background image

E

 2005 Hoffman Enclosures Inc.

4

87567377

UNPACKING AND INSPECTION

Inspect the industrial air conditioner by checking for concealed damage that may have occurred

during shipment.  Look for dents, scratches, loose assemblies, evidence of oil, etc.  Any evident

damage upon receipt should be noted on the freight bill.  Damages should be brought to the

attention of the delivering carrier within 15 days of delivery, NOT to HOFFMAN ENCLOSURE

INC.  If damage is evident, save all packaging materials and request the carrier to inspect the

product prior to filing a claim with the carrier.

HOFFMAN ENCLOSURES INC. cannot accept responsibility for freight damages; however, we

are ready to assist you in any way possible.  For assistance, call or write:

Hoffman Enclosures Inc.

2100 Hoffman Way

Anoka, MN 55303

1745

(763) 422

2211

PRODUCT HANDLING

To avoid possible shipping damage and facilitate transportation and storage, the industrial air

conditioner may have been shipped in a vertical position.  If it is necessary to place the air

conditioner in a vertical position after removing from carton, be certain it is placed in an upright

(horizontal) or mounting position for a minimum of five (5) minutes before operating, in order to

allow the compressor oil to drain to the compressor sump area.

PRODUCT IDENTIFICATION

For installation and maintenance as outlined in this manual, first refer to the nameplate on your

unit.  The nameplate will provide important data regarding capacity of the unit, minimum and

maximum ambient operating temperatures, type and amount of refrigerant required for

recharging, and electrical power characteristics when making electrical hookups or connections.

CAUTION

NEVER attempt to operate the air conditioner while in any other position than the operat-

ing position.  Running the refrigeration compressor without oil in the lower part of the hous-

ing will cause permanent damage to the unit.  This also voids the warranty.

When ordering service parts, specify the catalog or job number and

serial number.

Before installing, make certain these parameters are met.  Lower

or higher ambient temperatures may cause permanent damage or

malfunction of the unit.

Before operating, make certain outlet and power source match

these requirements.

Refer to ”Design Data” (page 3) and label information for full load

amp rating and ”Wiring Schematic” (page 9) for specific model.

Follow all applicable electrical codes.

Leak test pressures.

Summary of Contents for PROLINE PAC216T64

Page 1: ...Industrial Air Conditioner PROLINE PROLINE Top Mount AC 2000 BTU HOUR Air Conditioners for PROLINE Electronic Enclosures 87567377 Rev C 113357 P N 11359799 E 2005 Hoffman Enclosures Inc ...

Page 2: ...trical requirements The standard air conditioning units are intended for indoor use in non corrosive atmospheres operating at ambient temperatures from 50 F 10 C minimum to 125 F 52 C maximum Operation outside this range without prior modification or approval from Hoffman Enclosures Inc will void the warranty For applications where the ambient will be below 50 F 10 C consult the factory CAUTION Re...

Page 3: ...4 2 3 6 4 2 3 6 4 2 3 6 50 60 50 60 50 60 50 60 50 60 50 60 50 60 50 60 115 230 230 230 230 115 115 115 592 x 400 792 x 400 792 x 400 792 x 400 792 x 400 592 x 400 592 x 400 592 x 400 23 31 x 15 75 23 31 x 23 61 31 19 x 15 75 31 19 x 23 61 PAC216T64 23 31 x 15 75 23 31 x 23 61 31 19 x 15 75 31 19 x 23 61 PAC226T64 PAC216T66 PAC226T66 PAC216T84 PAC226T84 PAC216T86 PAC226T86 PAC216T65 PAC226T65 PAC2...

Page 4: ...upright horizontal or mounting position for a minimum of five 5 minutes before operating in order to allow the compressor oil to drain to the compressor sump area PRODUCT IDENTIFICATION For installation and maintenance as outlined in this manual first refer to the nameplate on your unit The nameplate will provide important data regarding capacity of the unit minimum and maximum ambient operating t...

Page 5: ...h a thermostat If the thermostat is not set properly the condenser fan and compressor may not operate while the evaporator fan runs If this condition exists the entering air temperature to the evaporator may be below the thermostat setpoint To correct set the thermostat setting to a lower setpoint until the condenser fan and compressor start The compressor is provided with automatic reset thermal ...

Page 6: ... complete check all internal and external electrical clearances to ensure equipment will function safely and properly Hardware included with PROLINE frame Hardware included with PROLINE A C Optional hardware MOUNTING INSTRUCTIONS 1 Remove cover from PROLINE frame 2 Remove shroud from air conditioner Four bolts and washers at top of air conditioner Two screws in front flange 3 Place air conditioner...

Page 7: ...es may knowingly vent or otherwise release into the environment any class I or class II substance used as refrigerant REFRIGERANT LOSS Your air conditioner was thoroughly tested before leaving the factory to insure against refrigerant leaks Shipping damage or microscopic leaks not found with sensitive electronic refrigerant leak detection equipment during manufacturing may require repair and recha...

Page 8: ...d condenser coil CONTINUED OPERATION OF THE AIR CONDITIONER WITH A CLOGGED OR DIRTY FILTER WILL DAMAGE AND SHORTEN COMPRESSOR LIFE The air conditioner features an easily removable inlet filter to facilitate necessary cleaning FILTER CLEANING INSTRUCTIONS 1 Flush the filter with warm water from the exhaust side to the intake side DO NOT USE CAUSTICS 2 After flushing allow filter to drain Placing it...

Page 9: ...87567377 9 E 2005 Hoffman Enclosures Inc WIRING SCHEMATIC ...

Page 10: ...E 2005 Hoffman Enclosures Inc 10 87567377 ...

Page 11: ...ar from the date of purchase for the hermetic system components and the air moving devices when installed and operated under the following conditions A Maximum voltage variation no greater than plus or minus 10 of name plate nominal rating B Maximum frequency variation no greater than plus or minus 3 Hz of nameplate nominal rating C Must not exceed minimum and maximum stated temperatures on the na...

Page 12: ...Great Britain Schroff UK Ltd Maylands Avenue Hemel Hempstead Herts HP2 7DE 44 01442 240471 www schroff co uk Sweden Schroff Scandinavia AB Box 2003 12821 Skarpnäck 46 08683 61 00 www schroff se France Schroff Sas Z I 4 rue du Marais 67660 Betschdorf 33 03 88 90 64 90 www schroff fr Italy Schroff srl Viale Milano 119 21013 Gallarate Varese 39 0331 79 40 03 Singapore Hoffman Schroff Pte Ltd 01 68 71...

Reviews: