Moreover, you can also connect the sensor communications and power 

supply input:

9 - power supply output for the flow sensor (from the main power supply 

source), 

55 - signal input (only if it is configured as a input of digital communication 

with the transducer) to communicate with the additional flow sensor 

(additional input 2). 

Please refer to the diagram below to connect the additional flow sensor with 

the open collector output for the sensor with the required power supplied 

from the calculator (1), open collector output (2) and the normally closed 

contact output (3).

In the case of ultrasonic transducers with a 4-wire connection (e.g. 

Sharky 473) the fourth wire (yellow) can be connected only if input I2 

is configured as a digital communication with the transducer. 

Otherwise, do not connect this cable. Incorrect connection may result 

in premature battery wear.

4.4 Connecting external power supply

The calculator can be powered from 230VAC or 24VAC power adapter, as 

well as using AA batteries, two AA or C batteries mounted on a separate 

plate or D battery mounted directly in the base.

Opening the cover provides direct access to the main battery or power 

adapter (Fig. 19).

If you are replacing the D battery on your own, pay attention to how it is 

mounted in the casing, the positive pole should be facing the upper edge of 

the casing.

Each battery or power adapter has cables to be connected to the calculator.

Main power supply must be connected on the terminal block (Fig. 12) to the 

connector marked with numbers: 60 – positive pole, 61 – negative pole.

In case of calculator equipped with power supply: the power adapter should 

be connected to the ~230 V power supply and to the terminals marked with 

numbers 27 and 28 (Fig. 20); for the 24 V power adapter the ~24 V power 

should be supplied to terminals marked with numbers 97, 98 (Fig. 21).

The power adapter has two sets of terminals marked with numbers 95 and 

96, allowing for the supply of power to interchangeable communication 

modules (terminals on modules marked with numbers 97 and 98). 

The electrical connection of power adapter should be performed by a 

properly licensed person.

4.5 Connecting additional input signals

Each version of the terminal block has 4 additional inputs.

Each of the inputs marked I1 (terminal no. 56 and 50), I2 (terminal no. 55 and 

50), I3 (terminal no. 54 and 50), I4 (terminal no. 53 and 50) can operate as 

an impulse input, the I3 input can additionally serve as an alarm input, and 

the I4 input can be used for digital communication with the flow transducer.

Each input has two terminals, marked as follows:

signal input (terminal no. 56, 55, 54, 53)

reference input for additional input, each input has a separate terminal 

for reference signal connection (terminal no. 50)

Fig. 22 shows the signal connection method for a sample additional input, for 

a device with output type: open collector (1), normally open contact (2).

4.6 Installation of additional modules

The calculator allows you to install up to two independent additional modules:

M-Bus

RS232

RS485

impulse outputs (2x OB, OC or OD class output)

impulse inputs and outputs (2x OB, OC or OD class output and 2x IB or 

IC class input)

analogue outputs (2x 4-20 mA or 0-10 V output)

LonWorks

RF module for IMR telemetry systems (AIUT)

Wireless M-Bus RF module

Fig. 23 shows the place and method of additional module installation. 

Modules can be installed in any connector except for RF modules, which can 

only be fitted in the connector marked with number 1 (Fig. 12).

4.7 Installation of the M-Bus module (module code: 001)

M-Bus module is powered from the M-Bus network and galvanically isolated 

from the calculator using optical isolation. The module supports primary, 

secondary and extended secondary addressing. The M-Bus signals are 

connected through the inputs marked with numbers 24,25 (Fig. 24).

Fig. 12 

Fig. 13 

Fig. 14 

Fig. 15 

Fig. 16 

Fig. 17 

Fig. 18 

BROWN

WHITE

BLUE

YELLOW

BROWN

WHITE

RED

YELLOW

BLUE

Summary of Contents for resideo EW500 Series

Page 1: ...use Heat Metering Guarde las instrucciones para un posterior uso Medici n de calor Instrukcj nale y zachowa na potrzeby p niejszego u ycia Pomiar ciep a EW5001CD0100 Flow sensor on supply pipe Pt500...

Page 2: ...ay sequence 10 E 1 Instalaci n de el calculador 21 2 Pantalla LCD 21 3 Configuraci n de el calculador desde el men 22 4 Conexi n el ctrica 23 5 Dimensiones 27 6 Descripci n del c digo de error 27 7 Se...

Page 3: ...the C cover to the mounting base using B screws 13 Place the seals Fig 6 wire Fig 7 sticker 1 2 Installation of the calculator on the ultrasonic transducer 1 2 1EW400 Ultrasonic Flow Meter 1 Remove t...

Page 4: ...ith the symbol 13 indicates the values or signals the failure of the backup battery 16 The main display field 8 digit field for displaying values and configuration data of the calculator Fig 9 17 Symb...

Page 5: ...er of the calculator Fig 5 The removal method is described in the section Installation of the calculator 4 1 Connecting the temperature sensors The calculator can work with two types of temperature se...

Page 6: ...ower adapter has two sets of terminals marked with numbers 95 and 96 allowing for the supply of power to interchangeable communication modules terminals on modules marked with numbers 97 and 98 The el...

Page 7: ...is connected through terminals no 97 98 the polarity of the connected power supply is arbitrary The impulse inputs are connected through terminals no 65 66 and 67 68 whereas the signal from the impuls...

Page 8: ...32 negative pole The module supplied by the manufacturer with its own power supply is in the sleep mode The APAT 13x2 module can be activated using the SW1 diagnostic button push and hold the button...

Page 9: ...difference error 10 s 32 Maximum flow exceeded error 10 s 64 Low level of main battery or mains power supply failure 10 s 24 h 128 Low level of backup battery 24 h 256 Additional input alarm 1 s 512...

Page 10: ...GB 10 MU1H 0511GE23 R0720 7 DISPLAY SEQUENCE...

Page 11: ...GB MU1H 0511GE23 R0720 11...

Page 12: ...GB 12 MU1H 0511GE23 R0720...

Page 13: ...GB MU1H 0511GE23 R0720 13...

Page 14: ...GB 14 MU1H 0511GE23 R0720...

Page 15: ...GB MU1H 0511GE23 R0720 15...

Page 16: ...GB 16 MU1H 0511GE23 R0720...

Page 17: ...GB MU1H 0511GE23 R0720 17...

Page 18: ...GB 18 MU1H 0511GE23 R0720...

Page 19: ...GB MU1H 0511GE23 R0720 19...

Page 20: ...GB 20 MU1H 0511GE23 R0720...

Page 21: ...ontaje del caudal metro ultras nico Fig 8 3 Desplazar el calculador en direcci n a los orificios para cables hasta que haga clic en el sensor de caudal 4 Seguir las instrucciones en lo punto 8 13 en c...

Page 22: ...descripciones adicionales de los valores mostrados en el campo principal el tipo de error y la hora actual o archivada en las pantallas seleccionadas 19 S mbolo de los datos diarios que indica la visu...

Page 23: ...introducidos no se guardar n en el calculador 4 CONEXI N EL CTRICA Para realizar las conexiones el ctricas retire la tapa C de el calculador Fig 5 El m todo de eliminaci n se describe en la secci n In...

Page 24: ...la fuente de alimentaci n de 230 V y a los terminales marcados con los n meros 27 y 28 Fig 20 Se debe suministrar alimentaci n de 24 V a los terminales marcados con los n meros 97 98 Fig 21 El adaptad...

Page 25: ...a 1 Las salidas de impulsos pueden operar en una de las tres clases OB OC u OD seg n EN 1434 2 La clase de operaci n de salida se configura durante la producci n y no puede modificarse posteriormente...

Page 26: ...minal positivo est marcado como Vcc mientras que el polo negativo como GDN Los cables de comunicaci n se conectan mediante un par de terminales situados en la parte superior izquierda del m dulo desig...

Page 27: ...able dentro del dispositivo 5 DIMENSIONES 6 DESCRIPCI N DEL C DIGO DE ERROR 7 SECUENCIA DEL DISPLAY Ver 7 Display sequence Fig 34 159 mm 100 mm C digo Descripci n Tiempo de respuesta 2 Sin caudal T di...

Page 28: ...unku otwor w kablowych a do momentu zatrza ni cia si przelicznika na przetworniku 4 Post puje zgodnie z punktami 8 13 opisanymi w przypadku monta u przelicznika na cianie 1 2 2Przetworniki Ultraflow 1...

Page 29: ...u optycznego symbol wy wietlany w czasie gdy aktywny jest port optyczny i mo liwa jest komunikacja 21 Symboldanychmiesi cznych okre lawy wietlaniedanychzarchiwum miesi cznego 22 Symbol danych rocznych...

Page 30: ...istnieje osobne wykonanie p ytki g wnej przelicznika Pomiar temperatury mo e by wykonywany za pomoc czujnik w Pt500 b d Pt1000 zar wno 2 jak i 4 przewodowych W zale no ci od ilo ci przewod w przy cze...

Page 31: ...do zacisk w oznaczonych cyframi 97 98 rys 21 Zasilacz posiada dwie pary zacisk w oznaczonych cyframi 95 i 96 umo liwiaj cych zasilanie wymiennych modu w komunikacyjnych zaciski na modu ach oznaczone...

Page 32: ...yj cia 2 wej cia impulsowe rys 28 kod modu u 080 wyj cia dla modu u wej wyj maj takie same wykonania jak dla modu u 016 Wej cia mog pracowa w klasie IB lub IC wed ug PN EN 1434 2 W ka dym z przypadk w...

Page 33: ...rzy rodzaje modu w IMR rys 34 z interfejsem radiowym wyk APAT 1312 z interfejsem radiowym i kablowym wyk APAT 1322 z interfejsem kablowym wyk APAT 1332 Modu y mog by zasilane w zale no ci od wykonania...

Page 34: ...ka powrotu 10 s 16 B d odwrotnej r nicy temperatur 10 s 32 B d przekroczenia przep ywu maksymalnego 10 s 64 Niski poziom g wnej baterii lub brak zasilania sieciowego 10 s 24 h 128 Niski poziom baterii...

Page 35: ...PL MU1H 0511GE23 R0720 35...

Page 36: ...presentative Ademco 1 GmbH MU1H 0511GE23 R0720 Subject to change 2020 Pittway S rl All rights reserved This document contains proprietary information of Pittway S rl and its affiliated companies and i...

Reviews: