HOLOPHANE LHD2 Series Quick Start Manual Download Page 4

9140053447 Rev. 0 

 

4

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

SELF-DIAGNOSTICS SYSTEM OPERATION 

(EMERGENCY OPERATION UNITS ONLY) 

 
Normal Power-Up Sequence

  

         At power-up, the red and green LED indicators will alternately flash for one to two seconds.  Next, the unit will go through a     
         “Power-Up Quick Test” with the green LED flashing quickly.  If no power-up faults were detected, the green LED will then   
         flash slowly for up to 36 hours to indicate that the battery is charging.  If any faults were detected during the “Power-Up  
         Quick Test”, these will be indicated by a flashing red LED indicator (see below for interpretation of flashing sequences).   
         The red LED may be accompanied by a buzzer.  This buzzer may be disabled by a short press of the test switch or by the  
         “SILENCE ALARM” button on the remote tester and will remain disabled for a period of 196 hours.  After the fault has been  
         corrected, the red LED flash and buzzer will be cleared automatically and the unit will return to normal operation except in  
         the case of lamp failure.  Once relamping has been completed, perform a manual test to clear the fault. 

Lamp Load Calibration  

         Once energized, the unit waits 36 hours while the batteries are charged and then performs a lamp load calculation  
         automatically only once during initial startup. The system will detect a load loss of 10% and indicate a lamp failure  
         of total load. Replace lamps as required. Upon lamp replacement, the system will return to normal operating status.   
         Manual Calibration: If, after installation and calibration, lamp load is increased or decreased the system will need to be   
         manually calibrated for the new total load. To re-calibrate, press the test switch four consecutive times. Lamp re-calibration  
         can also be accomplished with the optional remote control by pressing in sequence, 'Silence, Silence, Cancel, Silence'.  
         The lamps will illuminate for a period of 30 seconds during the calibration process and then the unit will return to normal    
         operation status.  Manual calibration can be performed at any time after 36 hours of charge or when the indicator status  
         light is solid green. 

Emergency Operation

  

         Emergency operation occurs when AC power fails.  The unit remains in this mode until AC power is restored.  During    
         emergency operation, both red and green LED indicators are disabled.  Upon restoration of AC power, the green LED will    
         flash for up to 36 hours to indicate that the unit is in battery charging mode. Allow 72 hours for the battery to fully charge. 

User Interface 

         Green LED Indicator 

 

Steady On – AC power is present and battery is fully charged 

 

Slow Flash – Battery charging 

 

Fast Flash – Unit is performing an automatic or manually initiated self-test 

 

         Red LED Indicator 

 

Single Flash – Battery fault 

 

Double Flash – Lamp failure 

 

Triple Flash – Charger fault 

 

Quad Flash – Emergency transfer failure  

         (If more than one fault condition is present simultaneously, the red LED will flash each fault pattern in sequence, and then   
          repeat) 

 

         Red and Green LED Indicators Together 

 

Slow flashing red and green – Low line voltage 

 

Fast flashing red and green – High line voltage 

 

         Pushbutton Test Switch 

 

Long Press (over 0.5 seconds) – Transfers unit to emergency (battery) operation as long as button is depressed 

 

Short Press – Initiates various self tests 

o

 

One Press – Cancel any self-test currently running 

o

 

Two Presses – Start 1 minute self-test 

o

 

Three Presses – Start 90 minute self-test 

o

 

Seven presses – Forces a complete system reset 

             (The unit will allow up to seven 1 minute tests during the first 24 hours of operation.  Allow at least 24 hours for battery   
               charging before performing any extended amount of testing) 

 

         Buzzer – Sounds in unison with the flashing red LED if a fault is detected.  May be disabled for up to 196 hours by a short   
         press of the test switch. 

 

         IR Receiver – Used with the optional hand-held IR remote tester to initiate or cancel manual testing. 

Reviews: