CONCEPT

®

 Wall

Mounted Disconnect Enclosures

Installation Instructions for General Electric SCH

Flexible Cable Operating Mechanisms

TABLE 1

Sub

Panel Drilling

Cable Mechanism

Circuit Breaker

No. of Holes

Hole Size

X

Y

C

min

SCOM1A

E150

4

8

32

1.38

4.88

1.38

SCOM1EF

SE150

4

10

32

1.38

4.88

1.38

SCOM1EF

SF250

4

12

24

1.38

7.75

1.38

SCOM1G

SG600

4

12

24

1.81

7.75

1.84

SCOM1K

SK1200

4

5/16

18

2.75

14.25

2.75

TABLE 2

Bulletin

Hoffman Disconnect Enclosure Description

Enclosure Depth

C

H

CWY

CONCEPT

®

 Wall Mounted Disconnect

8.00

3.85

CWY

CWSD

CONCEPT

®

 Wall Mounted Disconnect

12.00

10.72

Step1

 

 Determine disconnect hole pattern from Figure 3 GE and the above tables.  See disconnect manufacturers

instructions for range of disconnect location based on cable length being used and depth of enclosure.

NOTE

 

 Locate disconnect so appropriate wire bend space is provided for the line side wire size being used.  Refer

to National Electrical Code Article 430

10b for wire bend space required.

RSPSupply  -  1-888-532-2706 -  www.RSPSupply.com

http://www.RSPSupply.com/p-16178-Hoffman-CDSC24268LG-CONCEPT-Steel-Disconnect-Enclosure.aspx

Summary of Contents for CONCEPT CDSC24268LG

Page 1: ...CWY painted steel Or Hoffman Bulletin CWSD stainless steel CONCEPT Wall Mounted Disconnect Enclosures 87568832 Rev B 113357 P N 64323101 2005 Hoffman Enclosures Inc RSPSupply 1 888 532 2706 www RSPSu...

Page 2: ...eing installed See installation instruction index above for appropriate panel drilling instructions Additional holes may be required when using fused switches See disconnect manufacturers instructions...

Page 3: ...must be turned and held 90 counter clockwise While holding the screwdriver slot the handle may be turned clockwise thus opening the enclosure door To close the door push door to the closed position a...

Page 4: ...nclosures Installation Instructions for Allen Bradley 1494V variable depth Disconnects Figure 3 E 4 75 for 8 00 Deep E 11 62 for 12 00 Deep RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSuppl...

Page 5: ...st Do Not Install 11 54 1 38 1 25 7 25 1 38 1 25 69 2 03 10 62 201 1 4 20 UNC 1494V M60 for 70 400 AMP West Do Not Install 10 48 1 72 1 78 8 44 1 72 1 78 86 1 16 10 75 201 1 4 20 UNC See A B Instructi...

Page 6: ...p Figure 3 Hole Pattern For Disconnect Switch Size C361NC C361SC 30 AMP C361ND C361SD 60 AMP C361NE C361SE 100 AMP C361NF C361SF 200 AMP Hole Pattern For Circuit Breaker Frame Size HMCP FS FH EHD FDB...

Page 7: ...0A 11 34 3 13 7 25 1 38 31 6 95 2 75 10 32 UNF HMCP 250A 11 34 3 13 7 25 1 38 31 6 95 2 75 1 4 20 UNC KH KS DK KDB KD HKD KDC 400A Do Not Install 10 91 2 96 8 44 1 72 31 6 95 3 18 1 4 20 UNC HMCP 400A...

Page 8: ...s Installation Instructions for General Electric Type STDA Variable Depth Operating Mechanisms Figure 3 E 4 75 for 8 00 Deep E 11 62 for 12 00 Deep RSPSupply 1 888 532 2706 www RSPSupply com http www...

Page 9: ...75 SDOM1A SDOM1AP TB1 TEC TECL 4 1 4 20 2 22 9 09 75 3 00 6 75 TDOM3 TFJ TFK 4 1 4 20 9 09 1 69 2 75 10 88 TDOM4 JFRAME 4 1 4 20 D N t I t ll 8 47 1 63 5 50 8 63 TDOM5 TB4 TJH 4 1 4 20 Do Not Install...

Page 10: ...onnect Enclosures Installation Instructions for Square D 9422 Variable Depth Operating Mechanisms E 4 75 for 8 00 Deep E 11 62 for 12 00 Deep RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSup...

Page 11: ...1 47 1 18 3 94 RN1 4 1 2 3 4 8 32 3 38 10 25 1 38 1 50 5 13 RP1 4 1 2 3 4 10 24 3 38 10 25 1 56 1 50 7 13 RR 1 4 1 2 3 4 1 4 20 D N t I t ll 9 59 19 6 63 6 56 RR 1 4 1 2 3 4 375 Dia Do Not Install 8...

Page 12: ...ll Mounted Disconnect Enclosures Installation Instructions for Cutler Hammer C371 Flex Shaft Flexible Cable Operating Mechanisms RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 161...

Page 13: ...T Wall Mounted Disconnect 8 00 3 85 CWY CWSD CONCEPT Wall Mounted Disconnect 12 00 10 72 Step1 Determine disconnect hole pattern from Figure 3 CHand the above tables See disconnect manufacturers instr...

Page 14: ...PT Wall Mounted Disconnect Enclosures Installation Instructions for General Electric SCH Flexible Cable Operating Mechanisms RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 16178 H...

Page 15: ...nnect Enclosure Description Enclosure Depth C H CWY CONCEPT Wall Mounted Disconnect 8 00 3 85 CWY CWSD CONCEPT Wall Mounted Disconnect 12 00 10 72 Step1 Determine disconnect hole pattern from Figure 3...

Page 16: ...d Disconnect Enclosures Installation Instructions for Siemens I T E Max Flex Flexible Cable Operating Mechanisms Figure 3 ITE RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 16178...

Page 17: ...9 75 2 50 FHOLM036 4 1 4 20 2 50 9 75 2 50 These mechanisms include 36 operating cables If longer cables are needed order I T E components separately TABLE 2 Location of Disconnect Operating Handle Bu...

Page 18: ...ONCEPT Wall Mounted Disconnect Enclosures Installation Instructions for Square D 9422 Flexible Cable Operating Mechanisms RSPSupply 1 888 532 2706 www RSPSupply com http www RSPSupply com p 16178 Hoff...

Page 19: ...n which vary for 36 60 and 120 cable lengths See Square D instructions for relationship between 1 4 20 and 375 diameter holes for LA circuit breaker TABLE 2 Bulletin Hoffman Disconnect Enclosure Descr...

Page 20: ...HP2 7DE 44 01442 240471 www schroff co uk Sweden Schroff Scandinavia AB Box 2003 12821 Skarpn ck 46 08683 61 00 www schroff se France Schroff Sas Z I 4 rue du Marais 67660 Betschdorf 33 03 88 90 64 90...

Reviews: