FEATURES
•
Multi-Criteria Sensing:
uses four
sensing elements to react faster
while minimizing false alarms:
-
Photoelectric smoke sensor
detects airborne smoke particles
-
Carbon Monoxide (CO) sensor
detects smoldering fires
-
Infrared (IR) sensor measures
ambient light and flame
signatures, such as flame flicker
-
Thermal detection monitors for
dangerous rise in temperature
•
Low Temperature sensing:
senses ambient temperature
and reports if temperature goes
below 41°F (5°C).
•
CO Detector End-of-Life
reporting (detector needs
replacing)
•
Smoke detector maintenance
reporting (detector needs
cleaning)
•
Low Battery Detection
Table 1: Operation Modes
MODE
Status LED
(Top)
LED Windows
(Side)
Sounder
Speaker
Power Up
Blink Green,
every 2 secs
Dark
Silent
Voice welcome,
instructions after first
time power up or
after default
Normal
(Standby)
Single Blink
Green every
10 secs
Dark
Silent
Silent
Smoke
Alarm
Blink Red
every 10 secs
Blink red
Temp-3
Voice smoke
warning
Thermal
Alarm
Blink Red
every 10 secs
Blink red
Temp-3
Voice smoke
warning
CO Alarm
Blink Red
every 10 secs
Blink blue
Temp-4
Voice CO
warning
Powered
Down
Dark
Dark
Silent
Silent
POWER UP and LANGUAGE SELECTION
•
Remove battery pull tabs. Be sure batteries are seated
properly to avoid a low battery condition after 15 seconds.
•
Upon power up, Green LED Blinks every 2 secs / Sounder
is Silent. After power up, the detector prompts for
language selection.
•
Select the desired language.
English:
Press the Smoke (•) test button
Spanish: Press the CO (••) test button
RESETTING THE LANGUAGE
1. Press and hold both the Smoke and CO test
switches simultaneously for 10 seconds, then
release. The green light flashes rapidly.
2. Press and hold both buttons again for one
second and release. The sensor begins
speaking a Welcome message.
3. Select the desired language by pressing the
corresponding Smoke (English) or CO
(Spanish) test button.
ENROLLMENT
IMPORTANT:
The Smoke and Carbon Monoxide (CO) sensors each have unique serial numbers and must be enrolled in separate zones.
Enroll the Smoke Sensor
1. Remove the detector from the base plate (tamper switch must be faulted
when enrolling).
2. Put the control panel in Zone Programming mode.
3. Assign a zone number for the smoke detector zone.
Loop = 1; Zone Type = 09 (Fire) or 16 (Fire with Verification)
Input Type = 03 (Supervised RF)
When prompted for the serial number, press and release the Smoke Test
button for 1 second. The sensor sends two transmissions for enrollment.
Alternatively, you can manually enter the smoke sensor serial number
found on the unit’s label.
4. If Maintenance monitoring is desired:
VISTA-15P/20P/21iP, LYNX Touch, & Lyric: A
ssign a separate zone number
using the Smoke Detector serial number.
Loop = 2 (maintenance); Zone Type = choose a zone type based on
desired operation (ex.24 hr Trouble, Monitor, or Auxiliary)
Input Type = 03 (Supervised RF)
VISTA-128/250 Series: Enable “Smart Contact” option in zone
programming menu for the assigned smoke detector zone.
5. If Low Temperature reporting is desired, program a separate zone for this
smoke detector serial number
Loop = 3; Zone Type = choose a zone type based on desired
operation (ex.24 hr Trouble, Monitor, or Auxiliary);
Input Type = 03 (Supervised RF).
WARNING
:The fire protection zone must always be enrolled as Loop 1.
Otherwise, fire alarms will not be reported by the control.
Enroll the CO Sensor
1. Remove the detector from the base plate.
2. With the control panel in Zone Programming mode, assign a zone
number for the CO detector zone.
Loop = 1; Zone Type =14 (CO alarm); Input Type = 3 (Supervised RF)
When prompted for the serial number, press and release the CO Test
button for 1 second. The sensor sends two transmissions for
enrollment. Alternatively, you can manually enter the CO sensor serial
number, which is the smoke serial number plus 1 (ex. if smoke s/n is
0000781, the CO s/n is 0000782).
3. If End-of-Life monitoring is desired:
VISTA-15P/20P/21iP, LYNX Touch, & Lyric: automatically sent
VISTA-128/250 Series: program a separate zone for the CO serial no.
Loop = 2; Zone Type = choose a zone type based on desired
operation (
ex.24 hr Trouble or Auxiliary
); Input Type = 03 (
Supervised RF
)
5800COMBO - Combination Smoke/Carbon Monoxide (CO) Detector w/Built-in Wireless Transmitter
(features voice and 360 degree viewable LED ring)
INSTALLATION AND SETUP GUIDE
This device is intended for use with Honeywell control panels that support 5800 series devices. Before installing detectors, please
thoroughly read these installation instructions and read the
Limitations of Fire Alarm Systems
Insert (P/N 800-15144 5/13) and
System
Smoke Detectors Application Guide
(P/N SPAG9101 7/12).