Honeywell ADEMCO 4190SN Installation And Setup Manual Download Page 2

 

 

4190SN

TAMPER PINS
(SHORTENED WHEN
COVER IS IN PLACE)

MOUNTING
HOLES (3)

BLUE

JUMPER

TERMINAL ASSIGNMENT

1 (+)  POLLING LOOP (+)
2 (-)   POLLING LOOP (-)
3 (+)  LEFT LOOP 1 (+)
4 (-)   COMMON (-)
5 (+)  RIGHT LOOP 2 (+) 

RPM

+

+

RPM

+

- ALWAYS OBSERVE POLARITY.

ALWAYS CONNECT IN PARALLEL.
SEE TEXT FOR WIRE GUAGE AND WIRE LENGTH LIMITS.


RIGHT LOOP (LOOP 2): FOR N.C. SERIES CIRCUITS
ONLY. USE SEALED (REED) CONTACTS. SEE NOTE 1.
RIGHT LOOP NOT SUPERVISED. SEE UL NOTE 2 BELOW. 

LEFT LOOP (LOOP 1): FOR N.C. CIRCUIT (INTERNAL EOLR)
OR N.C. AND/OR N.O. CIRCUIT (EXTERNAL EOLR). SEE
NOTES 2 AND 3. LEFT LOOP SUPERVISED. CLASS B, STYLE B. 

SERIAL # ID 

4190SN-001-V1

POLLING LOOP - SUPERVISED CLASS B, STYLE 4

CIRCUIT, 25 OHM MAX LINE IMPEDANCE

POLLING LOOP
TERMINALS ON

CONTROL

RED

JUMPER

 

UL Notes 

1.

 

The 4190SN is designed to meet 
the following UL standards: 
UL609 Commercial Burglary, 
UL864 Commercial Fire, UL985 
Household Fire, and UL1023 
Household Burglary  

2.

 

The right loop may not be used 
for Commercial Fire or UL 
Commercial Burglary 
installations. 

3.

 

For Commercial Fire usage: Use 
N.O. contacts on the left loop.  
Supervise (style B) this loop 
using Model #EOL100 Fire Listed 
10K ohm EOLR.  

4.

 

For UL Commercial Burglary 
Usage: Use N.O. or N. C. contacts 
on the left loop.  Supervise using 
the 10K ohm EOLR supplied. 

5.

 

All circuits are power-limited. 

6.

 

For dry indoor use only. 

7.

 

Do not install in air-handling spaces. 

 

Note:

 See control panel instructions for 

minimum earth ground impedance. 

 

Specifications 

 

Physical: 

Width: 2-1/8” (53mm) 
Height:

  

3-1/4” (81mm) 

Depth:

  

1” (25mm) 

 

Electrical: 

Voltage Input: 8 – 12VDC 
Current Drain: 2mA  

 

Max. Loop Wire Run: 100’ 
Wire Gauge: 18-22 AWG 
Max. Loop Line Impedance: 300 ohm 
max. 

REFER TO THE INSTALLATION 
INSTRUCTIONS FOR THE CONTROL 
PANEL WITH WHICH THE DEVICE IS 
USED, FOR DETAILS ON LIMITATIONS 
OF THE ENTIRE ALARM SYSTEM. 

 

NFPA-72 Compliant 

 

For the latest warranty information, 

please go to: 

http://www.security.honeywell.com/hsc/r
esources/wa/index.html

 

 

ÊN6450-1V1cŠ 

N6450-1V1  2/09  Rev. A 

 

2 Corporate Center Drive, Suite 100 

P.O. Box 9040, Melville, NY  11747 

Copyright

 2009  

Honeywell International Inc. 

www.honeywell.com/security

 

 

 

 