background image

�  HCCHIKI  CORF'CRATION 

INSTALLATION  INSTRUCTIONS  FOR HOCHIKI  SMOKE  DETECTOR TYPE:SLV 

INTRODUCTION 

Photoelectric Type Smoke Detector:SLV-AS(AS7240-7) 

SLV-C (GB4715-93) 

SLV-E(J)(EN54-7:2000) 

Base:YBN-R/4C,YB0-R/4A,YBO-R/4C 

Other combinations of detector and base are also possible. 
Please confirm  with  Hochiki or the appointed sales agent. 

Ensure that the following  items are observed before installation and maintenance.  Hochiki cannot 

warrant  a detector's performance if such items are neglected. 

CAUTION 

1.This detector  is used to detect only smoke and cannot detect temperature or other phenomena.

2.This detector cannot be used to prevent 

FIRE 

itself, it is only intended to detect a certain characteristic of

fire.

3.When installing this detector, ensure that the location of each detector has been planned in accordance

with  appropriate  local and National Fire  Regulations or recommendations.

4.The  detector shall not be installed in  the following environmental conditions:

Situations in which condensation exists. 
Situations in which corrosive gas

_

es exist. 

Situations  in which dust or steam exist. 

Situations in which obstacles exist, which could impede airflow to the detector. 

5.Certain  actions can cause permanent damage to the detector and therefore if the detector is subjected to

any of the following actions it should not be used:

Disassembly and reassembly. 

Impact or shock. 

6.The  detector is expected to be used to detect only one real fire  situation and could suffer damage during

a fire condition. It should therefore be  replaced  if  damaged  during a  fire  or at any other time.

7.After installation, all detectors on the fire alarm system should be tested to verify correct operation.

8.lnstallation and maintenance should only be carried out by suitably trained personnel.

9.The detector must be subject to periodic maintenance during regular service visits,  which should be as

recommended by appropriate local and National Standards or recommendations.  In the event of no such

Standards existing,  Hochiki recommend that the minimum period of maintenance should  be 1 year and

that the following items should be taken into account:

In case where there is an excess build-up of dust on the insect screen, the sensitivity  of the 
detector could be affected. 

A  regular operational test should be performed. 

A  visual check for staining and mechanical damage. 

10.Detector operation should not be verified by the use of a naked flame or open fire. Operation should only

be checked by  equipment that is capable of exceeding the required detection threshold by small  amount,

sufficient to guarantee a fire  signal is produced by the detector.

Reviews: