Honeywell 012168 Mounting And Connection Instructionsmounting And Connection Instructions Download Page 5

 

 1.  General

Fully electronic mains/charger unit. 

-  12 V DC and 24 V DC outputs

-  Voltage-stabilized with current limitation

-  Redundancy standby operation with accum. monitoring

-  Deep-discharging protection

-  Charging circuit monitoring

-  Recognition of defective batteries

-  Accumulator capacity up to max. 80 Ah

Recommended housing for installing: Type ZG 3.1 or larger

When selecting the size of housing, pay attention to the 
space required for the accumulators.

  3.  Mounting

 

 

Attention

 

Safety instructions

When  performing  installation  work  of  any  kind,  the  unit  must 
be  de-energized.  Before  opening  the  housing,  wait  until  the 
electrolytic capacitors are discharged (approx. 3 minutes).

Never operate the unit without the housing.

When  installing  the  power  unit  in  a  control  panel  housing  or 
equivalent, ensure that the supplied 

insulating foil has been 

inserted between the housing base and the underside of 
the PCB

 and that the supplied distance bold is screwed tight 

to the housing base.

The non-fused earth conductor from the electric power circuit  
must be connected in the immediate vicinity of the connection 
terminals of the supply voltage.

The power supply line must be fixed when connecting so that 
the 

clearance (4 mm)

 and 

creep paths (5 mm)

 between the 

electronic  modules  and/or  their  periphery  and  the  power 
supply line are not shorter than stipulated.

If  the  neutral  line  cannot  be  clearly  identified,  a  second  pro-
tection  must  be  available  in  the  electric  power  circuit  so  that 
2-pole separation from the electric circuit  is possible.

The connection terminals must be protected against touching 
inadvertantly by using the supplied cover.

  4.  Functional description

Two independent control circuits are installed on the mother-
board.

-  First control circuit: 

  Supplies the control panel and the external users.

  A) - Output 

control panel

 supply (ST100)

   

- Additional: outputs ST101 and BU100 

   

The outputs are protected by the internal current control.

When  installing  in  accordance  with  VdS,  make  sure 
that  there  is  a  minimum  load  of  500  mA  as  supply 
current.

  B) - 2 outputs for 

external user 

   

The outputs are protected with fuses (1.6 AT per output).

When  installing  in  accordance  with  VdS,  make  sure 
that there is a minimum load of 100 mA per output as 
external load current.

-  Second control circuit: 

  Serves  as  a  charger  for  the  accumulators.  The  charging 

current is limited to 3.5 A.

  The  accumulator  charging  voltage  is  monitored  and  ad-

justed according to the temperature with the aid of an NTC 
resistor.

  The charge t

erminating voltage

 has been correctly set be-

fore leaving the factory (for Sonnenschein A500 series).

  If it requires resetting, proceed according to Chapter 5 "Set 

charge terminating voltage".

The supply voltage for the control panel and external users do-
es not require adjusting as it is monitored and adjusted by the
accumulated charging voltage so that in case of a mains failure, 
large voltage jumps are avoided.

G199022 EMT

Mounting and Connection Instructions

Mains/charger unit 12 V DC / 80 Ah
Item no. 012168

Subject to change

without notice

P00210-10-002-08

2018-07-31

  

2.  VdS guidelines for  power supply

The power supply must be connected to the mains with a 
separate fuse.

If the electrical installation has an earth-leakage circuit breaker 
(Fl switch), the energy supply must have its own earth-leakage 
circuit breaker. The fuse and Fl switch should, if possible, be 
within the security zone.

If the energy supply is not part of the control panel, it must be 
installed in the immediate vicinity (without a space between) so 
that  an  attack  on  the  connection  line  is  impossible  without 
causing mechanical damage to the housing. 

The  control  panel  and  power  supply  should,  if  possible,  be 
screwed together.

Users not belonging to the system should not be connected to 
the mains voltage.

