Service manual
22
T
T temp. up
T temp. down
TE7
Compressor off
Fan off
Compressor on
Fan on
TE8
TE9
Compressor on
Fan off
8.7.7 The louver opens to Standard Angle ANGLHEAT when power is on for the first time
8.8 Defrosting mode (available for heating mode)
8.8.1 Defrosting condition: Defrosting starts when either of the following &
:
A and B are satisfied:
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the following:
Calculate from the end of latest defrost, evaporator high temp. Protection only closes outdoor fan with the
Add up to 90 minutes.
e defrosting
time is 10 minutes. If item B is satisfied after item A, the defrosting time is 7.5minutes.
At condition , the defrosting time is 10 minutes.
After three times continuous 7.5-minute defrost, the fourth defrost time should be 10 minutes.
The circulation is as following:
compressor still running.
8.8.2
Defrosting
time
At condition , If item B is satisfied before item A, it would be regarded as severe frosting and th
7.5 minutes
defrost
7.5 minutes
defrost
7.5 minutes
defrost
7.5 minutes
defrost
8
es.
8
.8.3 Ending condition of defrosting
If one of following conditions is satisfied, end the defrost and turn into heating mode:
A. The defrost time has reached to 7.5 or 10 minut
B. The compressor current has reached to
I
DEFROST
or above,
I
DEROST
differs in different models
.8.4 Defrosting
Actions
Summary of Contents for HKEI-HCNI 263 G
Page 1: ...Cover HKEI HCNI 263 G HKEI HCNI 353 G HKEI HCNI 503 G HOKKAIDO SERVICE MANUAL ...
Page 10: ...Service manual 4 Refrigerant cycle diagram Cooling only Heat pump mode 7 ...
Page 12: ...Service manual 6 Wiring diagram HKEI HCNI 263 353 503 G Indoor Outdoor 9 ...
Page 13: ...Service manual 10 ...