PROSiXGB 

Wireless Glass Break Detector

 

Installation and Setup Guide 

 

 

The PROSiXGB is a wireless glassbreak detector intended for use with Honeywell Home controls that support 

PROSiX™ Series devices. 

MOUNTING GUIDELINES 

The PROSiXGB can be mounted 

on the wall or on the ceiling: 

  within 7.6 m (25 feet) of the 

protected glass 

  within clear view of the protected 

glass 

  at least 2 m (6.5 feet) from the floor 

  at least 1 m (3.3 feet) from forced 

air ducts 

  at least 1 m (3.3 feet) from sirens or 

bells greater than 5 cm (2 inches) in 

diameter 

  between the protected glass and 

any heavy window coverings 

  when heavy window coverings are 

present, the detector can be 

mounted on the window frame 

  Avoid mounting the detector on the 

same wall as the protected glass, 

on free-standing posts or pillars, or 

in rooms with noisy equipment (air 

compressors, bells, power tools, 

etc.), if this equipment is operated 

when the detector is armed. 

 

 

To remove the mounting bracket: 

Turn the top of the detector 15 degrees counter-

clockwise and separate the mounting bracket. 

NOTE

: Before mounting the device permanently, 

conduct a sensor test (see controller’s 

instructions) to verify adequate signal 

strength and adjust the device location and 

orientation as necessary.

 

The rear tamper plate MUST be mounted to a stud, 

solid wood, or with a robust wall anchor.

 

 

 

Summary of Contents for PROSiX Series

Page 1: ... and any heavy window coverings when heavy window coverings are present the detector can be mounted on the window frame Avoid mounting the detector on the same wall as the protected glass on free standing posts or pillars or in rooms with noisy equipment air compressors bells power tools etc if this equipment is operated when the detector is armed To remove the mounting bracket Turn the top of the...

Page 2: ...rs down Activate the tamper power down and up again or use the FG 701 Glassbreak Simulator to restart the enrollment process 1Refer to the PROSiXGB LEDs section NOTE Once enrolled in a system the detector cannot be used with another controller until it is removed from the current controller See the Controller s instructions for details PROGRAM THE PROSIXGB Consult the Controller s instructions for...

Page 3: ...d diagnosis To save power the LEDs are not visible during Normal Mode TEST THE PROSIXGB The detector should be tested after installation and at least once a year Test Mode can be activated remotely from the Controller see Controller s manual or on site with an FG 701 Glassbreak Simulator only when the system is disarmed Follow directions in the FG 701 Glassbreak Simulator Operating Instructions to...

Page 4: ...viewed at https customer resideo com en US support residential codes and standards FCC15105 Pages default aspx FCC IC STATEMENT This device complies with Part 15 of the FCC Rules and Industry Canada s license exempt RSSs Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interferenc...

Reviews: