background image

2

Mode Jumper Diagram Figure 1

NON-Heat Pump Applications

For 

NON

-Heat  Pump  System  applications,  the  jumper  tab 

should be in the 

"DA"

 position as shown in Figure 1 for proper 

operation.

NOTE:

 If the jumper tab is in the "RA" position for NON-

Heat Pump applications, the condenser fan motor will operate at 
full speed and will not modulate.

A selectable span of 25ºF or 30ºF is available (see 

Figure 1

).  

The 25ºF span is recommended for high efficiency units while the 

30ºF span is recommended for older lower efficiency units.

The Range Adjust potentiometer provides 50ºF-80ºF up to 70ºF-

100ºF for the 30ºF span.  The 25ºF span provides for adjustments 

from 55ºF-80ºF up to 75ºF-100ºF.  Markings are in 5ºF increments.  

Typically TXV devices should be set at full CCW or at the second 

mark.  Orifice or Cap Tube devices should be set at the 4th or full 

CW markings.  These positions should provide adequate control of 

head  pressure  for  the  specific  device  being  used.   The  lower  range 

adjust positions will allow control to a lower ambient.  Conversely, 

the higher range adjust positions will provide control only to a higher 

ambient. Factory Range Adjustment is set at 50ºF-80ºF.

CAUTION: It is not recommended that the range adjust be set 

to satisfy a selected head pressure.  These various range adjustments 

are  provided  to  ensure  proper  ambient  control  when  the  system  is 

properly  charged  (no  vapor  in  the  sight  glass),  filters  and  coils  are 

clean, and an air flow of 400 cfm/ton is available for delivery in the 

HVAC  system.    In  refrigeration  application,  consult  factory  or  see 

Engineering Bulletin for “Low Ambient Refrigeration Applications.”

Liquid Line Sensor

•  Install Sensor(s) to the top of liquid line where the line exits the 

condenser coil (refer to 

Figure 2

). If two compressors (circuits) 

are used, a second Sensor is required for the second refrigerant 

circuit. (Part Number 100-0017-001.)

•  Use the special tape provided to secure the Sensor to the liquid 

line. Stretch the tape slightly, as you wrap the tape around the 

sensor and liquid line. Use all the tape, lapping the Sensor. 

•  Firm, mechanically clean, contact is required between the metal 

tab of the Sensor and the liquid line.  When using one sensor, 

always use the control's 

S1

 and 

COM

 terminals.

• 

DO NOT

 use tie wraps or hose clamps to secure sensor to 

liquid line. Sensor element will break.

•  Connect the Sensor(s) wires to the Sensor input terminals.
•  Additional insulation of the taped sensor and adjacent refrigerant

line back to condenser header is required in extremely cold ambients 

(+20º F).

������������������
�������������������
���������������������
�����������������������
���������������

Sensor Diagram Figure 2

1

Checkout Procedure

Step 1

With power disconnected and the Controller wired:

1.

  Measure the ohms across the Control's terminals “#1” and 

“#2” using an ohm meter.

2.

  For single condenser applications; if you read 1 ohm or less 

(115V AC operating voltage), or 5 ohms or less (208V AC or 

greater operating  voltage), the controller is improperly wired.

CAUTION

Correct wiring error(s). Do not apply power if

incorrect ohm  values were measured during para-

graph 2, above. (The load is shorted; applying power

will destroy the controller.)

Step 2

With  the  compressor  disabled,  set  thermostat  for  cooling 
demand  and  apply  voltage  to  the  unit.  Condenser  fan  will 
start if liquid line temperature is 3º above the low ºF value 
selected using

selected

selected

 the Span jumper and Range Adjuat pot.

 using

 using

1.

  Monitor liquid line temperature (°F) and condenser motor 

voltage and current.

2.

  Verify that the motor is operating properly for temperature 

sensed.  Depending on the Range Adjust position, when the 

sensor temperature at “start up” is:

a.

Below Selected Span and Range Minimum,

depending on where the range adjust is set, the motor(s)

will not start.

b.

Within Selected Span and Range,

 the motor(s) will

start at full speed for a few seconds and immediately

modulate to a reduced speed proportional to the tempera-

ture sensed when the temperature is 3

°

F

 above the low end 

of the 

range adjust.

........................................................................  .

Continued on page 4

��

��

����

��

���

���

816-10DH Span

Range Adjust Pot

Sensor Installation

Summary of Contents for 816-10DH

Page 1: ... by the Installer Service Technician General CAUTION Failure to read and understand the accompa nying instructions and diagrams or failure to complete the Checkout Procedure prior to energizing the Control may result in permanent damage to the Control The 816 10DH Controller requires the installation of an addi tional line voltage to 24VAC transformer VAC transformer V 10VA minimum This additional...

Page 2: ...ure the Sensor to the liquid line Stretch the tape slightly as you wrap the tape around the sensor and liquid line Use all the tape lapping the Sensor Firm mechanically clean contact is required between the metal tab of the Sensor and the liquid line When using one sensor always use the control s S1 and COM terminals DO NOT use tie wraps or hose clamps to secure sensor to liquid line Sensor elemen...

Page 3: ...MOTOR GND 4 IF REQ LINE Microprocessor Controller S2 S1 COM Wiring Diagram for the 816 10DH Figure 4 3 50 55º 80 70 75º 100 Range Adjust Min Speed LOAD LINE 24VAC Faster Sleeve Slower Ball HPGND Span H P Model 816 10DH Featuring Range Span Adjust 30º 25º DA RA HP24V www hoffmancontrols com C 10 Amps 115 208 230 460 600 VAC 50 60 Hz Hoffman Controls 1 2 3 4 MOTOR GND 4 IF REQ LINE Microprocessor Co...

Page 4: ...ower to the unit observe operation 3 Verify operation as described above by monitoring liquid line temperature and observing motor speed Troubleshooting Guide 1 Check wiring review instructions 2 Additional 24 VAC transformer needed See GENERAL section instructions 3 Normal operation 4 Motor protected 5 Check Heat Pump Mode Jumpers DA and RA 1 Check wiring review instructions 2 Replace control 3 C...

Reviews: