Homa TCM 6 Series Installation And Operation Instruction Manual Download Page 12

 

12 

 

  Clean out debris from the pit before lowering the pump 

into operation position. 

  Fit the coupling flange at the discharge of the pump. 

Make sure that the rubber profile-seal is properly fixed to 
the flange and will not fall off when the pump is lowered 
into the pit. Slide the guide bar of the coupling flange 
between the guide rails and lower the pump into the pit 
by means of a chain secured to the pump handle. When 
the pump reaches the auto-coupling base unit, it will 
automatically connect tightly. 

  Hang up the end of the chain to a suitable hook at the 

top of the pit. 

  Adjust the length of the motor cable, so that it is not 

damaged during the pump operation. Make sure that the 
cables are not sharply bent or pinched. 

7.3 Automatic Float Switch Control 
The pumps may be supplied with float switch level con-
trollers. They start and stop the pump according to the  
liquid level in the pit. 

The difference in level between start and stop must be 
adjusted by adjusting the free swinging length of the ca-
ble between the float switch and the cable fastening. 
Long cable end: Large difference in level.  
Short cable end: Small difference in level. 
The stop level must be adjusted in such a way, that the 
pump stops before the liquid level is lowered below the  
top of the pump volute. 

The start level must in any case be below the bottom of  
the liquid inlet pipe of the pit. 

The high alarm level, if a separate float switch for that is 
installed, should be adjusted approx. 10 cm above the 
start level, in any case it must be below the bottom of the 
liquid inlet pipe of the pit, so that the start level must be  
adjusted accordingly. 

Never place the float switch in the sump without fixing the 
float switch cable to a fixed point i the sump, because the 
float switch needs a rotation around the fixing point of the 
cable to operate without any problems. Non-observance 
may cause an overflow because the pump does not start 
running or a dry run of the pump in fact that the pump 
does not stop, which will destroy the pump. 
Note: Only the proper adjustement and fixing of the float 
switch cable will guarantee a reliable pump operation. Af-
ter any modification of the float switch adjustment the  
function must be checked by a test-run of the pump. 
 

8. Start-Up 

Never let the pump run dry for a long time of period, 

as it will destroy the pump (danger of overheating). 

Start the pump, when the system has been filled with 

liquid and vented. Open the isolating valves. Check the 
position of the float switches. If necessary, check the di-
rection of rotation of the pump, as described under 6.4. 
Put the switch on the control box to the required mode of 
operation. 
 

9. Maintenance and Repair 

In case of a defect of the pump, a repair shall be car-

ried out only by the manufacturer or through an author-
ized workshop. Modifications of the pump must be con-
firmed by the manufacturer. Only HOMA spare parts shall 
be used. 

In accordance with the product liability law we point 

out that we shall not be liable for damages caused by our 
product due to unauthorized repair by persons other than 
the manufacturer or an authorized workshop or due to the 
use of spare parts other than original HOMA parts. The 
same product liability limitations are valid for accessories. 

Before maintenance or repair disconnect the pump 

from the power supply to avoid accidental starting of the 
pump! 

Before maintenance or repair make sure that all rotat-

ing parts stand still! 

Before carrying out maintenance and service, the 

pump must be thoroughly flushed with clean water. Rinse 
the pump parts in clean water after dismanteling. 

At pump types with oil chamber an overpressure can 

escape with loosening of the oil chamber control screw. 
Screw only when pressure balance took place. 
 
Pumps running under normal operation conditions should 
be inspected at least once a year. If the pumped liquid is 
very muddy or sandy or if the pump is operating continu-
ously, the pump should be inspected every 1.000 operat-
ing hours. 
 
For long and trouble-free operation of the pump, following 
points should be checked regularly: 
 
- Nominal current (A): Check with amp-meter. 

- Pump parts and impeller: Check for possible wear.  
Replace defective parts. 

- Ball bearings: Check the shaft for noisy or heavy opera-
tion (turn the shaft by hand). Replace defective ball bear-
ings. A general overhaul of the pump is usally required in 
case of defective ball bearings or poor motor function. 
This work must be carried out by an authorized  
service workshop. 

- Cable entry: Make sure that the cable entry is watertight 
and that the cables are not bent sharply and/or pinched. 
 
Additionally at pump types with oil chamber: 
 
- Oil level and oil condition in oil chamber:  
Put the pump in horizontal position, so that the screw of 
the oil chamber is above (at larger pumps: one of both 
screws). Remove the screw and infer a small quantity of 
oil. The oil becomes greyish white like milk if it contains 
water. This may be the result of defective shaft seal.  
In this case leave the condition of the shaft seals by a 
HOMA Service to examine. 
 
The oil should be replaced after 3000 operating hours.  
Oil type: Shell Tellus C22, degradable HOMA-Atox (avail-
able on request). Used oil is to be disposed accordingly. 
 
Servicing Contract  
For a regular expert execution of all necessary mainte-
nance and inspection we recommend the conclusion of a 
servicing contract by our HOMA Service. Please contact 
our HOMA customer service. 
 
 

Summary of Contents for TCM 6 Series

Page 1: ...Montage und Bedienungsanleitung Installation and Operation Instruction Manual 01 2005 Baureihe Series TCV TCM...

Page 2: ...2 Inhalt Contents Seite 3 Page 9 Seite 15 Page 15 DEUTSCH ENGLISH Bauma e Dimensions...

Page 3: ...die Pumpentypen TCV TCM aufgrund Ihrer Konzipierung und Bauart sowie in der von uns in Verkehr gebrachten Ausf hrung den einschl gigen grundlegenden Sicherheits und Gesundheitsanforderun gen der EG Ma...

Page 4: ...eise und Vorschriften aus dieser Bedienungsanleitung nicht eingehalten werden nicht haften F r Zubeh rteile gelten die gleichen Be stimmungen 3 Einsatz und Technische Beschreibung 3 1 Einsatz der Pump...

Page 5: ...icklungen im Stern geschaltet f r eine Netzspannung von 400 V 3Ph Die Kabelenden U V W ber den Motorschutzschalter mit den Netzanschlussklemmen L1 L2 L3 zu verbinden 6 3 Temperaturf hler Die 1 Ph Moto...

Page 6: ...tandsdifferenz zwi schen Ein und Ausschaltpunkt l sst sich individuell be stimmen F r eine einwandfreie Funktion beachten Sie bitte die nachstehenden Hinweise Die Befestigungspunkte sowie die L nge de...

Page 7: ...zu entsorgen lf ll mengen siehe Tabelle auf Seite Wartungsvertrag Zur regelm igen fachm nnischen Durchf hrung aller notwendigen Wartungs und Kontrollarbeiten empfehlen wir den Abschluss eines Wartungs...

Page 8: ...d erfragen Sie bitte bei unserem 0 22 47 70 20 Kundendienst unter der Hotline f r Notf lle Telefonnummer 0 22 47 70 20 0 22 47 70 23 31 Auf das im beiliegenden Garantieschein beschriebene Produkt gew...

Page 9: ...bH Industriestrasse 1 D 53819 Neunkirchen Seelscheid hereby declare that in respect to their design and construction the following pump types in the form in which they are marketed by us conform to th...

Page 10: ...s used for cleaning or maintenance of swimming pools make sure that no persons stay in the swimming pool during operation of the pump and that the pump is reliable by a 30 mA earth leakage circuit bre...

Page 11: ...the direction of rotation is not cor rect With smaller pumps the direction of rotation may be checked by watching the start jek Put the pump vertical on the ground and lift one edge Start the motor V...

Page 12: ...ol box to the required mode of operation 9 Maintenance and Repair In case of a defect of the pump a repair shall be car ried out only by the manufacturer or through an author ized workshop Modificatio...

Page 13: ...terial defects or production defects Costs for removal and installation of the complained product at the installation place costs for the ride of the mechanicians to the location and from the installa...

Page 14: ...ichnung des Ersatzteiles 1 2 3 4 Ben tigte Menge 1 2 3 4 Lieferanschrift Unterschrift Firmenstempel 13 Order Sheet for Spare Parts To HOMA Pumpenfabrik GmbH D 53819 Neunkirchen Seelscheid Fax 49 22 47...

Page 15: ...in mm Typ type A B D E F G TCV 4 TCV 5 R 2 AG BSP 2 M 180 221 95 370 180 TCV 6 TCM 6 R 2 AG BSP 2 M 220 260 125 440 210 Schachtinstallation mit Kupplungssystem Submerged Installation with auto couplin...

Page 16: ...16...

Reviews: