04 Calibration
offset
This item is used to raise or lower the current temperature reading by 1 degree Fahrenheit or 1/2 degree Celsius.
If this item is set to 30, no change will be made. Each digit below 30 will lower to temperature, and each digit
above 30 will raise the temperature.
(1 = “- 29” to 59 = “+ 29” temperature units; 30 = No change)
The default setting is 30.
05 Cool setpoint limit
This item is used to limit the temperature setting in cool mode. The desired cool setting can never be set below
this setting.
The default setting is 51.
06 Heat setpoint limit
This item is used to limit the temperature setting in heat mode. The desired heat setting can never be set above
this setting.
The default setting is 91.
07 Not
used
08 Not
used
09 Cooling
anticipator
This item adjusts the tendency of the thermostat to run the cooling system to refresh and dehumidify the air
before the temperature rises to the desired cool setting. A setting of 0 will disable this feature.
0
No anticipation
3-5
Normal
anticipation
10
Maximum
anticipation
The recommended setting for most forced air cooling systems is 4. A lower number will decrease the tendency
to run the cooling system below the cooling setting. A lower setting of 2 or 3 may be desired in dry climates.
The default setting is 4.
10 Heating
anticipator
This item adjusts the tendency of the thermostat to turn the heating unit off before the desired heat setting is
reached. This is done to avoid overheating the air while the walls and furniture catch up. A setting of 0 will
disable this feature.