INSTALLATION INSTRUCTIONS

33-00157EFS-03

HM700ADVALVE

ELECTRODE STEAM HUMIDIFIER 
DRAIN VALVE REPLACEMENT

Read before installing

CAUTION

Before Servicing

1. Disconnect main power source before accessing 

internal compartments.

2. The plumbing and electrical compartments 

contain high voltage components and wiring. 
Access should be limited to licensed HVAC 
professionals only.

3. During and following operation of the humidifier, 

the steam components in contact with the steam 
such as the cylinder, steam lines, steam 
distributors, and condensate lines can become 
hot and burn if touched. Please consult HM700 
Installation manual for reference.

4. Installations of humidity equipment installed by 

unqualified personnel or the use of non-
Honeywell Home parts and components will void 
warranty.

Included in the Box

• Drain Valve
• Clip
• Phillips Head Screws
• Wiring  Harness
• Installation Instructions

Tools Needed

• Screwdriver
• Pliers (optional)

To Replace the Drain Valve

Refer to the humidifier operating manual if necessary.

1.

Drain cylinder.

2.

Turn off the unit when the cylinder is empty. 

3.

Disconnect power to the unit. 

4.

Remove cylinder. 

5.

Disconnect spade terminals from the drain valve.

6.

Remove the two screws holding the valve to the drain 
pan.

7.

Squeeze the tabs of the spring clamp holding the 
hose to the drain valve and slide it up the hose. Pull 
hose from drain valve.

8.

Drain valve can be removed and replaced with new 
one.

9.

Reverse steps above to install drain valve.

NOTE:

New screws and hose clamp provided.

Input: 120 V - 240 V 

∿;

 12 A 

For more information on maintenance and replacement, 
please visit http://honeywellhome.com 
or call 1-800-468-1502 or 1-800-814-9452.

Fig. 1. Drain valve.