Figure 3
Figure 2
Shut Off Valve Leak Check:
6.) If no leaks are detected then replace backflow preventer and proceed to back fill hydrant with soil.
SEAL, O-RING
21O17OOO2
Figure 4
Remove backflow preventer at quick disconnect (Figure 2)
Operate hydrant at partial flow with thumb over outlet until the
water pressure forces past thumb. (Figure 3).
At this point shut off hydrant.
[ With hydrant full of water it is easier to detect if hydrant is leaking. Hydrant
should not drip from outlet once hydrant is full of water. ]
If hydrant leaks from outlet, remove operating rod and replace o-ring on stopper tip. (Figure 4)
GROUND
LEVEL
BURY
DEPTH
27”
FROST
LINE
Figure 1
1.)
2.)
Hydrant canister must be placed below existing frost line. Figure1
5.)
No ground preparation is required for the Freeze Flow Sanitary Yard Hydrant; therefore
it can be placed in any soil condition. Hydrant canister is stainless steel and pipes are
all galvanized steel, which meet ASTM specs.
4.) Attach hydrant to existing supply line using an approved thread sealant.
3.) Flush supply lines BEFORE installing hydrant.
It is still the responsibility of the installer to know his/her soil condition and to ensure that
proper corrosion protection is administered to the hydrant. The application of paint or
rubber tape may be needed to protect against some soil conditions.
BEFORE back filling with soil, perform a Shut Off Valve Leak Check to make sure shut
off valve does not leak due to debris in supply line or damaged o-ring. A leaking seat
can cause hydrant to fill with water and possibly freeze.
INSTALLATION
Freeze Flow hydrants are designed for heavy-duty commercial use where safe potable
water is needed. This hydrant drains into the canister below the frost line to prevent
freeze ups and cross contamination with the soil bacteria
Sanitary Yard Hydrant
Installation Instructions