HOLOPHANE LHD2 Series Quick Start Manual Download Page 2

9140053447 Rev. 0 

 

2

 

                                                   Heads

 

 
 

 
Cover Screws (2) 

                  

 

 

                                                                                                                            

 

 

            

                                                        

                   
 

                                                                                          
                                                                               Enclosure 
  ¾” Hub                                                                         
                                                                                
                    Lens  Screws (4) 
                                                        
                                    

                                                                                                                           

 

 

                                                                                                              

         Vent

 

 

         

 

             

 

 
 

 

  

 

                               

IR receiver, AC/Charge status indicator, & Test switch

 

                                      
                                                                   

Figure 1     

                                                                                             

Figure 2

 

                                                           
 

INSTRUCTIONS – INSTALLATION 

1.

 

Mount exit enclosure to wall using (4) thru holes or optional mounting feet. (See Figure 3). 

2.

 

Remove cover screws (2) and open cover. (See Figures 1 and 2). 

3.

 

Dismount exit lens by removing lens screws (4). (See Figures 1 and 2). 

4.

 

Connect ¾” conduit supply to ¾” hub on unit. 

5.

 

Hookup AC service to the connector assembly as follows: 

 

  120 VAC OPERATION 

 

277 VAC OPERATION 

 Black 

Wire 

}

- 120V Line

 

Blue Wire 

}

- 277V Line 

 

Black Wire 

Blue Wire 

 

White Wire 

- Common 

White Wire 

- Common 

 

Green Wire 

- Ground 

Green Wire 

- Ground 

      Unused primary wire must be insulated individually to prevent shorting. 

6.

 

If Fire Alarm Flasher is used: 

a.

 

Connect WHITE wire to 24VDC Positive and 24VDC Negative 

b.

 

Use wire nuts for connection (not supplied). 

7.

 

Connect Battery connectors to the panel (See Figures 4 and 6). 

8.

 

Adjust head(s) as follows: (See Figure 3). 

a.

 

Rotation – Loosen head nut and rotate head to desired position. Retighten head nut. An antirotation screw has been 
provided to ensure proper rotation. 

b.

 

Angle – Loosen thumb screw passing through head swivel sufficiently to allow internal teeth to disengage. Position 
head to desired angle.  

c.

 

Retighten both head nut and thumb screw. 

CAUTION

 – 

ensure lamp heads are positioned so they are aimed below horizontal

 

9.

 

A dual load terminal block is provided for lamp hook-up. Ensure total wattage of heads, both unit mounted and remote (if 
applicable), does not exceed unit rating. Factory mounted lamps are wired to the terminal block at points L+ and L-. All 
remote loads should be wired to the terminal block at RL+ and RL- (See Figure 5). Use wire gauge that limits voltage drop to 
an acceptable level (See page 6). 

10.

 

Chevron labels with self-adhesive backing are supplied.  Apply label(s) to exit lens as necessary. 

11.

 

Remount exit lens using lens screws. Close cover and secure with cover screws. 

 