6808 Manual — P/N LS10146-001SK-E:C 09/28/2017
31
Control Panel Installation
Using this value, and referring to the Wiring Distance table, it can be found that the available options are:
370 feet maximum using 22 Gauge wire
938 feet maximum using 18 Gauge wire
1493 feet maximum using 16 Gauge wire
2362 feet maximum using 14 Gauge wire
4.4.2 Wiring Configurations
Figure 4.8 illustrates Class B configurations wiring.
Figure 4.8 SBUS Class B Wiring
5860 Current Draw
= 2 x .100 amps
= .200 amps
5496 Current Draw
= 1 x .010 amps
= .010 amps
5865 Current Draw
= 1 x .200 amps
= .200 amps
5824 Current Draw
= 1 x .040 amps
= .040 amps
Total Worst Case Current Draw
= .450 amps
NOTE:
For assistance with SBUS calculation, please refer to www.silentknight.com.
Supervised
Power Limited