Y8150 FRESH AIR VENTILATION SYSTEM, W8150 FRESH AIR VENTILATION CONTROL

68-0282—11

8

CHECKOUT

In this section, make sure the ventilation system is 
operating correctly. 

1.

On thermostat, set Fan switch to Auto and System 
switch to Off.

2.

Set any remote switches throughout the house in the 
Off position.

3.

On the W8150, set the control switch to Off (remote 
only). 

4.

Press Test button for two seconds to enter test mode:
• A light on the control begins flashing.
• The HVAC system fan comes on.
• The damper moves to the Open position.

5.

Press the Test button again to exit test mode:
• No lights on the control are on.
• The HVAC system fan turns off.
• The damper returns to the closed position.

6.

Return the thermostat, ventilation control, and 
remote switches to the original settings.

7.

Refer to Troubleshooting section, if needed.

TIP:

• W8150 Ventilation Control automatically exits test 

mode after three minutes.

TROUBLESHOOTING

Problem

Possible cause 

What to do

Flashing red light 
during test mode 

(The current settings 
do not meet the 
selected ventilation 
requirement)

Not enough airflow

Measure airflow and check dial setting.

See Problem: Not enough airflow.

Ventilation on-time limit 
setting

If the device is set to 60%: Set the ventilation control to 100% 
maximum on time. This allows the HVAC fan to run up to 100% of the 
time. It may be preferable to increase airflow.

If the device is set to 100%: There is not enough airflow through the 
fresh air duct. 

Ventilation continues to occur according to the settings but chosen 
standard may not be met.

Flashing red light 
during normal 
operation

Low voltage

Check the voltage from the transformer for at least 20 Vac. If voltage 
is OK, replace W8150 Control. If voltage is not OK, disconnect damper 
and remote switch connections and check again. If voltage does not 
return to at least 20 Vac, replace transformer.

No light on 
ventilation control 
when switch set to:

On 

Override Off/

Remote Only and 
a remote switch is 
on.

No power to control

Verify 24 volt input to R and C terminals on ventilation control.

Check wiring connections per appropriate system diagram and 
replace transformer, if necessary.

Device malfunction

Cycle power off to control for ten seconds and recheck. If control does 
not recover, replace ventilation control.

HVAC fan does not 
come on after 
pressing Test button. 

Wiring

Check wiring connections per appropriate system diagram.

HVAC system does not 
have power

Restore power to the HVAC system.

Summary of Contents for W8150

Page 1: ...HRAE 62 2 2010 standard Ventilation and Acceptable Indoor Air Quality in Low Rise Residential Buildings Microcontroller optimizes the air delivery schedule to make efficient use of normal HVAC run times Easy to use input dials allow customized ventilation for each installation Test mode that includes immediate feedback to installer to confirm that air delivery requirements of selected ventilation ...

Page 2: ... Vac 12 VA 60 Hz Operation Power open spring closed Diameter 6 in Transformer AT120 Input 120 Vac Output 27 Vac open circuit 24 Vac full load at 20 VA Mounting Foot mounted Temperature 20 F to 160 F 29 C to 71 C Humidity 5 to 90 RH noncondensing Input Setting Ranges Bedrooms 2 5 Area 1000 4600 sq ft Vent Airflow 40 160 cfm Composite Setting Resolution 12 of ASHRAE 62 2 2010 recommended ventilation...

Page 3: ...ntilation continuously Off Remote Only W8150 supplies ventilation only when there is a remote call 8 Light Green Indicates device is powered and operating normally Used in Test Mode to signal if dial settings meet chosen standard 9 Light Red Indicates the device is not operating normally Used in Test Mode to signal if dial settings do not meet chosen standard 10 DIP1 Ventilation limit Choose betwe...

Page 4: ... or HRV ERV with a call for ventilation 18 DAMPER Damper two terminals 24 Vac powered contacts control fresh air damper 19 XFMR C 24 Vac ventilation control common Supplies power to W8150 and damper from transformer provided 20 XFMR R 24 Vac ventilation control power Supplies power to W8150 and damper from transformer provided No Name Description Function Device Number Component Location 1 Fresh a...

Page 5: ... To prevent complete opening move the red tab to the desired range stop location Wiring the control CAUTION Electrical Hazard Can cause personal injury or equipment damage Disconnect power to all systems before beginning installation 1 Wire the control See wiring diagrams in Fig 1 10 as listed below All wiring must comply with local codes ordinances and regulations 2 Reapply power to system and co...

Page 6: ... the control to meet the ventilation requirements for the home Ventilation Standard Building codes are different everywhere The W8150 Ventilation Control can be configured to operate based on ASHRAE 62 2 ASHRAE 62 1999 TIP Clear understanding of local codes and practices is required to make sure the ventilation system is installed and configured correctly Generally ASHRAE 62 2 control method is re...

Page 7: ...l to the nearest value For airflow set airflow cfm dial to the nearest value Vaulted ceilings do not need to be considered when setting this control For homes with multiple systems Resideo recommends a ventilation control and fresh air intake for each system Measure ventilation airflow for each system independently Refer to Multi system Setup Example for further details Customizing the ventilation...

Page 8: ...oblem Not enough airflow Ventilationon timelimit setting If the device is set to 60 Set the ventilation control to 100 maximum on time This allows the HVAC fan to run up to 100 of the time It may be preferable to increase airflow If the device is set to 100 There is not enough airflow through the fresh air duct Ventilation continues to occur according to the settings but chosen standard may not be...

Page 9: ... to actuator Damper actuator motor failure or mechanical failure Manually open damper and verify free movement damper should return to closed position when no power is applied If damper moves freely but does not operate when 24 volts is applied replace damper actuator If damper does not move freely replace fresh air damper Cooling compressor comes on when there is no cooling call from the thermost...

Page 10: ...p without emergency heat Wake Room System Fan Heat Auto AM DST Tue R C W Y G R RC W Y G M19994C GF RC CC CH W GT W8150A HVAC Wake Room System Fan Heat Auto AM DST Tue W R HVAC COOLING HEATING R C C Y G R RC W Y G M19995C GF RC CC CH W GT NOTE REMOVE FACTORY INSTALLED JUMPER BETWEEN CC AND CH ON W8150 W8150A Wake Room System Fan Heat Auto AM DST Tue W1 C R W2 Y1 Y2 G W1 C RC R W2 Y1 Y2 G M19996B GF...

Page 11: ...TTON ON THE PC8900 THEN SERVES AS A REMOTE AND THE W8150 CONTROLS BACKGROUND VENTILATION Ventilation Control Ventilation Control Service Auto Continuous Off Remote Only M35715A EARD6TZ FAN TIMER REMOTE AUX DAMPER C R XFMR AT120 W8150A Ventilation Control Ventilation Control Service Auto Continuous Off Remote Only M22001B ERV HRV EARD DAMPER NOT USED WITH HRV ERV REMOTE AUX DAMPER C R XFMR RED BLAC...

Page 12: ...ms fresh air intake measured at 127 cfm System 2 serves 1800 sq ft four bedrooms fresh air intake measured at 98 cfm Set W8150 for System 1 3100 sq ft four bedrooms 130 cfm Set W8150 for System 2 1900 sq ft two bedrooms 100 cfm CONVERSION TABLE Wake Room System Fan Heat Auto AM DST Tue W1 C R W2 Y1 Y2 G W1 C RC R W2 Y1 Y2 G M22021C GF RC CC CH W GT HVAC W8150A HUMIDIFIER FAN R8222 BLACK BLUE BLUE ...