66

TAKING CARE OF UNEXPECTED PROBLEMS

ENGINE WILL NOT START

Possible Cause

Correction

Fuel filler cap vent lever is in the 
OFF position.

Turn the vent lever to the ON
position (see page 25).

Engine switch is in the OFF
position.

Turn engine switch to the ON
position (see page 26).

Out of fuel.

Refuel (see page 47).

Bad fuel; generator stored 
without treating or draining 
gasoline, or refueled with bad 
gasoline.

Drain fuel tank and carburetor
(see page 61).
Refuel with fresh gasoline
(see page 47).

Low engine oil level caused Oil 
Alert to stop engine.

Turn the engine switch to the OFF 
position. Add engine oil. Then 
turn the engine switch to the ON 
position and restart the engine.

Spark plug faulty, fouled, or 
improperly gapped.

Gap or replace spark plug
(see page 55).

Spark plug wet with fuel 
(flooded engine).

Dry and reinstall spark plug.

Fuel filter restricted, carburetor 
malfunction, ignition 
malfunction, valves stuck, etc.

Take the generator to an 
authorized Honda servicing 
dealer, or refer to the shop 
manual.

31Z446020.book  66 ページ  2019年2月8日 金曜日 午前9時37分

Summary of Contents for EU22000i

Page 1: ...hailand 31Z44602 00X31 Z44 6020 GENERATOR Owner s Manual H i FM AH 英 PANTONE 186C K 背幅4 6mm EU2200i EU2200i Companion Companion See page 89 for Initial Use Instructions 2019 Honda Motor Co Ltd All Rights Reserved C ...

Page 2: ...contains poisonous carbon monoxide gas that can build up to dangerous levels in closed areas Breathing carbon monoxide can cause unconsciousness or death Never run the generator in a closed or even partly closed area where people may be present 31Z446020 book 0 ページ 2019年2月8日 金曜日 午前9時37分 QUICK REFERENCE INFORMATION Fuel Type Regular unleaded gasoline with an ethanol content of no more than 10 and a...

Page 3: ...intended to help you avoid damage to your generator other property or the environment We suggest you read the Distributor s Limited Warranty see page 79 to fully understand its coverage and your responsibilities of ownership When your generator needs scheduled maintenance keep in mind that your Honda servicing dealer is specially trained in servicing Honda generators and is supported by the parts ...

Page 4: ...important safety information in a variety of forms including Safety Labels on the generator Safety Messages preceded by a safety alert symbol and one of three signal words DANGER WARNING or CAUTION These signal words mean Safety Headings such as IMPORTANT SAFETY INFORMATION Safety Section such as GENERATOR SAFETY Instructions how to use this generator correctly and safely This entire book is fille...

Page 5: ...3 Starter Grip 13 Fuel Filler Cap Vent Lever 14 Choke Lever 14 Eco Throttle Switch 15 Parallel Operation Outlets 15 AC Circuit Protector 16 DC Receptacle A A2 types 17 DC Circuit Protector A A2 types 17 FEATURES 18 Ground Terminal 18 Output Indicator 19 Overload Alarm Indicator 20 Oil Alert Indicator 20 LED Light Patterns 21 BEFORE OPERATION 22 ARE YOU READY TO GET STARTED 22 Knowledge 22 IS YOUR ...

Page 6: ...Requirements 43 SERVICING YOUR GENERATOR 44 THE IMPORTANCE OF MAINTENANCE 44 MAINTENANCE SAFETY 45 Safety Precautions 45 MAINTENANCE SCHEDULE 46 REFUELING 47 FUEL RECOMMENDATIONS 48 ENGINE OIL LEVEL CHECK 49 ENGINE OIL CHANGE 50 ENGINE OIL RECOMMENDATIONS 51 AIR CLEANER SERVICE 52 MAIN AND OUTER FILTER CLEANING 54 SPARK PLUG SERVICE 55 SPARK ARRESTER SERVICE 57 STORAGE 59 STORAGE PREPARATION 59 Cl...

Page 7: ...Emission Control System Information 71 Air Index 73 Specifications 74 Wiring Diagram 75 CONSUMER INFORMATION 77 Dealer Locator Information 77 Honda Publications 77 Customer Service Information 78 Distributor s Limited Warranty 79 Honda Parts Accessories and Apparel 82 Emission Control System Warranty 84 INITIAL USE INSTRUCTIONS 89 ENGINE OIL 89 FUEL 90 BEFORE OPERATION 92 REGISTRATION 92 INDEX 93 ...

Page 8: ... smell Breathing carbon monoxide can KILL YOU IN MINUTES To avoid carbon monoxide poisoning follow these instructions when operating a generator Only run a generator OUTSIDE far away from windows doors and vents Never operate a generator inside a house garage basement crawl space or any enclosed or partially enclosed space Never operate a generator near open doors or windows Get fresh air and seek...

Page 9: ...onnecting the generator combinations shown below An EU2200i can only be paired with EU2000i or EU2000i Companion models that have serial numbers within the ranges shown below Never connect an EU2200i generator to a different generator model other than the models specified above Fire and Burn Hazards The exhaust system gets hot enough to ignite some materials Keep the generator at least 3 feet 1 me...

Page 10: ...as been in operation Refuel only outdoors in a well ventilated area and on a level surface Never smoke near gasoline and keep other flames and sparks away Do not overfill the fuel tank Make sure that any spilled fuel has been wiped up and cleaned before starting the engine Always store gasoline in an approved container 31Z446020 book 8 ページ 2019年2月8日 金曜日 午前9時37分 ...

Page 11: ...se labels warn you of potential hazards that can cause serious injury Read them carefully If a label comes off or becomes hard to read contact your Honda servicing dealer for a replacement Example A type 31Z446020 book 9 ページ 2019年2月8日 金曜日 午前9時37分 ...

Page 12: ...10 GENERATOR SAFETY Example A type 31Z446020 book 10 ページ 2019年2月8日 金曜日 午前9時37分 ...

Page 13: ...ges to locate and identify the most frequently used controls SPARK PLUG MAINTENANCE COVER MUFFLER SPARK PLUG FRAME SERIAL NUMBER AIR CLEANER FUEL FILLER CAP VENT LEVER FUEL FILLER CAP ENGINE SWITCH STARTER GRIP MAINTENANCE COVER CHOKE LEVER 31Z446020 book 11 ページ 2019年2月8日 金曜日 午前9時37分 ...

Page 14: ... THROTTLE SWITCH PARALLEL OPERATION OUTLETS AC RECEPTACLES DC RECEPTACLE DC CIRCUIT PROTECTOR GROUND TERMINAL OUTPUT INDICATOR OVERLOAD INDICATOR OIL ALERT INDICATOR AC CIRCUIT PROTECTOR ECO THROTTLE SWITCH PARALLEL OPERATION OUTLETS AC CIRCUIT PROTECTOR GROUND TERMINAL OUTPUT INDICATOR OVERLOAD INDICATOR OIL ALERT INDICATOR 20 A RECEPTACLE 30 A twist lock receptacle 31Z446020 book 12 ページ 2019年2月8...

Page 15: ...loses only the fuel valve see page 28 ON Running position opens the fuel valve and allows the engine to be started Starter Grip Pulling the starter grip operates the recoil starter to start the engine Do not allow the starter grip to snap back against the generator Return it gently to prevent damage to the starter ENGINE SWITCH ON OFF STARTER GRIP FUEL OFF 31Z446020 book 13 ページ 2019年2月8日 金曜日 午前9時3...

Page 16: ...he possibility of fuel leakage Allow the engine to cool well before turning the vent lever to the OFF position Choke Lever The choke is used to provide proper starting mixture when the engine is cold It can be opened and closed by operating the choke lever manually Move the choke lever to the CLOSED position to enrich the mixture for cold starting FUEL FILLER CAP VENT LEVER OFF ON FUEL FILLER CAP ...

Page 17: ... ON Recommended to minimize fuel consumption and further reduce noise levels when less than a full load is applied to the generator OFF The Eco Throttle system does not operate Parallel Operation Outlets These outlets are used for connecting both types of the EU2200i generators Standard and Companion or EU2000i generators Standard and Companion for parallel operation see page 33 through 37 A Honda...

Page 18: ...he circuit protector switches OFF automatically check that the appliance is working properly and does not exceed the rated load capacity of the circuit before resetting the circuit protector ON A A2 types A1 type 20 A RECEPTACLES ON OFF PUSH AC CIRCUIT PROTECTOR AC CIRCUIT PROTECTOR 20 A RECEPTACLE ON OFF PUSH AC CIRCUIT PROTECTOR AC CIRCUIT PROTECTOR 31Z446020 book 16 ページ 2019年2月8日 金曜日 午前9時37分 ...

Page 19: ...frequently while charging to prevent overcharging the battery DC Circuit Protector A A2 types The DC circuit protector automatically shuts off the DC battery charging circuit when the DC charging circuit is overloaded when there is a problem with the battery or when the connections between the battery and the generator are improper However the DC circuit protector does not prevent overcharging DC ...

Page 20: ...qualified electrician electrical inspector or local agency having jurisdiction for local codes or ordinances that apply to the intended use of the generator NEUTRAL FLOATING The generator stator winding is isolated from the frame and from the AC receptacle ground pin Electrical devices that require a grounded receptacle pin connection will not function if the receptacle ground pin is not functiona...

Page 21: ...tacles In addition the output indicator has a simplified hour meter function When you start the engine the indicator blinks according to the generator s cumulative operating hours as follows No blinks 0 100 hours 1 blink 100 200 hours 2 blinks 200 300 hours 3 blinks 300 400 hours 4 blinks 400 500 hours 5 blinks 500 or more hours OUTPUT INDICATOR GREEN 31Z446020 book 19 ページ 2019年2月8日 金曜日 午前9時37分 ...

Page 22: ...ests an abnormal of inverter unit see page 68 Oil Alert Indicator The Oil Alert system is designed to prevent engine damage caused by an insufficient amount of oil in the crankcase Before the oil level in the crankcase can fall below a safe limit the Oil Alert indicator red comes ON and the Oil Alert system automatically will stop the engine the engine switch will remain in the ON position If the ...

Page 23: ...e diagnosis Status Possible cause Output Indicator Overload indicator Oil Alert Indicator Normal Operating normally Malfunction Inverter unit failure Abnormal Output overcurrent Inverter unit overheat Warning Engine oil low OIL ALERT INDICATOR OVERLOAD INDICATOR OUTPUT INDICATOR 31Z446020 book 21 ページ 2019年2月8日 金曜日 午前9時37分 ...

Page 24: ...ating see pages 32 and 37 IS YOUR GENERATOR READY TO GO For your safety to ensure compliance with environmental regulations and to maximize the service life of your equipment it is very important to take a few moments before you operate the generator to check its condition Be sure to take care of any problem you find or have your servicing dealer correct it before you operate the generator Failure...

Page 25: ...n Check the Engine Before each use look around and underneath the engine for signs of oil or gasoline leaks Check the engine oil level see page 49 A low engine oil level will cause the Oil Alert system to shut down the engine Check the air filters see page 52 Dirty air filters will restrict air flow to the carburetor reducing engine and generator performance Check the fuel level see page 47 Starti...

Page 26: ... damaged Make sure that the appliance is in good working order Faulty appliances or power cords can create a potential for electric shock Make sure the electrical rating of the tool or appliance does not exceed the rated power of the generator or the receptacle being used Operate the generator at least 3 feet 1 meter away from buildings and other equipment Do not operate the generator in an enclos...

Page 27: ...clear of debris mud water etc Cooling holes are located on the side panel the control panel and the bottom of the generator If the cooling holes are blocked the generator may overheat and damage the engine inverter or windings Refer to SAFE OPERATING PRECAUTIONS on page 24 and perform the IS YOUR GENERATOR READY TO GO checks see page 22 Refer to the AC OPERATION see page 30 AC PARALLEL OPERATION s...

Page 28: ...red for warm up 4 To start a cold engine move the choke lever to the CLOSED position To restart a warm engine leave the choke lever in the OPEN position 5 Turn the engine switch to the ON position ECO THROTTLE SWITCH OFF CHOKE LEVER CLOSED ON ENGINE SWITCH 31Z446020 book 26 ページ 2019年2月8日 金曜日 午前9時37分 ...

Page 29: ...ent damage to the starter 7 If the choke lever was moved to the CLOSED position to start the engine gradually move it to the OPEN position as the engine warms up 8 If you wish to use the Eco Throttle system turn the Eco Throttle switch to the ON position after the engine has warmed up for 2 or 3 minutes STARTER GRIP CHOKE LEVER ECO THROTTLE SWITCH OPEN Direction to pull ON 31Z446020 book 27 ページ 20...

Page 30: ...position can reduce the fuel in the carburetor When using the FUEL OFF position the generator will continue to run for several minutes until the fuel in the carburetor has been consumed and then the engine will stop Turn the engine switch to the OFF position after the engine stops After stopping the engine using the FUEL OFF position restarting the engine will require additional pulls on the recoi...

Page 31: ...n cable after stopping the engines if you do not wish to resume parallel operation If the generator will not be used for a long period of time refer to page 61 for information on Draining the Fuel Tank and Carburetor PARALLEL OPERATION CABLE optional equipment 31Z446020 book 29 ページ 2019年2月8日 金曜日 午前9時37分 ...

Page 32: ... than their electrical rating for startup When an electric motor is started the overload indicator red may come ON This is normal if the overload indicator red goes OFF within 4 seconds If the overload indicator red stays ON consult your generator dealer 1 Start the engine see page 25 and make sure the output indicator green comes ON OVERLOAD INDICATOR RED OUTPUT INDICATOR GREEN 31Z446020 book 30 ...

Page 33: ...red will go ON The overload indicator red will stay ON and after about four seconds current to the connected appliance s will shut off and the output indicator green will go OFF Stop the engine and investigate the problem Determine if the cause is a short circuit in a connected appliance or an overload Correct the problem and restart the generator 20 A RECEPTACLE 31Z446020 book 31 ページ 2019年2月8日 金曜...

Page 34: ... wattage for startup Make sure the electrical rating of the tool or appliance does not exceed the maximum power rating of the generator Maximum power is 2 2 kVA For continuous operation do not exceed the rated power Rated power is 1 8 kVA In either case the total power requirements VA of all appliances connected must be considered Appliance and power tool manufacturers usually list rating informat...

Page 35: ...c motor is started the overload indicator red may come ON This is normal if the overload indicator red goes OFF within 4 seconds If the overload indicator red stays ON consult your generator dealer During parallel operation the Eco Throttle switch should be in the same position on both generators 1 Connect the parallel operation cable between the EU2200i to either an EU2200i Companion or another E...

