TERMINALS T01 TO T32 - MAIN CONTROLS
T01
Positive supply (+12Vdc or +24Vdc) input direct from fuse or circuit breaker.
T02
Positive supply output protected by 10A fuse on base PCB. For use, if required.
T03
To Emergency Stop push-button (Normally Close).
T04
To Emergency Stop push-button (Normally Close).
T05
To Common terminal of Auto - Manual - Test selector switch.
T06
To Auto terminal of Auto - Manual - Test selector switch.
T07
To Manual terminal of Auto - Manual - Test selector switch.
T08
To Test terminal of Auto - Manual - Test selector switch.
T09
To Manual Start push-button (Normally Open).
T10
To Manual Start push-button (Normally Open).
T11
To Mains Fail contact (selectable Normally Open or Normally Close).
T12
To Mains Fail contact (selectable Normally Open or Normally Close).
T13
To Bell Cancel push-button (Normally Open).
T14
To Bell Cancel push-button (Normally Open).
T15
To Alarm Reset push-button (Normally Close).
T16
To Alarm Reset push-button (Normally Close).
T17
Negative ( - ) supply input from battery.
T18
Negative ( - ) supply output. Internally connected to T17.
T19
Positive ( + ) supply output when Fault Monitor Relay trips. For use as master alarm or in
Building Automation System if required.
T20
Positive ( + ) supply output to external Energized Stop relay.
T21
Positive ( + ) supply output
to external Fuel Solenoid Relay (Energized Run relay).
T22
Positive ( + ) supply output to external Start relay (Crank relay).
T23
To Generator Run contact (Normally Open). From external 240VAC
AFR
relay.
Page 8
HOKKIM
giving you control
Control & Protection Relays
Summary of Contents for HAMF-4
Page 2: ...Page 2 HOKKIM giving you control Control Protection Relays ...
Page 3: ...Page 3 HOKKIM giving you control Control Protection Relays ...
Page 4: ...Page 4 HOKKIM giving you control Control Protection Relays ...
Page 5: ...Page 5 HOKKIM giving you control Control Protection Relays ...
Page 7: ...Page 7 HOKKIM giving you control Control Protection Relays ...