background image

 

 

 

 

Testing 

The detector should be tested immediately after installation and at least once a year. 

Recommended: 

 Notify the Central Station that the smoke detector is undergoing tests, so they do not dispatch authorities. 

 

After enrolling, verify adequate signal strength by conducting a sensor test (see the Control Panel’s instructions) with the device in its 

intended mounting location. Adjust the device location and orientation as necessary. 

 

Tests and testing methods: 

There is no specific Test Mode that needs to be initiated to test smoke, heat, or Rate-of-Rise.  These can be applied to the detector 

at any time as a test. 

 

  Test Button – When the Test Button is held down, the unit initiates a test on the smoke sensor, chamber, heat sensor, End-of-

Life, and battery.  If all tests pass, it sounds a normal alarm and sends alarm signal to the Control.  However, if one of these 

tests fails, it sends a trouble signal to the Control and provides fail status on the yellow led and sounder.  The Test Button is also 

used to silence or Hush the detector.  To Hush the detector, press and release the large Test Button.  Only the detector that 

initiated the alarm can be Hushed by the Test Button.  Other detectors that sound with One-Go-All-Go must be silenced by the 

Control by entering a disarm command.  Depending on how much smoke is still in the chamber determines if the Hush feature 

silences the detector and make it send an Alarm restore to the Control.  If there is too much smoke still in the chamber, it does 

not Hush nor send a restore to the Control Panel.  When Hush is successful, the sounder comes back on after 10 minutes and a 

restore signal is still not sent provided there is still enough smoke in the chamber to be considered an alarm.  Once the smoke 

level is below threshold in the chamber, Hush causes the sounder to

 

remain off and the restore signal is sent.  Entering a disarm 

command to the Control also silences all detectors that are sounding without needing to Hush any smoke detector.  See the 

LED and Sounder Indication Chart on the next page. 

  Smoke Entry Test (canned smoke*) – Can be done at any time.  Once the chamber is clear, the sounder will stop, and it will 

send a restore signal to the Control Panel. 

  Direct Heat Test (hair dryer 12” or further from the detector) 

  135° F fixed Heat Detection 

  Rate-of-Rise >104° F (40° C) @ 15° F/minute (8.33° C/minute). 

CAUTION:

  The detector alarms when 135° F is exceeded and restore when it falls below 135° F.  However, the thermistor is 

damaged at 195° F and the integrity of the detector itself is compromised and needs to be replaced. 

 

 

Reviews: