Mounting and Connection Instructions RF BUS-2 wireless receiver
29
6.3 Mounting
6.3.1 Strain relief of cable
Before closing the housing, secure the cable with a cable tie at the provided pull relief (see in Chapter 3.)
6.3.2 Seal
housing
Seal the housing after mounting, programming and testing correctly the system by pressing the plastic seal into the
screw opening on the front of the housing.
Ensure that the housing is closed and screwed correctly. Clean the seal (free from grease) and cover with the label
(VdS imprint). After attaching the plastic seal, the housing cannot be opened without destroying the seal.
7.
Technical data
Operating voltage U_b
12 V DC, residual ripple 1 Vss
Operating voltage range
10 V DC to 15 V DC
Current consumption
typ. 15 mA
Frequency range 1
433,05…434,79 MHz
Transmission power 1
<10 mW
Frequency range 2
863…870 MHz
Transmission power 2
<25 mW
Transmitting range
typ. 300 m by free visibility
Installation position
arbitrary
Protection class as per DIN 40 050
IP 30
Environmental class as per VdS
II
Operating temperature range
-10 °C to +55 °C
Storage temperatur range
-25 °C to +70 °C
Dimensions W x H x D
118 x 118 x 31 mm without antennas
Antennas (L)
75 mm
135 mm
Colour
traffic white (similar to RAL 9016)
Hereby, the Novar GmbH declares that the radio equipment RF BUS-2 wireless receiver, Item no.
015600.01 is in compliance with Directive 2014/53/EU.
The full text of the EU declaration can be downloaded from our homepage https://www.security.honeywell.de/ in
the service/download area.
Summary of Contents for 015600.01
Page 2: ... ...
Page 8: ...Montage Anschluss Anleitung RF BUS 2 Koppler 8 3 Fotoübersicht RF BUS 2 Koppler ...
Page 15: ...Montage Anschluss Anleitung RF BUS 2 Koppler 15 9 Anschlussplan ...
Page 18: ... ...
Page 31: ...Mounting and Connection Instructions RF BUS 2 wireless receiver 31 9 Connection diagram ...