Page 36: ...overloaded see page 37 or if there is a short circuit in a connected appliance the overload indicator red will go ON The overload indicator red will stay ON and after about four seconds current to the connected appliance s will shut off and the output indicator green will go OFF Stop both engines and investigate the problem Determine if the cause is a short circuit in a connected appliance or an o...

Page 37: ...ly be connected to EU2000i or EU2000i Companion generators that have specific frame serial numbers Refer to the table below to confirm that your EU2000i or EU2000i Companion generator is compatible with an EU2200i Models Frame Serial Number Range EU2000i EU2000i Companion EAAJ 2017305 and later EACT 1000001 and later 31Z446020 book 35 ページ 2019年2月8日 金曜日 午前9時37分 ...

Page 38: ...s sluggish or stops suddenly turn it off immediately Disconnect the appliance and determine whether the problem is the appliance or the rated load capacity of the generator has been exceeded Never connect other than the specified generator models see page 7 For parallel operation use only a Honda approved parallel operation cable optional equipment Never connect or remove the parallel operation ca...

Page 39: ...nsidered Appliance and power tool manufacturers usually list rating information near the model number or serial number Substantial overloading that continuously lights the overload indicator red may damage the generator Marginal overloading that temporarily lights the overload indicator red may shorten the service life of the generator EU2200i EU2200i Companion and EU2200i Companion 4 4kVA EU2200i...

Page 40: ...uipment 1 Before connecting the battery charging cable to a battery that is installed in a vehicle disconnect the vehicle battery ground cable from the negative battery terminal WARNING Battery posts terminals and related accessories contain lead and lead components Wash hands after handling 2 Plug the battery charging cable into the DC receptacle of the generator The battery gives off explosive h...

Page 41: ...essive current draw by the battery or a wiring problem will trip the DC circuit protector PUSH button extends out If this happens wait a few minutes before pushing in the circuit protector to resume operation If the DC circuit protector continues to go OFF discontinue charging and see your authorized Honda generator dealer The circuit protector does not prevent overcharging the battery BATTERY CHA...

Page 42: ...rminal 3 Disconnect the red lead of the battery charging cable from the positive battery terminal 4 Disconnect the battery charging cable from the DC receptacle of the generator 5 Connect the vehicle battery ground cable to the negative battery terminal BATTERY CHARGING CABLE optional equipment BLACK LEAD RED LEAD 31Z446020 book 40 ページ 2019年2月8日 金曜日 午前9時37分 ...

Page 43: ...h to the OFF position and connect the appliance to the generator If the engine still will not reach normal operating speed check that the appliance does not exceed the rated load capacity of the generator If high electrical loads are connected simultaneously turn the Eco Throttle switch to the OFF position to reduce voltage changes The Eco Throttle system is not effective for use with appliances o...

Page 44: ...cedures System Ground This generator has a system ground that connects generator frame components to ground terminals in the AC output receptacles The system ground is not connected to the AC neutral wire Improper connections to a building s electrical system can allow current from the generator to backfeed into the utility lines Such backfeed may electrocute utility company workers or others who ...

Page 45: ...ation OSHA regulations local codes or ordinances that apply to the intended use of the generator Please consult a qualified electrician electrical inspector or the local agency having jurisdiction In some areas generators are required to be registered with local utility companies If the generator is used at a construction site there may be additional regulations that must be observed 31Z446020 boo...

Page 46: ...operation or use it in dusty conditions consult your servicing dealer for recommendations applicable to your individual needs and use Remember that an authorized Honda servicing dealer knows your generator best and is fully equipped to maintain and repair it To ensure the best quality and reliability use only new Honda Genuine parts or their equivalents for repair and replacement Maintenance repla...

Page 47: ... parts Let the engine and exhaust system cool before touching Injury from moving parts Do not run the engine unless instructed to do so Read the instructions before you begin and make sure you have the tools and skills required To reduce the possibility of fire or explosion be careful when working around gasoline Use only a non flammable solvent not gasoline to clean parts Keep cigarettes sparks a...

Page 48: ...this maintenance schedule could result in non warrantable failures REGULAR SERVICE PERIOD 3 Perform at every indicated month or operating hour interval whichever comes first ITEM Each use First month or 20 Hrs Every 3 months or 50 Hrs Every 6 months or 100 Hrs Every year or 200 Hrs Page Engine oil Check level o 49 Change o o 50 Air cleaner Check o 52 Clean o 1 54 Spark plug Check adjust o 55 Repla...

Page 49: ...avoid spilling fuel Do not fill the fuel tank above the upper level mark see page 48 on the fuel filter Never refuel the engine inside a building where gasoline fumes may reach flames or sparks Keep gasoline away from appliance pilot lights barbecues electric appliances power tools etc Spilled fuel is not only a fire hazard it causes environmental damage Wipe up spills immediately Gasoline is high...

Page 50: ...olvents and corrosion inhibitors Use of fuels with content of ethanol or methanol greater than shown above may cause starting and or performance problems It may also damage metal rubber and plastic parts of the fuel system Engine damage or performance problems that result from using a fuel with percentages of ethanol or methanol greater than shown above are not covered under warranty If your equip...

Page 51: ... 4 If the level is low fill to the upper limit of the oil filler neck with the recommended oil see page 51 5 Reinstall the oil filler cap securely 6 Reinstall the maintenance cover and tighten the maintenance cover screw securely The Oil Alert system will automatically stop the engine before the oil level falls below safe limits However to avoid the inconvenience of an unexpected shutdown check th...

Page 52: ...iller neck Improper disposal of engine oil can be harmful to the environment If you change your own oil please dispose of the used oil properly Put it in a sealed container and take it to a recycling center Do not discard it in a trash bin dump it on the ground or pour it down the drain 5 With the engine in a level position fill with the recommended oil see page 51 to the upper limit of the oil fi...

Page 53: ...mended for general use Other viscosities shown in the chart may be used when the average temperature in your area is within the recommended range The SAE oil viscosity and service category are in the API label on the oil container Honda recommends that you use API service category SJ or later or equivalent oil AMBIENT TEMPERATURE 31Z446020 book 51 ページ 2019年2月8日 金曜日 午前9時37分 ...

Page 54: ...d outer filters from the air cleaner housing 4 Check the main and outer filters to be sure they are clean and in good condition If the main and outer filters are dirty clean them as described on page 54 Replace the main and outer filters if they are damaged MAIN FILTER MAINTENANCE COVER SCREW MAINTENANCE COVER AIR CLEANER COVER SCREW OUTER FILTER AIR CLEANER COVER 31Z446020 book 52 ページ 2019年2月8日 金...

Page 55: ...install the maintenance cover and tighten the maintenance cover screw securely Operating the engine without the air filters or with a damaged air filter will allow dirt to enter the engine causing rapid engine wear This type of damage is not covered by the Distributor s Limited Warranty AIR CLEANER COVER RUBBER SEAL AIR FILTERS AIR CLEANER COVER SCREW AIR CLEANER COVER 31Z446020 book 53 ページ 2019年2...

Page 56: ...oapy water rinse and allow to dry thoroughly or clean in nonflammable solvent and allow to dry 2 Dip the air cleaner element in clean engine oil and then squeeze out all excess oil The engine will smoke when started if too much oil is left in the air filters 3 Wipe dirt from the air cleaner housing and cover using a moist rag Be careful to prevent dirt from entering the air duct that leads to the ...

Page 57: ...ed and free of deposits An incorrect spark plug can cause engine damage If the engine is hot allow it to cool before servicing the spark plug 1 Remove the spark plug maintenance cover 2 Remove the spark plug cap 3 Clean any dirt from around the spark plug base 4 Use a spark plug wrench to remove the spark plug SPARK PLUG MAINTENANCE COVER SPARK PLUG CAP SPARK PLUG WRENCH SPARK PLUG CAP 31Z446020 b...

Page 58: ...ss threading 8 After the spark plug is seated tighten with a spark plug wrench to compress the sealing washer If reinstalling a used spark plug tighten 1 8 1 4 turn after the spark plug seats If installing a new spark plug tighten 1 2 turn after the spark plug seats TORQUE 8 7 lbf ft 12 N m 1 2 kgf m A loose spark plug can overheat and damage the engine Overtightening the spark plug can damage the...

Page 59: ...ry hot Allow the muffler to cool before servicing the spark arrester Clean the spark arrester as follows 1 Remove the four 6 mm screws and remove the muffler protector 2 Remove the three 6 mm bolts and remove the muffler the spark arrester and the muffler gasket MUFFLER PROTECTOR 6 mm SCREWS MUFFLER GASKET Replace SPARK ARRESTER MUFFLER 6 mm BOLTS 31Z446020 book 57 ページ 2019年2月8日 金曜日 午前9時37分 ...

Page 60: ... Be careful to avoid damaging the screen The spark arrester must be free of breaks and tears Replace the spark arrester if it is damaged 4 Replace a new muffler gasket the spark arrester the muffler and the muffler protector in the reverse order of removal 31Z446020 book 58 ページ 2019年2月8日 金曜日 午前9時37分 ...

Page 61: ...d it leaves gum deposits that clog the fuel system If the gasoline in your generator deteriorates during storage you may need to have the carburetor and other fuel system components serviced or replaced The length of time that gasoline can be left in your fuel tank and carburetor without causing functional problems will vary with such factors as gasoline blend your storage temperatures and whether...

Page 62: ...add gasoline stabilizer Turn the engine switch to the OFF position and drain the carburetor float bowl see page 62 1 year or more Drain the fuel tank and carburetor see page 61 Change the engine oil and lubricate the cylinder see page 63 Use gasoline stabilizers that are formulated to extend storage life Follow the manufacturer s instructions for use Contact your authorized Honda generator dealer ...

Page 63: ...Reinstall the fuel filter and the fuel filler cap 2 Loosen the maintenance cover screw and remove the maintenance cover see page 49 Gasoline is highly flammable and explosive You can be burned or seriously injured when handling fuel Stop the engine and let it cool before handling fuel Keep heat sparks and flame away Handle fuel only outdoors Wipe up spills immediately FUEL FILTER FUEL FILLER CAP M...

Page 64: ... the ON position see page 26 6 Pull the starter grip 3 to 4 times to drain the gasoline from the fuel pump into a suitable container 7 Turn the engine switch to the OFF position securely 8 Tighten the carburetor drain screw and then reinstall the maintenance cover 9 Reinstall the spark plug cap and spark plug maintenance cover CARBURETOR DRAIN SCREW ENGINE SWITCH OFF FUEL OFF 31Z446020 book 62 ページ...

Page 65: ...istribute the oil then reinstall the spark plug 2 Reinstall the spark plug cap on the spark plug securely 3 Reinstall the spark plug maintenance cover 4 Reinstall the maintenance cover and tighten the maintenance cover screw securely 5 Pull the starter grip see page 27 slowly until you feel resistance then return the starter grip gently This closes the valves so moisture cannot enter 31Z446020 boo...

Page 66: ...Place the generator on a level surface Tilting or laying it on its side can cause fuel or oil leakage With the engine and exhaust system cool cover the generator to keep out dust A hot engine and exhaust system can ignite or melt some materials Do not use a plastic sheet as a dust cover A nonporous cover will trap moisture around the generator promoting rust and corrosion REMOVAL FROM STORAGE Chec...

Page 67: ...A hot engine and exhaust system can burn you and can ignite some material To prevent fuel spillage when transporting the generator should be secured upright in its normal operating position with the engine switch OFF and the fuel filler cap vent lever turned fully counterclockwise to the OFF position see page 28 Take care not to drop or strike the generator when transporting Do not place heavy obj...

Page 68: ... and carburetor see page 61 Refuel with fresh gasoline see page 47 Low engine oil level caused Oil Alert to stop engine Turn the engine switch to the OFF position Add engine oil Then turn the engine switch to the ON position and restart the engine Spark plug faulty fouled or improperly gapped Gap or replace spark plug see page 55 Spark plug wet with fuel flooded engine Dry and reinstall spark plug...

Page 69: ...red without treating or draining gasoline or refueled with bad gasoline Drain fuel tank and carburetor see page 61 Refuel with fresh gasoline see page 47 Fuel filter restricted carburetor malfunction ignition malfunction valves stuck etc Take the generator to an authorized Honda servicing dealer or refer to the shop manual 31Z446020 book 67 ページ 2019年2月8日 金曜日 午前9時37分 ...

Page 70: ...ler or refer to the shop manual AC circuit protector tripped Check AC load and reset circuit protector see page 16 Faulty power tool or appliance Replace or repair power tool or appliance Stop and restart the engine Faulty generator Take the generator to an authorized Honda servicing dealer or refer to the shop manual Possible Cause Correction DC circuit protector OFF Turn DC circuit protector ON ...

Page 71: ...e frame serial number and date purchased in the spaces below You will need this information when ordering parts and when making technical or warranty inquiries Frame serial number Date purchased FRAME SERIAL NUMBER 31Z446020 book 69 ページ 2019年2月8日 金曜日 午前9時37分 ...

Page 72: ...this carburetor modification This engine when operated at high altitude with the carburetor modifications for high altitude use will meet each emission standard throughout its useful life Even with carburetor modification engine horsepower will decrease about 3 5 for each 1 000 foot 300 meter increase in altitude The effect of altitude on horsepower will be greater than this if no carburetor modif...

Page 73: ... reduce evaporative emissions The U S and California Clean Air Acts EPA and California regulations require all manufacturers to furnish written instructions describing the operation and maintenance of emission control systems The following instructions and procedures must be followed in order to keep the Honda engine emissions within the emission standards Tampering and Altering Tampering is a vio...

Page 74: ... have service performed at non Honda locations However the use of replacement parts that are not of the original design and quality may impair the effectiveness of your emissions control system A manufacturer of an aftermarket part assumes the responsibility that the part will not adversely affect emissions performance The manufacturer or rebuilder of the part must certify that use of the part wil...

Page 75: ...ability description is intended to provide you with information relating to the engine s emission durability period The descriptive term indicates the useful life period for the engine s emission control system See your Emission Control System Warranty see page 84 for additional information Descriptive Term Applicable to Emission Durability Period Moderate 50 hours 0 80 cc inclusive 125 hours grea...

Page 76: ...ith Eco Throttle switch OFF Cooling system Forced air Ignition system Full transistor Engine oil capacity 14 oz 0 44 L Fuel tank capacity 0 95 US gal 3 6 L Spark plug CR5HSB NGK Model EU2200iT EU2200iT Companion Type A A2 A1 AC output Rated voltage 120 V Rated frequency 60 Hz Rated current 15 A Rated output 1 8 kVA Maximum output 2 2 kVA DC output Only for charging 12 V automotive batteries Maximu...

Page 77: ... R G Bl G Bl G Bl G G R W G R G Bl OUTPUT INDICATOR OVERLOAD INDICATOR Y G Bl Bl Bu Bu R W R Y R W W R R Y W R G R G Bl ENGINE BLOCK FRAME BLOCK CONTROL PANEL BLOCK INVERTER BLOCK GENERATOR BLOCK DC OUTLET RECEPTACLE FRAME GROUND SPARK UNIT ECO THROTTLE SWITCH PARALLEL OUTLETS CIRCUIT PROTECTOR 20A GROUND TERMINAL OIL ALERT INDICATOR BLACK YELLOW BLUE GREEN RED WHITE GRAY PINK LIGHT GREEN SKY BLUE...

Page 78: ...INDICATOR OVERLOAD INDICATOR Y G Bl Bl Bu Bu R W R Y R W W R R Y W R W W R G R G Bl ENGINE BLOCK FRAME BLOCK CONTROL PANEL BLOCK INVERTER BLOCK GENERATOR BLOCK FRAME GROUND SPARK UNIT ECO THROTTLE SWITCH PARALLEL OUTLETS AC RECEPTACLE 5 20R L5 30R CIRCUIT PROTECTOR 20A GROUND TERMINAL OIL ALERT INDICATOR BLACK YELLOW BLUE GREEN RED WHITE GRAY PINK LIGHT GREEN SKY BLUE ORANGE BROWN W R G Bu Y Bl Gr...

Page 79: ...our Honda dealer or visit http powerequipment honda com support shop manuals Parts Catalog This manual provides complete illustrated parts lists Available through your Honda dealer or visit http peparts honda com Accessories Catalog Your authorized Honda power equipment dealer offers a wide selection of accessories optional equipment to make your Generator even more useful Visit http powerequipmen...

Page 80: ... by the dealership s management contact the Honda Power Equipment Customer Relations Office You can write to American Honda Motor Co Inc Power Equipment Division Customer Relations Office 4900 Marconi Drive Alpharetta Georgia 30005 8847 Or telephone 770 497 6400 1 888 888 3139 toll free 8 30 am to 7 00 pm ET When you write or call please give us this information Model and serial numbers see page 6...

Page 81: ...erican Honda or a dealer authorized by American Honda to sell those products This warranty applies to first retail purchaser and each subsequent owner during the applicable warranty time period unless noted otherwise What American Honda will Repair or Replace Under Warranty American Honda will repair or replace at its option any part that is proven to be defective in material or workmanship under ...

Page 82: ... To locate a dealer near you visit our web site at http powerequipment honda com and click on Find a Dealer If you are unable to obtain warranty service or are dissatisfied with the warranty service you receive contact the owner of the dealership involved normally this will resolve the problem However if you should require further assistance write or call the Power Equipment Customer Relations Dep...

Page 83: ...ch disc tire wheel bearing recoil starter rope cable belt cutter blade oil and grease 3 Cleaning adjustment and normal periodic maintenance work carburetor cleaning engine oil draining blade sharpening belt and cable adjustments 4 Any product that has ever been declared a total loss or sold for salvage by a financial institution or insurer 5 Auger and paddle assemblies skid shoes and scraper bars ...

Page 84: ...r Equipment parts accessories or apparel that are proven to be defective in material or workmanship under normal use during the applicable warranty time period Anything replaced under warranty becomes the property of American Honda Motor Co Inc The warranty on all parts accessories and apparel replaced under warranty will expire coincident with the original warranty on the replaced parts accessori...

Page 85: ...apparel affected or damaged by collision normal wear use in an application for which the product was not designed or any other misuse neglect incorporation or use of unsuitable attachments or parts unauthorized alteration improper installation or any causes other than defects in material or workmanship of the product Installing parts and accessories on non Honda products or engines voids this warr...

Page 86: ...t the state s stringent anti smog standards Specific Honda products that do not meet the California emissions regulations can be identified by a Not for sale in California decal Other States U S territories and Canada In other areas of the United States and in Canada your engine must be designed built and equipped to meet the U S EPA and Environment Canada emission standards for spark ignited engi...

Page 87: ...led due to abuse neglect improper maintenance or unapproved modifications You are responsible for presenting your power equipment engine to a Honda Power Equipment dealer as soon as a problem exists The emission related warranty repairs should be completed in a reasonable amount of time not to exceed 30 days If you have any questions regarding your emission warranty rights and responsibilities you...

Page 88: ...nce items such as spark plugs and filters that are on the warranted parts list are warranted up to their required replacement interval only Honda will also replace other engine components damaged by a failure of any warranted part during the warranty period Honda cannot deny coverage under the emission warranty solely for use of non Honda replacement parts or service performed at a location other ...

Page 89: ... your region Exclusions Failures other than those resulting from defects in material or workmanship are not covered by this warranty This warranty does not extend to emission control systems or parts that are affected or damaged by owner abuse neglect improper maintenance misuse misfueling improper storage collision the incorporation of or use of unsuitable attachments or the unauthorized alterati...

Page 90: ... the first required replacement only See the MAINTENANCE SCHEDULE on page 46 SYSTEMS COVERED BY THIS WARRANTY PARTS DESCRIPTION Fuel Metering Carburetor assembly includes starting enrichment system Oxygen sensor Throttle body Engine temperature sensor Engine control module Fuel injector Fuel regulator Intake manifold Evaporative Fuel tank Fuel cap Fuel hoses Vapor hoses Carbon canister Canister mo...

Page 91: ...to the upper limit of the oil filler neck SAE 10W 30 oil is recommended for general use for additional recommendations see page 51 Maximum oil capacity 14 oz 0 44 L Do not overfill the engine with oil If the engine is overfilled the excess oil may be transferred to the air cleaner housing and air filter 5 Screw in the oil filler cap securely 6 Reinstall the maintenance cover and tighten the mainte...

Page 92: ...ronmental damage Wipe up spills immediately This engine is certified to operate on unleaded gasoline with a pump octane rating of 86 or higher Refer to page 48 for additional fuel recommendations 1 Remove the fuel filler cap Gasoline is highly flammable and explosive You can be burned or seriously injured when handling fuel Stop the engine and let it cool before handling fuel Keep heat sparks and ...

Page 93: ... fuel filler cap vent lever OFF for storage or transport and ON to run the generator Move the generator at least 10 feet 3 meters away from the fueling source and site before starting the engine After initial fueling or anytime the generator is run completely out of fuel starting the engine may require additional pulls of the starter grip This generator utilizes a vacuum operated fuel pump and may...

Page 94: ...egister Your Generator If your dealer did not collect registration information from you please take a few minutes and register your purchase with Honda This allows us to contact you with any important updates regarding your generator Please note registration is not required to obtain warranty service You can register your generator by visiting the Honda Power Equipment website http powerequipment ...

Page 95: ...dification for High Altitude Operation 70 Check the Engine 23 Choke Lever 14 Cleaning 59 COMPONENT CONTROL LOCATIONS 11 Connections to a Building s Electrical System 42 CONSUMER INFORMATION 77 CONTENTS 3 CONTROLS 13 CONTROLS FEATURES 11 Customer Service Information 78 D DC Circuit Protector A A2 types 17 DC OPERATION A A2 types 38 DC Receptacle A A2 types 17 Dealer Locator Information 77 Distribut...

Page 96: ... OIL RECOMMENDATIONS 51 Engine Switch 13 ENGINE WILL NOT START 66 F FEATURES 18 Fire and Burn Hazards 7 Fuel 59 90 Fuel Filler Cap Vent Lever 14 FUEL OFF Position 13 FUEL RECOMMENDATIONS 48 G GENERATOR SAFETY 6 Ground Terminal 18 H Honda Parts Accessories and Apparel 82 Honda Publications 77 I IMPORTANT SAFETY INFORMATION 6 INITIAL USE INSTRUCTIONS 89 IS YOUR GENERATOR READY TO GO 22 K Knowledge 2...

Page 97: ...R AT THE DC RECEPTACLES 68 O Oil Alert Indicator 20 OPERATION 24 Operator Responsibility 6 Output Indicator 19 Overload Alarm Indicator 20 P Parallel Operation Outlets 15 Q QUICK REFERENCE INFORMATION Inside back cover R REFUELING 47 Refuel With Care 8 REGISTRATION 92 REMOVAL FROM STORAGE 64 31Z446020 book 95 ページ 2019年2月8日 金曜日 午前9時37分 ...

Page 98: ...ERVICE 55 Special Requirements 43 Specifications 74 STANDBY POWER 42 Starter Grip 13 STARTING THE ENGINE 25 STOPPING THE ENGINE 28 STORAGE 59 STORAGE PRECAUTIONS 64 STORAGE PREPARATION 59 System Ground 42 T TAKING CARE OF UNEXPECTED PROBLEMS 66 TECHNICAL INFORMATION 69 THE IMPORTANCE OF MAINTENANCE 44 TRANSPORTING 65 W Wiring Diagram 75 31Z446020 book 96 ページ 2019年2月8日 金曜日 午前9時37分 ...

Page 99: ...contains poisonous carbon monoxide gas that can build up to dangerous levels in closed areas Breathing carbon monoxide can cause unconsciousness or death Never run the generator in a closed or even partly closed area where people may be present 31Z446020 book 0 ページ 2019年2月8日 金曜日 午前9時37分 QUICK REFERENCE INFORMATION Fuel Type Regular unleaded gasoline with an ethanol content of no more than 10 and a...

Page 100: ...hailand 31Z44602 00X31 Z44 6020 GENERATOR Owner s Manual H i FM AH 英 PANTONE 186C K 背幅4 6mm EU2200i EU2200i Companion Companion See page 89 for Initial Use Instructions 2019 Honda Motor Co Ltd All Rights Reserved C ...

Reviews: