MOUNTING 

After enrolling and before mounting permanently, conduct Go/No Go test (see controller’s 

instructions) to verify adequate signal strength. Adjust the device location as necessary. 
1.  Using two supplied screws and anchors, mount the base.  
2.  Attach the smoke detector to the mounting base with a clockwise motion.   
3.  Test each detector as described in the Testing section. 
4.  Confirm all desired signals have been received by the Central Station. 

NOTE:

 NFPA 72 recommends the installation of detectors only after completing 

construction or any other dust producing activity. 

 

 

TESTING 

Test communications between the detector and the control panel.  

The detector mode has two test buttons; one for smoke testing and 

one for CO testing. 

 

The detector may also be functionally tested using canned smoke 

and canned CO.  If the detector fails any of the test methods, the 

detector should be replaced. 

NOTE:

 Testing the detector will activate the alarm and send a signal to 

the panel. 

Before testing, notify the proper authorities to avoid any 

false alarms.  

Smoke Test  (Alarm Test)

 

Press and hold the Smoke Test button for 1 to 2 seconds. The 

detector will sound and illuminate per Table 2 and send a smoke 

alarm signal to the control panel (all programmed smoke detector 

loops are signaled). Verify that the smoke alarm signal was 

received at the control panel.  

Smoke System Test (Functional Smoke Test) 

Press and hold the Smoke Test button for 3 to 5 seconds to enter 

the functional smoke test mode. 

See Functional Smoke Test section. 

NOTE

:  Detector sounds an alarm when using canned smoke 

only

 when in 

Functional Test mode (canned smoke does not cause alarm 

sounding when in normal mode). 

Functional Smoke Test 

With the detector in smoke system (functional) test mode, spray 

canned smoke into the detector. The canned smoke that can be 

used and is approved for test include: Home Safeguard Industries 

25S, SDi CHEK02 and CHEK06, SDi SOLOA4, and SDi 

SMOKESABRE. 

1. 

The detector will sound and illuminate per Table 2 and a smoke 

alarm signal will be sent to the panel.   

2. 

Verify the smoke alarm signal was received by the control panel. 

CO Test (Alarm Test) 

Press and hold the CO Test button for 1 to 2 seconds. The control 

panel should display and sound a CO alarm (all programmed CO 

detector loops are sent). 

CO System Test (Functional CO Test) 

Press and hold the CO Test button for 3-5 seconds to enter the 

functional gas test mode. 

See Functional Gas Test section below.  

 

Functional Gas Test 

Solo C6 brand canned CO may be used to verify the detector’s 

ability to sense CO by utilizing the RealTest® feature as follows: 
1.  Press and hold the CO test button for 3 to 5 seconds. The green 

LED will start blinking once per second indicating the detector is 

in RealTest® mode. (If the detector will not go into RealTest® 

mode, the CO sensor may be in fault or at end-of-life.) 

2.  While the green LED is blinking once per second, spray a small 

amount of canned CO directly into the CO gas entry port.  

3.  Upon successful gas entry and if functioning properly, the 

detector will go into CO alarm and send an alarm to the control 

panel. 

4.  The CO test will automatically clear when the CO clears from the 

sensor or in 30 seconds if no CO was introduced.

 

 

 

 

 

 

 

Table 2: LED Indication & Sounder during Test and Trouble 

MODE 

 

Status LED 

(Top) 

Side LED 

Windows 

 

Sounder 

Speaker 

 

Smoke Test   

Blink Red 

once every 

second 

Dark 

Temp-3 

Warning of alarm 

signal  transmission.  

Voice smoke  

warning 

Smoke System 

(functional) Test 

Blink Red 

once every 10 

secs 

Blink once 

every  

10 secs 

 

 

CO Test   

Blink Red 

once every 

second 

Dark 

Temp-3 

Warning of alarm 

signal  transmission.  

Voice smoke  

warning 

RealTest™   

Functional CO  gas entry 

test – 

Waiting for gas 

entry 

Blink Green 

once per 

second 

Dark 

Silent 

Voice instructions for 

testing; warning of 

alarm signal 

RealTest™   

Functional CO  gas entry 

test  -

Upon successful 

gas entry

 

Blink Red 

once every  

10 secs 

Blink blue 

every  

10 secs 

Modified 

Temp-4 

Voice carbon 

monoxide warning 

Low Battery 

Blink Amber 

every 

10 secs 

Dark 

Chirp every 45 

secs after 

7 days 

Voice instructions 

when chirp is  

hushed by pressing 

either test button 

Smoke Maintenance 

Blink Amber 

every 5 secs 

Dark 

Silent 

Voice smoke 

maintenance 

instructions if either 

test button is pressed 

CO Trouble 

Double 

Blink  Amber  

every 5 secs 

Dark 

Silent 

 

CO End of Life – 

First 

29 days

 

Double 

Blink Amber  

every 3 secs 

Dark 

Silent 

Voice end-of- life 

instructions 

when either test 

button 

 is pressed

 

CO End of Life – 

after 

30 days 

 

Double 

Blink Amber 

every 3 secs 

Dark 

Chirp every 

45 secs 

Voice end-of-life 

instructions when  

either test button 

is pressed

 

Power Up 

Blink Green, for 

30 secs  

Dark 

Silent 

Language set 

instructions only on 

first time power-up  

Normal (Standby) 

Single Blink 

Green every 10 

secs 

Dark 

Silent 

Silent 

Freeze Warning (low 

temp) 

Blink Red 

every  

10 secs 

 

 

 

 

Summary of Contents for 5800COMBO

Page 1: ... the smoke detector zone Loop 1 Zone Type 09 Fire or 16 Fire with Verification Input Type 03 Supervised RF When prompted for the serial number press and release the Smoke Test button for 1 second The sensor sends two transmissions for enrollment Alternatively you can manually enter the smoke sensor serial number found on the unit s label 4 If Maintenance monitoring is desired VISTA 15P 20P 21iP LY...

Page 2: ... Test Functional CO Test Press and hold the CO Test button for 3 5 seconds to enter the functional gas test mode See Functional Gas Test section below Functional Gas Test Solo C6 brand canned CO may be used to verify the detector s ability to sense CO by utilizing the RealTest feature as follows 1 Press and hold the CO test button for 3 to 5 seconds The green LED will start blinking once per secon...

Page 3: ... from children Dispose of used batteries properly Remove old batteries Wait 10 seconds and then replace with four new batteries To avoid a low battery indication when installing new batteries all 4 batteries must be installed within 15 seconds of installing the first one Any low battery condition that may have occurred should clear when the base plate is installed CLEANING NOTE Notify the proper a...

Page 4: ... including interference that may cause undesired operation SUPPORT WARRANTY For the latest documentation and online support information please go to https mywebtech honeywell com For the latest warranty information please go to www honeywell com security hsc resources wa For patent information see www honeywell com patents MyWebTech Warranty Patents REFER TO THE INSTALLATION INSTRUCTIONS FOR THE C...

Reviews: