Honeywell ADEMCO 4229 Installation And Setup Manual Download Page 1

 

 

ADEMCO 4229

WIRED ZONE EXPANDER/RELAY MODULE

INSTALLATION AND SETUP GUIDE

 

 

 
GENERAL INFORMATION 

The ADEMCO 4229 Wired Zone Expander/Relay Module 
adds up to eight end-of-line resistor supervised zones and 
two dry form C (SPDT) relay outputs to compatible control 
communicators via the control’s keypad wiring. 

The module may be mounted within the control’s cabinet (if 
room permits), or remotely.  If mounted remotely, there are 
provisions to tamper-protect the unit.  Communication to the 
module is supervised so that it cannot be disconnected from 
the keypad wiring without detection by the control.  If the 
wiring is cut, a tamper or alarm signal will result, to indicate 
that this device (and possibly other similarly connected 
devices) has become inoperative. 

IMPORTANT

: Some carbon monoxide detectors may not be 

compatible with the ADEMCO 4229 hardwire zone 
expanders. When using carbon monoxide detectors in 
systems that support the 4229 zone expanders, install the 
detectors only on the basic hardwire zones of the system 
control panel, and NOT on the zone expanders. 

INSTALLATION

 

When the module is to be mounted inside the control’s 
cabinet, it should be mounted horizontally.  Insert self-
tapping screws (provided) in two adjacent raised tabs at the 
back of the cabinet.  Leave the heads projecting 1/8”.  Hang 
the module on the screw heads via two of the slotted holes 
on the back of its housing.  In this case, the module’s cover 
need not be tamper protected.  

See the control’s instructions 

for additional information. 

When the module is to be mounted remotely, holes on its 
back permit it to be mounted horizontally or vertically.

  Wires 

can exit from the side or the breakout on the back of its 
housing.  Place DIP switch #8 in the OFF position and, 
when the installation is completed, the module’s cover put 
on.  A magnet in the cover, positioned near a reed switch in 
the unit, will cause a tamper signal to be sent to the control if 
the cover is removed.  

Affix the connections label that accompanies the unit to the 
inside of the module’s cover (if the cover is to be used)) or to 
the inside of the control’s cover 

CONNECTIONS AND SETTINGS

 

See the table and the diagram on the reverse side. 
Make protection zone connections to 12-position terminal 
block TB1.  Each zone that is used must have a 

2K ohm 

end-of-line resistor 

connected 

across the end of its loop, 

as shown. 

 

 

If a zone is not programmed, the resistor need not be used. 
The method of programming each zone for type of alarm 
and reporting code to the central monitoring station varies 
with the control to which the module is connected.  Refer to 
the installation instructions for that control unit. 

Set the DIP switch to one of 31 addresses, as shown in the 
table on the reverse side, so the control can identify the 
module and communicate with it properly.  

The address to 

be set is determined by the particular control to be used, 
and the control’s installation instructions must be consulted.  
As shipped, the DIP switch is set for an address of “0.” 

Zone A can be set for a fast response time of 10ms to an 
open circuit, if desired, by setting position 1 of the DIP 
switch to “OFF.”  As shipped, it is set to “ON” for a response 
time of 300ms, as shown in the table on the reverse side.  
All of the module’s other protection zones have a nominal 
response time of 300ms. 

Connections to the module’s two relays are made via the 7-
conductor cord provided.  Refer to the control’s installation 
instructions for specific information on how to program the 
control’s various activation options for the relays. 

Connections to the control’s keypad wiring points can be 
made via 4-position terminal block TB2, the 4-pin plug, or 
both (wire color connections are the same) 

SPECIFICATIONS

 

Physical 

6-7/16”W x 4-1/4”H x 1-1/4”D 

 

(163mm x 108mm x 32mm) 

Electrical 

Input Voltage:   12VDC (from control’s remote keypad 
 connection 

points) 

Input Current: 

30mA (relays off) 

 

100mA (relays on) 

Relay Contact 
 

Rating:  2A max. at 28VDC/AC 

 

 

 

 

 