37
OPERATION
Voltage Selector Switch
Set of
Receptacles
Total Current
Available
Power Producing
Circuit
120 V/240 V Position
120 V ONLY Position
Switch Position
Receptacle
Available Power
1
3
4B
2
4A
18.8 A
18.8 A
1
2
When the voltage selector switch is in the 120 V/240 V position, you
must balance the load. Divide the load between the two sets of
receptacles shown below. Balancing is necessary because each set of
receptacles is powered by only one power producing circuit that can
produce a maximum of 18.8 amps.
When the voltage selector switch is in the 120 V ONLY position, you do
not need to spread the load over the receptacles. You must, however,
make sure the load on any receptacle does not exceed its available
power shown in the preceding table and the total load does not
exceed 37.5 amps.
120 V ONLY
120 V/240 V
1
2
3
4A
4B
1
2
3
4A-4B
30 A at 120 V
20 A at 120 V
20 A at 120 V
30 A at 120 V
None
18.8 A at 120 V
18.8 A at 120 V
18.8 A at 120 V
18.8 A at 240 V
The power available to each receptacle depends on the position of the
voltage selector switch.
Disconnect or turn OFF all appliances or tools connected to the
generator before changing the voltage selector switch position.
The generator may be damaged if the switch position is changed with
loads connected and operating.
11/03/27 07:57:50 31Z11710_038
Summary of Contents for EM5000is
Page 1: ......
Page 79: ...77 TECHNICAL CONSUMER INFORMATION Wiring Diagram 11 03 27 08 04 03 31Z11710_078 ...
Page 100: ...98 MEMO 11 03 27 08 06 56 31Z11710_099 ...
Page 101: ...99 MEMO 11 03 27 08 06 58 31Z11710_100 ...
Page 102: ...100 MEMO 11 03 27 08 07 01 31Z11710_101 ...
Page 104: ...00X31Z117200 ...