background image

WARNING: In no case should more than 2 air inlet holes be cut off the tube. There must be a minimum of 10 holes in

the tube exposed to the air stream.

B. INSTALLATION FOR DUCTS MORE THAN 8 (2.4 M) FEET WIDE

NOTE: To install inlet tubes in ducts more than 8 feet wide, work must be performed inside the air duct. Sampling of air

in ducts wider than 8 feet is accomplished by using the SSDST-10 inlet sampling tube.

Install the inlet tube as follows:

1. Drill a 3/4-in (19 mm) hole in the duct directly opposite the hole already drilled for the inlet tube.
2. Slide the inlet tube into the bushing located in the center of the duct housing. Position the tube so that the arrows

point into the air flow. Secure the tube flange to the housing bushing with the two #6 self-tapping screws.

3. From inside the duct, couple the other section of the inlet tube to the section already installed using the 1/2-inch con-

duit fitting supplied. Make sure that the holes in both air inlet tubes are lined up facing the direction of air flow.

4. Trim the end of the tube protruding through the duct so that 1 to 2 in (25 to 51 mm) of the tube extends outside the

duct. Plug this end with the tube end plug and tape closed any holes in the protruding section of the tube. Be sure to
seal the duct when the tube protrudes.

5. Any tube (over 3 ft - 91 cm long) that doesn’t protrude through the duct (on the side opposite the housing) must be

supported by other means.

NOTES: – An alternate method to using the SSDST-10 is to use two SSDST-5 inlet tubes. Remove the flange from 

one of the tubes and install as described above. After the installation, use electrician’s tape to close off
some of the sampling holes so that there is a total of 12 holes spaced as evenly as possible across the
width of the duct.

– Air currents inside the duct may cause excessive vibration. This vibration can slowly open the seal 

around the tube and permit air to escape. To prevent this from occurring, a 3-inch floor flange, available 
at most plumbing supply houses, may be used. This flange/connector mounting technique makes the 
initial installation easier because a 1-in to 1-1/4-in (25 to 32 mm) hole may be drilled where the flange/
connector will be used. It is easier to push the inlet tube through the larger hole.

MODIFICATION OF INLET SAMPLING TUBES

There may be situations where duct widths are not as specified for the installation. In such cases, it is permissible to
modify an inlet sampling tube that is longer than necessary to span the duct width.

Use a 0.193-inch diameter (#11) drill and add the appropriate number of holes so that the total number of holes exposed
to the air flow in the duct is 10 to 12. Space the additional holes as evenly as possible over the length of the tube.

STEP 5. COMPLETE FIELD WIRING

Wiring Installation Guidelines

All wiring must be installed in compliance with the National Electrical Code and the local codes having jurisdiction using
the proper wire size. The conductors used to connect smoke detectors to control panels and accessory devices should
be color-coded to reduce the likelihood of wiring errors. Improper connections can prevent a system from responding
properly in the event of a fire.

For signal wiring, (the wiring between interconnected detectors or from detectors to auxiliary devices), it is recommend-
ed that single-conductor wire be no smaller than 18 gauge (0.812 sq. mm). The duct detector terminals accommodate
wire sizes up to 14 gauge (2.087 sq mm). The last foot (30 mm) or so of conduit should be flexible steel conduit (avail-
able in electrical supply houses) which facilitates easier installation and puts less strain on the conduit holes in the hous-
ing. Solid conduit connections may be used, if desired.

To insure stable communications, the loop resistance of the communication line must not exceed 40 ohms.

STEP 7. PERFORM DETECTOR CHECK

AIR FLOW

1. To verify sufficient sampling of ducted air, use a manometer to measure the differential pressure created from air flow

across the sampling tubes. The pressure should measure no less than 0.01 inches of water and no greater than 1.20
inches of water.

2. Inspect the duct housing sensing chamber and clear any obstructions that may impede air flow across the detector

head. If a smoke test is required, smoke such as cigarette, cotton wick, or punk smoke may be blown directly at the
smoke sensor head. It is important to plug the exhaust and sampling tube hole to prevent ducted air from blowing
smoke away from the smoke sensor head. Record all test records in the Detector Test Log enclosed (Page 12).

CAUTION:

REMOVE THE PLUGS AFTER TESTING OR THE SENSOR WILL NOT SENSE SMOKE IN THE AIR
DUCT.

ALARM TESTS

Check the detector interconnections before replacing the duct housing cover. Check the 14506873-001 as follows:

A. SSDM0204 MAGNET TEST

1. Make sure power is applied to the detector.
2. Position the painted surface of the test magnet against the housing next to the rib molded onto the outside of the

housing (see Figure 7).

3. The LEDs on the detector should latch on as should any accessories (SSDPA400, SSDRA400Z, SSDRTS451), and

the alarm condition should be verified at the control panel. The control panel must be active for an alarm to be ini-
tiated.

A78-2452-00

A78-2453-00

Figure 7. Testing Detector Alarm

Figure 8. Detector Head Removal

B. SSDRTS451/SSDRTS451KEY REMOTE TEST STATION

The SSDRTS451/SSDRTS451KEY Remote Test Station facilitates test of the alarm capability of the duct detector, as indi-
cated in the SSDRTS451/SSDRTS451KEY manual. The 14506873-001 duct detector cannot be reset by the
SSDRTS451/SSDRTS451KEY. It must be reset at the system control panel.

To install the SSDRTS451/SSDRTS451KEY test coil, connect the device as shown in Figure 9. Position the coil in the
detector housing with the arrow facing up and pointing toward the detector as in Figure 9. Attach the coil leads to the
housing terminals as shown; polarity is not important. Firmly screw the test coil mounting bracket in place over the test
coil. The wire run connecting the remote test station to the duct detector must be less than 25 ohms.

