Hochiki HF-24 UV Flame Detector – Installation Manual
9
Detector to Detector Distance
In mounting more than one detector, the value of ‘R’ shown below is determined
according to the detectable area mentioned in 2.2.
Performance Check
Approximately one second after the power supply is switched on, the
detector which has been mounted reaches its’ normal operating condition
Make flames within the detectable area using a candle or a lighter and
confirm that an alarm is produced within 5 to 30 seconds in the area
approximately 3m apart from the sensor
The flame of a candle or a lighter should satisfy the requirements shown
below
Performance tests should be carried out in the area specified below
©
1995 Hochiki Europe (UK) Ltd DS0204/ISS1/DEC95