ÊN8910V2OŠ

 

N8910V2 5/11  Rev. B

 

4229 ADDRESS SETTINGS

SWITCH

NUMBER

("—" means "OFF")

0

1

2

3

4

5

6

7

8

9

10 11 12 13 14 15

2

ON — ON — ON — ON — ON — ON — ON — ON —

3

ON ON — — ON ON — — ON ON — — ON ON — —

4

ON ON ON ON — — — — ON ON ON ON — —

— —

5

ON ON ON ON ON ON ON ON — —

— — — — — —

12

34

5

OFF

ON

DIP SWITCH: 

(WHITE AREAS DENOTE SWITCH HANDLES)

4229-003-V1

POSITIONS 2-6: 

POSITION 1:

DETERMINE ZONE EXPANDER'S ADDRESS. CONSULT CONTROL'S INSTRUCTIONS
FOR ADDRESS USE. 

SWITCH SETTING SHOWN SET FOR ADDRESS "0".

DETERMINES ZONE A's RESPONSE TIME:

ON = NORMAL (300MS) RESPONSE, SHOWN (AS SHIPPED).
OFF = FAST (10MS) RESPONSE TO AN OPEN.

6

ON ON ON ON ON ON ON ON

67

8

16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

ON — ON — ON — ON — ON — ON — ON — ON —

ON ON — — ON ON — — ON ON — — ON ON — —

ON ON ON ON — — — — ON ON ON ON — — — —

ON ON ON ON ON ON ON ON — — — — — — — —

— — — — — — — —

— — — — — — —

ON ON ON ON ON ON ON ON

POSITION 7:

POSITION 8:

DIP SWITCH POSITION #7: NOT USED LEAVE ON

DIP SWITCH POSITION #8: CASE TAMPER ON = DISABLED  OFF= ENABLED

NOTE:

 ADDRESSES 16-31 MAY NOT BE AVAILABLE; CONSULT THE HOST CONTROL PANEL

            INSTALLATION INSTRUCTIONS.

 

 

 

 

EOLR value is 2K ohms. 

 

GRN

BLK

(–) GROUND

RED

(+) 12V

YEL

PIN

1

4

3

2

1

ZONES

DIP SWITCH

FOR SETTING
ADDRESS AND
ZONE "A" RESPONSE

TB1

WIRED ZONE

EXPANDER/RELAY

MODULE

TB2

RELAY

2

RELAY

1

DATA OUT
TO CONTROL

DATA IN
FROM CONTROL

REED

(TAMPER)

SWITCH

TERMINATE EACH PROGRAMMED ZONE
WITH 2K OHM END-OF-LINE RESISTOR
(EACH ZONE'S MAX. LOOP RESISTANCE:
300 OHMS + EOL)

4-PIN

CONSOLE

PLUG 

EITHER

OR BOTH

CAN BE

USED 

4229-004-V1

2

3

4

5

6

1

7

8

BRN

WHT

GRY
VIO
BLK

YEL
ORG

NO

NC

C

GND

NO

NC

C

RLY

1

RLY

2

RELAYS

"OFF"

RELAY

CONNECTOR

{

{

{

1

2

3

4

5

8

11

2

1

3

4

6

7

9

10

12

A

B

C     D

F

G

H

E

2K

 

 
 

FOR LIMITATIONS OF THE ENTIRE ALARM SYSTEM, REFER TO THE INSTALLATION AND SETUP GUIDE FOR THE CONTROL 
PANEL WITH WHICH THIS DEVICE IS USED. 

 

For the latest warranty information, please go to: 

http://www.security.honeywell.com/hsc/resources/wa

 

2 Corporate Center Drive, Suite 100

P.O. Box 9040, Melville, NY 11747

Copyright © 2008 Honeywell International Inc.

 