TWIST
COUNTERCLOCKWISE
TO REMOVE

DUCT
HOUSING

TWIST
CLOCKWISE
TO INSTALL

DETECTOR
HEAD

TEST
LOCATOR

TEST
MAGNET

PAINTED SIDE

TOWARD HOUSING

DUCT
HOUSING

DETECTOR

HEAD

H500-03-00

8

I56-475-09R

H500-03-00

5

I56-475-09R

Summary of Contents for 14506873-001

Page 1: ...72 requirements The detector should be cleaned at least once a year TABLE OF CONTENTS GENERAL DESCRIPTION 1 Contents of the Duct Detector Housing Kit 2 INSTALLATION SEQUENCE 3 Verify Duct Air Velocity 3 Drill the Mounting Holes 3 Mount Duct Housing 3 Install the Inlet Tube 4 Ducts Less Than 8 ft 244 cm Wide 4 Ducts More Than 8 ft 244 cm Wide 5 Interim Modification of Inlet Tube 5 Field Wiring 5 Wi...

Page 2: ...respective code commands from the panel See panel instructions for details CONTENTS OF THE DUCT DETECTOR HOUSING KIT The 14506873 001 Air Duct Detector Housings consist of the following items See Figure 1 See Note 1 for Inlet Sampling Tube and Detector Supply information 1 Complete housing base and cover assembly 2 Two 10 sheet metal mounting screws 3 Two sampling tube filters 4 One test magnet 5 ...

Page 3: ...he duct See Figure 2 Location of detectors mounted in or on air ducts should be at least six duct widths downstream from any duct openings deflection plates sharp bends or branch connections Exception Where it is physically impossible to locate the detector accordingly the detector can be positioned closer than six duct widths but as far as possible from the opening bend or deflection plates STEP ...

Page 4: ...t tube If the inlet tube is shorter than the width of the air duct install the end cap into the inlet tube as shown in Figure 3 2 Slide the inlet tube into the bushing located in the center of the duct housing Position the tube so that the arrows point into the air flow 3 Secure the tube flange to the housing bushing with the two 6 self tapping screws 4 For tubes longer than the width of the air d...

Page 5: ...ibration This vibration can slowly open the seal around the tube and permit air to escape To prevent this from occurring a 3 inch floor flange available at most plumbing supply houses may be used This flange connector mounting technique makes the initial installation easier because a 1 in to 1 1 4 in 25 to 32 mm hole may be drilled where the flange connector will be used It is easier to push the i...

Page 6: ...CCESSORIES MAY BE USED SUCH THAT THE GIVEN CURRENT LOADS TOTAL AUX POWER TEST STANDBY STATE ALARM STATE 26mA MAX AT 24 VDC 87mA MAX 24 VDC TERMINALS 3 6 20mA MAX 12 VDC ALARM CONTACTS TERMINALS 2 6 NOTE THE SSDRTS451 SSDRTS451KEY RESET CANNOT BE USED ON THE 14506873 001 TEST RESET NOT USED 4 5 6 7 8 9 10 11 12 13 14 15 16 17 COMMUNICATION LINE FROM PANEL COMMUNICATION LINE TO REST OF SYSTEM NOTE F...

Page 7: ...ust accumulation System filters remove a large percentage of this contami nation but cannot remove all of it Dust inside the duct detector causes problems First very fine particles of dust can enter the detector sensing chamber and cause the unit to go into alarm Second the accumulation of dust and dirt necessitates a more frequent periodic cleaning schedule which can result in substantial cost an...

Page 8: ...utside of the housing see Figure 7 3 The LEDs on the detector should latch on as should any accessories SSDPA400 SSDRA400Z SSDRTS451 and the alarm condition should be verified at the control panel The control panel must be active for an alarm to be ini tiated A78 2452 00 A78 2453 00 Figure 7 Testing Detector Alarm Figure 8 Detector Head Removal B SSDRTS451 SSDRTS451KEY REMOTE TEST STATION The SSDR...

Page 9: ...nel should indicate an alarm condition PERIODIC MAINTENANCE REQUIREMENTS Air duct smoke detectors should be maintained at least once a year more often if the detector heads become obviously dirty The detectors must also be cleaned immediately after a fire Failure to properly maintain air duct smoke detectors may cause unnecessary false alarms Honeywell recommends that a permanent Detector Test Log...

Page 10: ... screens part no SSDRS14 d Brush or vacuum the inside of the cover Cover may then be blown out using clean compressed air e Vacuum sensing chamber before using clean compressed air to loosen and blow out any remaining debris f Press the screen back into the cover g Replace the detector cover on the sensing chamber Rotate it clockwise to lock it into place BOTH TYPES OF UNITS 5 Reinstall the detect...

Page 11: ...806A1037 or TC806A1052 are used the constraints above do not apply 2 The duct control circuitry auxiliary relay contacts and auxiliary alarm output may change states if the sensor is test ed and the LED is turned on for more than 4 seconds If the LED is latched on for less than 4 seconds the control circuitry of the 14506873 001 will NOT operate 3 The panel must not continuously poll the same unit...

Page 12: ...__________ ________ __________ ________ ______________ ____________________________ ________ __________ ________ ______________ ____________________________ ________ __________ ________ ______________ ____________________________ ________ __________ ________ ______________ ____________________________ ________ __________ ________ ______________ ____________________________ ________ __________ ____...

Reviews: