built-in tamper switch that will cause a 
CHECK signal to be displayed at the console of the 
system if it is removed from its installation bracket. The 
mounting bracket can also be made tamperproof by 
breaking off the smaller tab at the scribed line (see Figure 
6), thus preventing removal of the detector without a tool. 
To remove the detector, use a small screwdriver to 
depress the tamperproof tab and turn the detector 
counterclockwise. 

 

Testing

 

NOTE: 

Before testing, notify the proper authorities that 
the smoke detector system is undergoing 
maintenance and will temporarily be out of 
service. Disable the zone or system undergoing 
maintenance to prevent unwanted alarms. 

Detectors must be tested after installation and following 
periodic maintenance. The 5808EU may be tested as 
follows: 

A. Test Switch 

A recessed test switch is located on the detector housing. 
Push and hold the recessed test switch with a 2.5mm 
maximum diameter tool (an allen wrench or small 
screwdriver). The LED on the detector should blink once 
per second. 

B. Test Module

 (Model No. MOD400R) 

The MOD400R test module can be used with a digital 
multimeter or analog voltmeter to check the detector 
sensitivity as described in the test module’s manual. 

C. Smoke Entry Test 

Hold a smoldering punk stick or cotton wick at the side of 
the detector and gently blow smoke through the detector 
until the unit alarms. 

D. Direct Heat Method

 (Hair dryer of 1000-1500 watts) 

Direct the heat toward either side thermistor. Be sure to 
hold the heat source about 30cm from the detector to 
avoid damage to the plastic. The detector will reset only 
after it has time to cool. 
Smoke detection testing is recommended for verifying 
system protection capability. 
A detector that fails to activate with any of these tests 
should first be cleaned as outlined in this manual's 
MAINTENANCE section. If the detector still fails to 
activate, return for repair. 
Notify the proper authorities that the system is back on 
line. 

 

Testing Transmitter Signal

 

NOTE:

 Remove battery tab before installation. 

This test should be performed before installation to 
determine a strong communication path with the control 
panel and after installation is complete. Also, the 
owner/user should test the unit at least weekly. 
1. Activate the wireless system's TEST mode from the 

console. 

2. Depress and hold the smoke detector's TEST switch 

and the detector should immediately transmit an alarm 
signal to the control panel. The LED will start to blink 
about 2.5 seconds after depressing the switch. 

3. The wireless system's console should emit at least 3 

audible sounds when the alarm transmission is 
received and will display the trans-mitting detector's ID 
number. 

4. When the console has received the test signal, release 

the TEST switch. The LED will immediately turn off, 
and a few seconds later, the detector's ID number will 
clear from the console display. 

5. If the console does not respond as noted, check the 

polarity of the batteries and be sure they are fresh. If 
this is an initial installation, try moving the detector to 
another location that provides proper reception. Also 
be sure that the detector's ID has been enrolled by the 
control panel (see PROGRAMMING). Then, repeat the 
test. 

6. Turn off the system's TEST mode from the console 

(security code + 

OFF). 

 

Maintenance

 

NOTE:

  Before removing the detector, notify the proper 

authorities that the smoke detector is 
undergoing maintenance and will be out of 
service. If the detector will be out of service for 
an extended period of time, disable the zone to 
prevent unwanted alarms. 

To clean or replace the filter, refer to Figure 8: 
1. Remove the detector from its mounting plate (rotate 

counter-clock-wise and pull straight out). 

2.  Carefully remove the two batteries. 
3. Remove the detector cover (A) by using a thin-bladed 

screwdriver to push back each of the four plastic 
retention pads on the cover while applying constant 
upward pressure on the battery-retaining plastic clip. 

4. Remove the filter (B) by lifting straight out. Vacuum the 

filter thoroughly. 

5. 

Clean the black-veined chamber section (C) by 
vacuuming or blowing out dust and particles. 

6. To reinstall the filter, position over the black-veined 

chamber section (aligning two of the four legs of the 
screen near the two thermistors), and snap into place. 
Replacement filters are available (order part number 
K4419). 

7. Replace the cover by positioning the two V-notches in 

the metal base with the V-shaped plastic guides on 
both inner sides of the cover and snapping the metal 
base into place. 

8. Replace the batteries. Remount the detector to the 

mounting plate. 

9. Notify the proper authorities that the detector is back 

on line. 

A

COVER  

B

FILTER

(REPLACEMENT

P/N K4419)

THERMISTOR

LED

PC BOARD

THERMISTOR

BATTERIES

TEST SWITCH

C

 

Figure 8. Removal of Cover and Filter for Cleaning 

 

WARNING! 

Limitations of Smoke Detectors / Transmitters 

This smoke detector is designed to 

activate and initiate

 

emergency action, but will do so only when used in 
conjunction with an authorized fire alarm system. 
Smoke detectors will not work without power. Battery-
powered smoke detectors will not work if batteries are 
weak, missing, or improperly installed. 
Alarm signals sent by the wireless transmitter in this 
detector may be blocked or reflected by metal before 
reaching the alarm receiver. Even if the signal path has 
been recently checked, blockage can occur if a metal 
object is moved into the path. 

Smoke detectors will not sense fires that start where 
smoke does not reach the detectors.

  Smouldering 

fires typically do not generate a lot of heat, which is 
needed to drive smoke up to the ceiling where the smoke 
detector is usually located. For this reason, there may be 
large delays in detecting a smouldering fire with a 
photoelectric-type detector. It may alarm only after 
flaming has initiated, which will generate the heat needed 
to drive the smoke to the ceiling. 
Smoke from fires in chimneys, in walls, on roofs, or on 
the other side of a closed door may not reach the smoke 
detector and alarm it. A detector cannot quickly detect a 
fire developing on another level of a building. Alarm 
warning devices, such as bells or horns, may not alert 
people or wake up sleepers if they are located on the 
other side of closed or partly open doors, or on another 
level. Persons may not hear a warning device over the 
noise levels of a radio, air conditioner, other appliances, 
or traffic. For this reason, 

detectors and alarm horns 

shall be located on every level and in every bedroom 
within a building.

 Alarm warning devices, however loud, 

may not warn hearing-impaired people or waken deep 
sleepers. 

Smoke detectors shall be located in any room where 
an alarm control is located, or in any room where  
 

 
 
 

alarm control connections to an 

AC source or phone 

lines are made.

 If detectors are not so located, a fire 

within any of these rooms could prevent the control from 
reporting a fire. 

Smoke detectors have sensing limitations, too.

 

Photoelectronic detectors are required to pass fire tests 
of the flaming and smouldering types. This is to ensure 
that they can detect a wide range of fires. 
Photoelectronic detectors sense smoldering fires better 
than flaming fires, which have little, if any, visible smoke. 
Because fires develop in different ways, and are often 
unpredictable in their growth, this type of detector is not 
always best, and a given detector may not always provide 
early warning of a specific type of fire. In general, 
detectors cannot be expected to provide warnings for 
fires resulting from inadequate fire protection practices, 
violent explosions, escaping gases that ignite, improper 
storage of flammable liquids like cleaning solvents that 
ignite, other similar safety hazards, arson, smoking in 
bed, children playing with matches or lighters, etc. Smoke 
detectors used in high air velocity conditions may cause 
smoke detector alarm delay due to dilution of smoke 
densities created by frequent and rapid air exchanges. 
Additionally, high air velocity environments may create 
increased dust contamination, demanding more frequent 
detector maintenance. 
To keep your equipment in excellent working order, 
ongoing maintenance is required per the manufacturer’s 
recommendations. A preventative maintenance 
agreement should be arranged through the local 
manufacturer’s representative. Though smoke detectors 
are designed for long life, they may fail at any time. Any 
smoke detector, fire alarm equipment, or any component 
of that system which fails shall be repaired or replaced as 
soon as possible. 

 

LIMITED WARRANTY 

Honeywell International Inc., acting through its Security & 
Custom Electronics business ("Seller") 165 Eileen Way, 
Syosset, New York 11791, warrants its product(s) to be in 
conformance with its own plans and specifications and to be 
free from defects in materials and workmanship under normal 
use and service for 24 months from the date stamp control on 
the product(s) or, for product(s) not having a manufacturer’s 
date stamp, for 12 months from date of original purchase 
unless the installation instructions or catalog sets forth a 
shorter period, in which case the shorter period shall apply. 
Seller's obligation shall be limited to repairing or replacing, at 
its option, free of charge for materials or labor, any product(s) 
which is proved not in compliance with Seller's specifications 
or proves defective in materials or workmanship under normal 
use and service. Seller shall have no obligation under this 
Limited Warranty or otherwise if the product(s) is altered or 
improperly repaired or serviced by anyone other than 
Honeywell factory service. Connection of any device(s) to a 
communicating bus of a Honeywell security system (e.g., 
keypad bus, polling loop) other than those manufactured or 
approved by Honeywell shall void this warranty.  For warranty 
service, return product(s) transportation prepaid, to Honeywell 
Factory Service, 165 Eileen Way, Syosset, New York 11791. 
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, 
OF MERCHANTABILITY, OR FITNESS FOR A 
PARTICULAR PURPOSE OR OTHERWISE, WHICH 
EXTEND BEYOND THE DESCRIPTION ON THE FACE 
HEREOF. IN NO CASE SHALL SELLER BE LIABLE TO 
ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL 
DAMAGES FOR BREACH OF THIS OR ANY OTHER 
WARRANTY, EXPRESS OR IMPLIED, OR UPON ANY 
OTHER BASIS OF LIABILITY WHATSOEVER, EVEN IF THE 
LOSS OR DAMAGE IS CAUSED BY THE SELLER'S OWN 
NEGLIGENCE OR FAULT. 
Seller does not represent that the product(s) it sells may not 
be compromised or circumvented; that the product(s) will 
prevent any personal injury or property loss by burglary, 
robbery, fire or otherwise; or that the product(s) will in all 
cases provide adequate warning or protection. Customer 
understands that a properly installed and maintained alarm 
system may only reduce the risk of a burglary, robbery, fire

,

 

or other events occurring without providing an alarm, but it is 
not insurance or a guarantee that such will not occur or that 
there will be no personal injury or property loss as a result. 
CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY 
FOR ANY PERSONAL INJURY, PROPERTY DAMAGE OR 
OTHER LOSS BASED ON A CLAIM THAT THE 
PRODUCT(S) FAILED TO GIVE WARNING. HOWEVER,

 

IF

 

SELLER

 

IS

 

HELD

 

LIABLE,

 

WHETHER

 

DIRECTLY

 

OR

 

INDIRECTLY,

 

FOR

 

ANY

 

LOSS

 

OR

 

DAMAGE

 

ARISING

 

UNDER

 

THIS

 

LIMITED

 

WARRANTY

 

OR

 

OTHERWISE,

 

REGARDLESS

 

OF

 

CAUSE

 

OR

 

ORIGIN,

 

SELLER'S

 

MAXIMUM

 

LIABILITY

 

SHALL

 

NOT

 

IN

 

ANY

 

CASE

 

EXCEED

 

THE

 

PURCHASE

 

PRICE

 

OF

 

THE

 

PRODUCT(S),

 

WHICH

 

SHALL

 

BE

 

THE

 

COMPLETE

 

AND

 

EXCLUSIVE

 

REMEDY

 

AGAINST

 

SELLER. 

This warranty replaces any previous warranties and is the 
only warranty made by Seller on this product(s). No increase 
or alteration, written or verbal, of the obligations of this 
Limited Warranty is authorized. 
 

 

0560  DECLARATION OF CONFORMITY

 

The 5808EU is in conformity with the essential 
requirements as described in Directive 1999/5/EC and 
satisfies all the technical regulations applicable to the 
product within this directive. 
EN 300 220-1:2000 

ETS 300 683:1997   EN 50130-4:1998

 EN 

60950:1992 

Intended for use in Europe except Ireland and the UK. 
Replace battery only with the same or equivalent type. 
Dispose of used batteries according to the battery 
manufacturer’s instructions. 

 

 

 

165 Eilleen Way, Syosset, New York 11791 

Copyright © 2006 Honeywell International Inc. 

www.honeywell.com/security 

ÊK4021ENV3ÅŠ 

K4021ENV3  Rev. B

 (Part of K4021V3 Rev. B  7/01) 

Reviews: