Model 5496 Intelligent Power Module Installation and Operation Manual 151276-L8
3-6
3.4.2
Class B Supervised Wiring
Figure 3-6 shows how to wire for Class B output supervision. Use in/out wiring
methods for proper supervision. Refer to Section 4 for notification appliances that
must be used with the 5496.
Class B Output Notification Circuits
Figure 3-6 shows four, 1.5 amp devices wired as Class B circuits.
Place a 4.7k ohm EOL resistor (provided) at the end of each circuit to enable
supervision when using all outputs as Class B notification appliance circuits. The 4.7k
EOLs must be wired to the terminals whether or not you are using all output
terminals.
Figure 3-6 Regulated Class B Supervised Input/Output Connections
3.4.3
Releasing Operations
Approved releasing solenoids are list in Table 3-1
.
Do not mix cross alarming zones
with smoke verification zones. There must be at least two automatic detection
devices in each protected space. Spacing must be reduced to 0.7 times the linear
spacing in accordance with NFPA 72.
Table 3-1: Approved Releasing Solenoids
Manufacturer
Part Number
Rating
Current
Freq
Asco
T8210A107
24 VDC
3A max
0 Hz
8210G207
24 VDC
3A max
0 Hz
Power Limited
1.5
Ω
max