2005 Hoffman Enclosures Inc.
CONCEPT
®
Wall
−
Mounted Disconnect Enclosures
Installation Instructions for General Electric SCH
Flexible Cable Operating Mechanisms
TABLE 1
Sub
−
Panel Drilling
Cable Mechanism
Circuit Breaker
No. of Holes
Hole Size
X
Y
C
min
SCOM1A
E150
4
8
−
32
1.38
4.88
1.38
SCOM1EF
SE150
4
10
−
32
1.38
4.88
1.38
SCOM1EF
SF250
4
12
−
24
1.38
7.75
1.38
SCOM1G
SG600
4
12
−
24
1.81
7.75
1.84
SCOM1K
SK1200
4
5/16
−
18
2.75
14.25
2.75
TABLE 2
Bulletin
Hoffman Disconnect Enclosure Description
Enclosure Depth
C
H
CWY
CONCEPT
®
Wall Mounted Disconnect
8.00
3.85
CWY
CWSD
CONCEPT
®
Wall Mounted Disconnect
12.00
10.72
Step1
−
Determine disconnect hole pattern from Figure 3 GE and the above tables. See disconnect manufacturers
instructions for range of disconnect location based on cable length being used and depth of enclosure.
NOTE
−
Locate disconnect so appropriate wire bend space is provided for the line side wire size being used. Refer
to National Electrical Code Article 430
−
10b for wire bend space required.