Notes 

1.  

The electrical circuit in the hazardous area must be capable of withstanding an a.c. test voltage of 500 volts to earth or 
frame of the equipment, for a period of one minute without breakdown. 

2.  

The installation must comply with National requirements. 

3.  

The system must be marked with a durable label which should appear on or adjacent to the principal item of electrical 
apparatus in the system or at the interface between the intrinsically safe and non-intrinsically safe circuits.  This 
marking shall include the word SYST or SYSTEM, for example “System No. BAS Ex 98D2264” or “BAS No. Ex 
98D2264 SYST”. 

A. Unspecified equipment except that no voltage shall exceed 250V with respect to earth. 

B. EITHER:  

Any BASEEFA Certified shunt safety Zener Diode Barrier with the following parameters: 

‰

 

 

30V or less 

‰

 

 200mA 

or 

less 

‰

 

 1W 

or 

less 

The barrier earth must be connected via a high integrity connection, using an insulated conductor equivalent to a 4mm

2

 copper 

conductor, such that the impedance from the point of connection to the main power system earth is less than 1 ohm. 

OR:  

Any one channel from the following BASEEFA Certified Galvanic Isolators: 

Type Number 

Um=250V 

I.S. Output 

Certificate No. 

MTL 3043 

2-3 

5/6-7/8   

Ex86B2285 

MTL 40612Channel 

9-8 or 12-11 

1/2-3 or 4/5-6   

Ex94C2040 

MTL 5061 2Channel 

9-8 or 12-11 

1/2-3 or 4/5-6 

Ex96D2426 

MTL5561 2 Channel 

9-8 or 12-11 

1/2-3 or 4/5-6 

BASEEFA09ATEX0027 

P&F KFD0-CS-Ex1.51 

11-12 

1-2 

Ex96D2152 

P&F KFD0-CS-Ex2.51 

11-12 or 9-8/10 

1-2 or 4-5 

Ex96D2152 

P&F KFD0-CS-Ex1.51P 

11-12 

1-2 

Ex96D2152 

P&F KFD0-CS-Ex2.51P 

11-12 or 9-8/10 

1-2 or 4-5 

Ex96D2152 

Note: Earthing requirements as described above for Zener Diode Barriers, is not required with Galvanic Isolators. 

 

 

C. Up to 20 SLR-E-IS Intrinsically Safe Photoelectric Smoke Detectors complete with YBN-R/4 IS Bases, BASEEFA

Certificate 

BAS01ATEX1281 

OR: 

Up to 20 DCD-1E-IS Intrinsically Safe Heat Detectors complete with YBN-R/4 IS Bases, BASEEFA

Certificate No 

BAS01ATEX1021 

OR: 

A combination of each type to a maximum of 20 units. 

D. End-of-line resistor.  The end-of-line resistor must have a body surface area of 230mm

2

 or more. 

E. Optional Remote Indicator consisting of Light Emitting Diode (LED)

only.  The LED must have a surface area of 230mm

2

 or 

more.  The interconnecting cable to any Remote Indicator(s) is to be considered as part of the interconnecting cable described 
at G below. 

F. Optional interconnection for sharing a single Remote Indicator between any number of SLR-E-IS or  

DCD-1E-IS/YBN-R4/IS Detector/Base combinations as shown above.  The terminal 4 in each base may be interconnected as 
shown at F above and a single Remote Indicator connected to any one such base.  The interconnecting cable between any 
terminals 4 and the wiring to any Remote Indicator is to be considered as part of the interconnecting cable described at G 
below. 

G. Interconnecting cable having the following maximum parameters: 

Group 

Capacitance 

C  

µF 

Inductance 

mH 

Inductance to Resistance ratio 

L/R 

µH/ohm 

IIC 0.07 

0.62 

36 

IIB 0.56 

1.86 

146 

IIA 1.82 

4.96 

286 

H. Optional cable screen.  If used, this must only be connected to earth within the safe area and must be isolated from the 
electrical circuit and must be capable of withstanding an a.c. test voltage of 500 volts for a period of one minute without 
breakdown. 

J. Up to 20 optional devices, for example switches such as manual call points having appropriate BASEEFA Certification for 
use in the intended hazardous environment (Hochiki part no. CCP-IS) or otherwise classified as simple apparatus according to 
BS EN 60079-11:2007.  Such devices may be fitted with a resistor in series with the switch and /or an end-of-line resistor as 
per D above.  Where such a resistor is used it must have a body surface area of 230mm

2

 or more (typical resistance 470 - 680 

ohm). 

 

 
 