7. Connection diagram
Allocation of fuses Si1 bis Si7:
Si1: 1 AT
Si2: 1 AT
Si3: 4 AT
Secondary fuse mains transformer
Si4: 2.5 AF
Si5: 1 AF
Ext. user 12 V DC (1 und 2)
Si6: 1 AF
Si7: 3.15 AF
Mains fuse
Ext. user 230 V AC
Output voltage 12 V DC
Ext. user 12 V DC (3 und 4)
Accumulator charging
The folIowing table shows which type of
fault message (
or
) is used:
Intrusion detection control panel:
Fire detection control panel:
12 V DC / 20 Ah
A
Item no. 010691
12 V DC / 32 Ah
A
Item no. 010692
Type A
Type B
Unit
Type
100-M10
B
561-B8
B
561-M5
B
561-M8
B
561-M10
B
561-M10/5S
B
561-M20
B
561-M99
B
561-M100
B
561-MB8
B
561-MB16
B
561-MB48
B
561-MB100
B
561-MB256/plus
B
608-F
A
616-F
A
664-F
A
708-F
A
Power supply in housing:
12 V DC / 17 Ah
A
Item no. 012141
P
N
P'
N'
Rel. 1
SE
Fault
Fault
+12 V DC
0 V
Mains
Adjustment of
accumulator
charging voltage
Si3
4 AT
Si5
1 AF
Si4
2,5 AF
Si6
1 AF
Si7
3,15 AF
Si1
1 AT
Si2
1 AT
Fault messages:
With R33:
Accum. and mains fault = Type A
Without R33: Only accum. fault
= Type B
TR1
PO 1
PO 2
PO 3
1
2
3
4
Ext. user
+12 V DC
+ - + - + - + -
Mains
230 V AC
Ext. user
230 V AC
Accum. 1
Accum. 2
R33
4 solder support points
for free disposal
Mounting and Connection Instruktions Mains/charger unit 12 V DC / 32 Ah
7