Hoeptner Freeze Flow Sanitary Yard Hydrant Installation Instructions Download Page 1

Figure 3

Figure 2

Shut Off Valve Leak Check:

6.)  If no leaks are detected  then replace backflow preventer and proceed to back fill hydrant with soil.

SEAL, O-RING

21O17OOO2

Figure 4

Remove backflow preventer at quick disconnect (Figure 2) 

Operate hydrant at partial flow with thumb over outlet until the 

water pressure forces past thumb.  (Figure  3).   

At this point shut off hydrant.

 [ With hydrant full of water it is easier to detect if hydrant  is leaking.  Hydrant 

    should not drip from outlet once  hydrant is full of water.  ]

If hydrant leaks from outlet, remove operating rod and replace o-ring on stopper tip. (Figure 4) 

GROUND

LEVEL

BURY

DEPTH 

27”

FROST

 LINE

Figure 1

1.) 
2.)

Hydrant canister must be placed below existing frost line. Figure1

5.)

No ground preparation is required for the Freeze Flow Sanitary Yard Hydrant; therefore 

it can be placed in any soil condition.   Hydrant canister is stainless steel and pipes are 

all galvanized steel, which meet ASTM specs.

4.) Attach hydrant to existing supply line using an approved thread sealant.

3.) Flush supply lines BEFORE installing hydrant.

 It is still the responsibility of the installer to know his/her soil condition and to ensure that 

proper corrosion protection is administered to the hydrant. The application of paint or 

rubber tape may be needed to protect against some soil conditions.

BEFORE back filling with soil, perform a Shut Off Valve Leak Check to make sure shut 

off valve does not leak due to debris in supply line or damaged o-ring.  A leaking seat 

can cause hydrant to fill with water and possibly freeze. 

INSTALLATION

Freeze Flow hydrants are designed for heavy-duty commercial use where safe potable

water is needed. This hydrant drains into the canister below the frost line to prevent

freeze ups and cross contamination with the soil bacteria

Sanitary Yard Hydrant

Installation Instructions

HOEPTNER  PERFECTED PRODUCTS