511391
201T User Manual
17
2/07
Honeywell
Detection Range and Alarm Levels
Detection Range and Alarm Levels
A different alarm level may have been programmed in order to satisfy
the constraint of a particular application.
Gas Detected
Range
Alarm A
Alarm B
AlarmC
C
2
H
4
O
Ethylene oxide
0-20.4 ppm 1.0 ppm
5.0 ppm
9.0 ppm
CL
2
Chlorine
0-15.3 ppm 0.5 ppm
1.0 ppm
13.0 ppm
CO50
Carbon monoxide 0-51 ppm
9 ppm
15 ppm
45 ppm
CO100 Carbon monoxide 0-102 ppm
25 ppm
45 ppm
90 ppm
CO250 Carbon monoxide 0-255 ppm
25 ppm
200 ppm
225 ppm
CO500 Carbon monoxide 0-510 ppm
50 ppm
250 ppm
450 ppm
CO1000 Carbon monoxide 0-1020 ppm 100 ppm
500 ppm
900 ppm
H
2
S
Hydrogen sulfide
0-51 ppm
10 ppm
15 ppm
45 ppm
H
2
Hydrogen
0-2.55% Vol. 1.00% Vol. 2.00%
Vol. 2.25%
Vol.
HCL
Hydrogen chloride 0-51 ppm
3 ppm
4 ppm
45 ppm
HCN
Hydrogen cyanide 0-51 ppm
5 ppm
9 ppm
45 ppm
NO
Nitrogen monoxide 0-102 ppm
25 ppm
35 ppm
90 ppm
NO
2
Nitrogen dioxide
0-10.2 ppm 0.72 ppm
2 ppm
9 ppm
O2 Oxygen
0-25.5%
Vol.
19.5%
Vol. 22.0%
Vol. 23.0%
Vol.
SO
2
Sulfur dioxide
0-10.2 ppm 2 ppm
5 ppm
9 ppm
R-11
Refrigerant Q2
0-1020 ppm 500 ppm
750 ppm
900 ppm
R-12
R-22
R134A
COMB
Combustibles
0-102% LEL 25% LEL
50% LEL
90% LEL
Summary of Contents for 201T
Page 2: ......
Page 3: ...Gas Detection Device 201T User Manual ERP 511391 2 07 ...
Page 4: ......
Page 6: ......
Page 8: ......
Page 10: ......
Page 12: ......
Page 30: ......
Page 34: ......
Page 35: ...Dispositif de détection de gaz 201T Manuel de l utilisateur ERP 511391 2 07 ...
Page 36: ......
Page 38: ......
Page 40: ......
Page 42: ......
Page 44: ......
Page 62: ......
Page 66: ......