AC receptacle selection
The generator has separate main power producing circuits. These two
circuits supply power to different receptacles shown when the voltage
selector switch is in the 120/240 V position.
When two or more receptacles are used, prevent overloading by
dividing the load between the two power circuits.
The chart below shows the rated load in amperes that can be
connected to each receptacle to balance the generator when the 120/
240 V locking plug receptacle is used for 120 V.
The total rated ampere draw is:
(L type only)
Model
EM50is
EM70is
Main power
circuit
Main Circuit I
Main Circuit II
Main Circuit I
Main Circuit II
Receptacles powered
by each main circuit
1, 3 and 4
2 and 5
1, 3 and 4
2 and 5
Power distribution
(rated ampere)
1
3
4 = 18.8A
2
5 = 18.8A
1
3
4 = 22.9A
2
5 = 22.9A
EM50is: 37.5A/EM70is: 45.8A