Honeywell ADEMCO 4190SN Installation And Setup Manual Download Page 1

N6450-1V1  2/09  Rev. A 

ADEMCO 4190SN 

V-Plex

®

 Two-Zone (SIM) 

Serialized Interface Module 

INSTALLATION AND SETUP GUIDE 

 

General Information 

The ADEMCO 4190SN V-Plex

®

 is a 2-

zone expander, which allows use of the 
available expansion zones provided by 
controls that support V-Plex loop 
devices.  The 4190SN consists of two 
protection loops, known as the left 
(primary) and right (secondary) loops. 

The left loop can be used for: 

 

closed-circuit devices, with or with 

out EOLR supervision 

 

open-circuit devices with EOLR 

supervision 

 

fast-response (10 millisecond) 

devices. 

Follow the chart to the right for 
cutting the correct jumpers and 
choosing the correct resistor when 
using the left loop. 

 

The right loop can be used for: 

 

closed-circuit devices only 

 

has no EOLR supervision 

 

400 millisecond response time. 

The jumpers do not affect the 
operation of the right loop.  The right 
loop cannot be used alone. 

 

Supervision 

The tamper/supervision response of 
the 4190SN is determined by the zone 
response type assigned to the left loop 
zone.  While the system is armed, 
tamper/supervisory faults will report 
as alarms if the left loop zone is 
assigned a burglary response type and 

will report as troubles if the left loop 
zone is assigned a non-burglary 
response type (i.e., fire, panic, aux).   
While the system is disarmed, tamper/ 
supervisory will always report as 
troubles. 

 

Programming Notes 

 

Program the unit like any other zone, 
according to the alarm control’s 
installation instructions.  Enter the 
following information when prompted 
for in programming: 
“INPUT TYPE” = “6” (SL—Serial 

    Number Device) 

Left Zone = Loop 1 
Right Zone = Loop 2 

 

JUMPERS 

USAGE (APPLIES TO 
LEFT ZONE – LOOP 1 
ONLY) 

RED 

Cut for fast response 
(10msec) 

BLUE 

Cut for use with no 
EOLR (closed-circuit 
only).  Doing this 
automatically puts an 
internal 10K ohm resistor 
in series with the zone. 

NONE CUT 

Use the 10K ohm 
resistor provided, with 
switches in either an 
open-circuit or closed 
circuit configuration. The 
4190SN draws 2mA from 
the V-Plex loop in this 
mode. 

 

 