Condition on delivery

Functional Description

 (continued)

Switching off the power supply

If  the  accumulator  voltage  drops 

below  10.5  V

  during 

accumulator operation, the power supply to the control panel 
and the external users is switched off (switch-off relay).

This avoids unforeseeable reactions from the control panel on 
the  one  hand,  and  protects  the  accumulator  from  deep 
discharging on the other.

A  "!U_bat<"  signal  is  given  before  switch  off  (See  below  for 
description).

Collective faults:

The messages are transmitted via the outputs
 

- "Fault" (ST100/3), HIGH active and

 

- "Fault" (ST100/2), LOW active.

The following fault 

causes 

are possible:

 

Mains / ext. user / charger controller defective / 

 

accum. defective or missing / SE input

The type of fault can be determined by the LEDs on the power 
supply PCB.

With the DIP switch S100 certain fault causes can be switched 
to  the  collective  fault  output  (see  Chapter  7  "Connection  Dia-
gram").

Fault U_ext. 

(ST100/7), output, LOW active.

This output is active when there is a fault in the user outputs.

Fault SE

 (ST100/1), input, LOW active.

For connecting "Fault" outputs of additional emergency power 
supplies (cascading).

Mains 

(ST100/6), output, HIGH active. 

This output is active during power on.

!U_bat<:  

(ST100/8), output, LOW active.

Switch-off warning

This  output  warns  of  the  impending  switch-off  of  the  power 
supply. 
The output is set when the accum. voltage drops 

below 10.8 V.

 

A  corresponding  message  can  be  transmitted  e.g.  via  an 
AWUG.

U_bat <10.5 V

 (ST104/2), output, HIGH active.

This  output  is  transmitted  when  the  power  supply  (U_bat 
<10.5 V) is switched off.

TEST 

(ST104/1), input, LOW active.

This input allows a function test of the output U_bat <10.5 V 
(ST104/2) by applying a 0 V potential. LD3 must light up.

 

Attention

 

It only is permitted to switch the input "Test" to the 
0 V potential.

 

Do not apply a HIGH potential.

RESET key

For  the  initial  start-up  procedure,  the  mains  voltage  must 
be  available  so  that  the  switch-off  relay  is  energized  and 
the voltage is connected to the power supply output.

The reset key is necessary, when the power supply unit requires 
operating without mains (e.g. for test purposes).  
The reset key is used for energizing the switch-off relay.

  5.   Set charge terminating voltage

1.  The  power  supply  must  have  reached  operating  temper-

ature.

 

For this purpose it must be operated for at least two hours 
at rated load and with closed housing.

2.  Connect a 

charged accumulator

.

 

A  not  completely  charged  accumulator  leads  to  a  miss-
alignment.

3.  Adjust the voltage at the accumulator terminals using the 

potentiometer  PO100  according  to  the  ambient 
temperature at the accumulator as per the following table.

 

Please take note of the type of accumulator.

  
 

 

ATTENTION:

 

 

 

Only alter the charge terminating voltage:

1.  After measuring the exact temperature and

2.  When the voltage deviates >200 mV from the set value as 

per following table.

  6.   External NTC thermistor resistor

 

Item no.  010693

When using an external NTC thermistor resistor, the wire jumper 
DB102 must be debridged. 

The  external  NTC  should  be  fixed  to  the  accumulator  in  a 
suitable manner (e.g. with double-sided adhesive tape) and 
connected by soldering to the bore holes.

Note:  

Basically,  we  recommend  using  an  external  NTC 

thermistor resistor. 

 

If  the  accumulator  is  not  in  the  close  vicinity  of  the 
NTC100,  an  external  NTC  thermistor  resistor  must 
be used.

  U  (V)

L

  14.50
  14.30
  14.10
  13.95
  13.80
  13.65
  13.50
  13.40
  13.30
  13.25
  13.20

  U  (V)

L

  14.10
  13.95
  13.75
  13.60
  13.50
  13.45
  13.40
  13.35
  13.30
  13.25
  13.20

For  installation  in  compliance  with  VdS,  an 
external  NTC  thermistor  resistor  must  always  be 
used!

6                                                                    Mounting and Connection Instructions Mains/charger unit 12 V DC / 80 Ah

Summary of Contents for 012168

Page 1: ... eindeutig identifizierbar ist muss eine zweite Absicherung im Versorgungsstromkreis so angeordnet werden dass eine 2 polige Trennung vom Versorgungsstromkreis möglich ist Die Anschlussklemmen müssen nach der Installation durch die mitgelieferten Abdeckungen gegen versehentliches Berühren geschützt werden 1 Allgemeines Vollelektronisches Netz Ladeteil 12 V DC und 24 V DC Ausgänge Spannungsstabilis...

Page 2: ...t Schalter Taster oder Relais gegen 0 V geschaltet werden Kein HIGH Potenzial anlegen RESET Taster Bei der Erstinbetriebnahme muss zunächst einmal die Netz spannung vorhanden sein damit das Abschaltrelais anzieht und somit die Spannung am Netzteilausgang anliegt Der Reset Taster wird benötigt wenn das Netzteil ohne Netz z B zu Testzwecken betrieben werden soll Der Reset Taster sorgt dafür dass das...

Page 3: ...e bitte Kapitel 2 und 3 in dieser Anleitung Wichtiger Hinweis Kommen mehrere Netzteile zur Erhöhung der Notstromkapazität zurAnwendung müssen die 0 V Potenziale aller Netzteile über KL103 KL104 miteinander verbunden werden PO 100 8 Bohrungen zum Einlöten des Anschlusskabels des externen NTC s Interne Meßspannung Interne Meßspannung Montage Anschluss Anleitung Netz Ladeteil 12 V DC 80 Ah 3 Ladeschl...

Page 4: ...des 24 V Ausgangs Permanente Akku Überwachung Temperaturgeführte Akku Ladespannung Betriebstemperaturbereich 5 C bis 45 C Lagerungstemperaturbereich 25 C bis 70 C Umweltklasse gemäß VdS II Abmessungen Platine L x B 250 x 97 5 mm Gehäuse B x H x T 102 x 252 x 80 mm 1 Bei Verwendung dieses Ausgangs ist die Stromentnahme aus dem Akku zu berücksichtigen 2 Der angegebene Wert entspricht der Gesamtstrom...

Page 5: ...l When installing in accordance with VdS make sure that there is a minimum load of 500 mA as supply current B 2 outputs for external user The outputs are protected with fuses 1 6 AT per output When installing in accordance with VdS make sure that there is a minimum load of 100 mA per output as external load current Second control circuit Serves as a charger for the accumulators The charging curren...

Page 6: ...5 V ST104 2 by applying a 0 V potential LD3 must light up Attention It only is permitted to switch the input Test to the 0 V potential Do not apply a HIGH potential RESET key For the initial start up procedure the mains voltage must be available so that the switch off relay is energized and the voltage is connected to the power supply output The reset key is necessary when the power supply unit re...

Page 7: ... AT External user 230 V AC LED Indication LD1 Accumulator fault LD2 U_BAT 10 8 V switch off warning LD3 U_BAT 10 5 V switch off of power supply LD4 U_BAT 9 45 V accumulator defective LD5 Charger controller defective LD6 Mains voltage missing LD7 Fault external user LD8 Fault input SE actuated DIP Switch S100 Fault messages can be switched through to collective fault with S100 The respective switch...

Page 8: ...ration Permanent accumulator monitoring Temperature guided accumulator charging voltage Operating temperature range 5 C to 45 C Storage temperature range 25 C to 70 C Environmental class as per VdS ll Dimensions PCB L x W 250 x 97 5 mm Housing W x H x D 102 x 252 x 80 mm 1 When using this output the current consumed from the accumulator should be taken into consideration 2 The declared value corre...

Reviews: