- 15 -
Series 4 Models: “Wall” Type Top Class R32 Refrigerant AC
Operation
Lamp
Timer
Lamp
Display
Error Information
1 time
OFF
E0
Indoor unit EEPROM parameter error.
2 times
OFF
E1
Indoor / outdoor units communication error.
4 times
OFF
E3
The indoor fan speed is operating outside of the normal range.
5 times
OFF
E4
Indoor room temperature sensor T1 is in open circuit state or has short
circuit.
6 times
OFF
E5
Evaporator coil temperature sensor T2 is in open circuit state or has short
circuit.
7 times
OFF
EC
Refrigerant leak detected.
1 time
ON
F0
Overload current protection.
2 times
ON
F1
Outdoor ambient temperature sensor T4 is in open circuit state or has
short circuit.
3 times
ON
F2
Condenser coil temperature sensor T3 is in open circuit state or has
short circuit.
4 times
ON
F3
Compressor discharge temperature sensor TP is in open circuit state
or has short circuit.
5 times
ON
F4
Outdoor unit EEPROM parameter error.
6 times
ON
F5
The outdoor fan speed is operating outside of the normal range.
1 time
FLASH
p0
IPM malfunction or IGBT over-strong current protection.
2 times
FLASH
p1
Over voltage or too low voltage protection.
3 times
FLASH
p2
High temperature protection of IPM module.
5 times
FLASH
p4
Inverter compressor drive error.
6.2 General Troubleshooting
6.2.1 Error Display (Indoor Unit)
When the indoor unit encounters a recognized error, the indicator light (Operation Lamp) will flash in a correspon-
ding series, the timer indicator (Timer Lamp) may turn on or begin flashing, and an error code will be displayed.
These error codes are described in the following table.
For other errors:
The display board may show a garbled code or a code undefined by the service manual.
Ensure that this code is not a temperature reading.
Troubleshooting:
Test the unit using the remote control.
If the unit does not respond to the remote, the indoor PCB requires replacement.
If the unit responds, the display board requires replacement.