The  accumulators  used  in  the  power  supply  must  be 
approved. For parallel switching, only accumulators of the 
same age and from the same production series are allowed 
to be used.

The accumulators must be fixed on the housing base using 
Dual lock fasteners

 (Item no. 055280).

Seite 1 - 4        Page 5 - 8

Summary of Contents for 012168

Page 1: ... eindeutig identifizierbar ist muss eine zweite Absicherung im Versorgungsstromkreis so angeordnet werden dass eine 2 polige Trennung vom Versorgungsstromkreis möglich ist Die Anschlussklemmen müssen nach der Installation durch die mitgelieferten Abdeckungen gegen versehentliches Berühren geschützt werden 1 Allgemeines Vollelektronisches Netz Ladeteil 12 V DC und 24 V DC Ausgänge Spannungsstabilis...

Page 2: ...t Schalter Taster oder Relais gegen 0 V geschaltet werden Kein HIGH Potenzial anlegen RESET Taster Bei der Erstinbetriebnahme muss zunächst einmal die Netz spannung vorhanden sein damit das Abschaltrelais anzieht und somit die Spannung am Netzteilausgang anliegt Der Reset Taster wird benötigt wenn das Netzteil ohne Netz z B zu Testzwecken betrieben werden soll Der Reset Taster sorgt dafür dass das...

Page 3: ...e bitte Kapitel 2 und 3 in dieser Anleitung Wichtiger Hinweis Kommen mehrere Netzteile zur Erhöhung der Notstromkapazität zurAnwendung müssen die 0 V Potenziale aller Netzteile über KL103 KL104 miteinander verbunden werden PO 100 8 Bohrungen zum Einlöten des Anschlusskabels des externen NTC s Interne Meßspannung Interne Meßspannung Montage Anschluss Anleitung Netz Ladeteil 12 V DC 80 Ah 3 Ladeschl...

Page 4: ...des 24 V Ausgangs Permanente Akku Überwachung Temperaturgeführte Akku Ladespannung Betriebstemperaturbereich 5 C bis 45 C Lagerungstemperaturbereich 25 C bis 70 C Umweltklasse gemäß VdS II Abmessungen Platine L x B 250 x 97 5 mm Gehäuse B x H x T 102 x 252 x 80 mm 1 Bei Verwendung dieses Ausgangs ist die Stromentnahme aus dem Akku zu berücksichtigen 2 Der angegebene Wert entspricht der Gesamtstrom...

Page 5: ...l When installing in accordance with VdS make sure that there is a minimum load of 500 mA as supply current B 2 outputs for external user The outputs are protected with fuses 1 6 AT per output When installing in accordance with VdS make sure that there is a minimum load of 100 mA per output as external load current Second control circuit Serves as a charger for the accumulators The charging curren...

Page 6: ...5 V ST104 2 by applying a 0 V potential LD3 must light up Attention It only is permitted to switch the input Test to the 0 V potential Do not apply a HIGH potential RESET key For the initial start up procedure the mains voltage must be available so that the switch off relay is energized and the voltage is connected to the power supply output The reset key is necessary when the power supply unit re...

Page 7: ... AT External user 230 V AC LED Indication LD1 Accumulator fault LD2 U_BAT 10 8 V switch off warning LD3 U_BAT 10 5 V switch off of power supply LD4 U_BAT 9 45 V accumulator defective LD5 Charger controller defective LD6 Mains voltage missing LD7 Fault external user LD8 Fault input SE actuated DIP Switch S100 Fault messages can be switched through to collective fault with S100 The respective switch...

Page 8: ...ration Permanent accumulator monitoring Temperature guided accumulator charging voltage Operating temperature range 5 C to 45 C Storage temperature range 25 C to 70 C Environmental class as per VdS ll Dimensions PCB L x W 250 x 97 5 mm Housing W x H x D 102 x 252 x 80 mm 1 When using this output the current consumed from the accumulator should be taken into consideration 2 The declared value corre...

Reviews: